INSP-Sprinkler Rough-in/Hydro | 6/27/2003 | 6/27/2003 | 6/27/2003 | A | PASS |
Troy Cobbley
|
|
|
|
DOC - Permit Finaled | 6/27/2003 | 6/27/2003 | 6/27/2003 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 6/27/2003 7:26:02 AM
|
INSP-Final Inspection | 4/8/2003 | 4/9/2003 | 4/9/2003 | A | FAIL |
Troy Cobbley
|
|
|
I could not final project due to outstanding fire alarm plan issues. As for life safety the exit sign at the main exit needs repaired and door hardware for two group/offices near the main exit need approved hardware installed. They consist of double doors with manual flush bolts. Two existing fire extinguisher cabinets are mounted too high but contractor has letter from city giving approval to leave them at current hight. 4/9/2003 11:03:35 AM
|
INSP-Final Inspection | 4/9/2003 | 4/9/2003 | 4/9/2003 | A | PASS |
Troy Cobbley
|
|
|
Fire sprinklers finaled
|
Sprinkler Plan Check | 3/5/2003 | | 3/17/2003 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/17/2003 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 3/17/2003 | | 3/17/2003 | | DONE |
|
|
|
|
Telephone call | | | 3/17/2003 | | DONE |
|
|
|
permit ready and fees due
|
Issue and Print Permit | | | 3/17/2003 | | DONE |
|
|
|
|
Plan resubmittals received | | | 3/4/2003 | | DONE |
|
|
|
To Bill Alexander
|
INSP-Final Inspection | 2/27/2003 | 2/28/2003 | 2/28/2003 | A | FAIL |
Troy Cobbley
|
|
|
The city approved sprinkler plans show a maximum spacing of 148 square feet in the conference room 009 and the lobby 002. The sprinkler pendants as installed exceed this. One sprinkler upright has a bent deflector and needs replacing 2/28/2003 3:02:02 PM
|
Inspection Record Card- Fire | 1/30/2003 | | 1/30/2003 | | DONE |
|
|
|
|
Telephone call | | | 1/30/2003 | | DONE |
|
|
|
permit ready and fees due
|
Issue permit | | | 1/30/2003 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 1/24/2003 | | 1/30/2003 | | DONE |
|
|
|
1/30/2003 09:46:06 JWA - activity updated through activity FIRA22 from case FIR03-00034.
|
Sprinkler Plan Check | 1/24/2003 | | 1/30/2003 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/30/2003 | | DONE |
Bill Alexander
|
|
|
|
Application received | | | 1/24/2003 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|