INSP-Final Inspection | 4/21/2003 | 4/21/2003 | 4/21/2003 | P | PASS |
Rick Jackson
|
|
|
gauge installed; called Dave Brown (SLRMC Building Services) and told him that this permit will be closed out 4/21/2003 1:50:01 PM
|
DOC - Permit Finaled | 4/21/2003 | 4/21/2003 | 4/21/2003 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 4/21/2003 1:50:06 PM
|
INSP-Sprinkler Rough-in/Hydro | 4/7/2003 | 4/17/2003 | 4/17/2003 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 4/7/2003 at 3:00:33 PM. Contact: ###-####. flow test okay; need gauge on south stair standpipe 4/17/2003 2:36:15 PM
|
Issue and Print Permit | | | 3/5/2003 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 1/29/2003 | | 3/4/2003 | | DONE |
Bill Alexander
|
|
|
3/4/2003 11:55:43 JWA - activity updated through activity FIRA22 from case FIR03-00040.
|
Sprinkler Plan Check | 2/19/2003 | | 3/4/2003 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/4/2003 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 3/4/2003 | | 3/4/2003 | | DONE |
|
|
|
|
Telephone call | | | 3/4/2003 | | DONE |
|
|
|
###-#### john
|
Inspection Record Card- Fire | 3/4/2003 | | 3/4/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/4/2003 | | 3/4/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/4/2003 | | 3/4/2003 | | DONE |
|
|
|
|
Application received | | | 2/19/2003 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 2/19/2003 | | 2/19/2003 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/19/2003 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 1/29/2003 | | 1/31/2003 | | FAIL |
Bill Alexander
|
|
|
a. The calculations provided verified the supply available with the minimum demand for Light and OH. But adjusted City Water to the pump inlets should be adjusted up and not down, since the pump is lower than the supply in this facility! This installation shall be carefully engineered, taking into consideration the water supply and all water demands, the characteristics of the particular pressure-reducing valve installing, including verification that the valve is capable of regulating water pressure from "0", very low flow, to the maximum flow demands set upon the device. Designer must prove a single head operation, to the maximum demand calculated (reference item "e" below.
b. Complete data submittals on the PRV, which includes rated flow charts, installation requirements with its intended approved application usage verifying the regulating of water in all applicable flow conditions are required.
c. Designer/Engineer must include clear, precise and details plans of all work incorporating, including details in the added control valve required per NFPA 13:5-14.1.2.4, tamper supervision per UFC 1003.3 and whatever is required to verify minimum code compliance with the installation.
d. Provide drain valve/s and piping meeting the minimum requirements of NFPA 13:5-14.2.4.2, 5-14.2.4.3, which shall be included on plans as addressed in Item "c" above.
e. Calculations provided are for the verification of light hazard protection on the 4th floor and OH-1 protection in the basement. No verification provided of the standpipe system demand and minimum pressures required in meeting NFPA14:5-9.1.1, 5-7, shown attached to this piping. If the piping is not attached to the fire sprinkler piping, how the PRV will be flow tested?
|
Miscellaneous action | | | 1/31/2003 | | DONE |
|
|
|
Returned plans and calculations (5 each) to the front desk for calling and returning.
|
Telephone call | | | 1/31/2003 | | DONE |
|
|
|
Plans failed called to return.
|
Telephone call | | | 1/31/2003 | | DONE |
|
|
|
Faxed copy of review.
|
Application received | | | 1/29/2003 | | |
|
|
|
|