Permit Information
Permit NumberFIR03-00040
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 190 E BANNOCK ST
Project NameSPR EAST TOWER EXP CODE UPGRAD
Customer Number 
ePlanReview 
Description
(St. Luke's ED/NICU East Tower- Code Verification) 03/04/2003 - PORV valve removed and 6" tied into "Low Pressure" system. This permit is to verify the Code compliance of the installation of a Pressure Reducing Valve on the 6" supply main feeding the East Tower Expansion building built and finaled under BLD00-00361 with sprinkler work permitted under FIR01-00323. This valve was installed by an issued change order request to De Best Fire Protection, and installed without permit review or approval, which includes the valve itself; it's related appurtenance/devices, required flow testing and recalculation of affected remote areas for system verification. This fire sprinkler system work shall comply with NFPA 13-1999, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is not attached to any building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/21/20034/21/20034/21/2003PPASS
DetailsRick Jackson
gauge installed; called Dave Brown (SLRMC Building Services) and told him that this permit will be closed out 4/21/2003 1:50:01 PM
DOC - Permit Finaled4/21/20034/21/20034/21/2003PPASS
DetailsRick Jackson
Finaled by inspector at 4/21/2003 1:50:06 PM
INSP-Sprinkler Rough-in/Hydro4/7/20034/17/20034/17/2003PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 4/7/2003 at 3:00:33 PM. Contact: ###-####. flow test okay; need gauge on south stair standpipe 4/17/2003 2:36:15 PM
Issue and Print Permit  3/5/2003 DONE
Plan assigned to (Bill)1/29/2003 3/4/2003 DONE
DetailsBill Alexander
3/4/2003 11:55:43 JWA - activity updated through activity FIRA22 from case FIR03-00040.
Sprinkler Plan Check2/19/2003 3/4/2003 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  3/4/2003 DONE
DetailsBill Alexander
Inspection Record Card- Fire3/4/2003 3/4/2003 DONE
Telephone call  3/4/2003 DONE
###-#### john
Inspection Record Card- Fire3/4/2003 3/4/2003 DONE
Inspection Record Card- Fire3/4/2003 3/4/2003 DONE
Inspection Record Card- Fire3/4/2003 3/4/2003 DONE
Application received  2/19/2003 DONE
Plan assigned to (Bill)2/19/2003 2/19/2003 DONE
Plan resubmittals received  2/19/2003 DONE
DetailsBill Alexander
Sprinkler Plan Check1/29/2003 1/31/2003 FAIL
DetailsBill Alexander
a. The calculations provided verified the supply available with the minimum demand for Light and OH. But adjusted City Water to the pump inlets should be adjusted up and not down, since the pump is lower than the supply in this facility! This installation shall be carefully engineered, taking into consideration the water supply and all water demands, the characteristics of the particular pressure-reducing valve installing, including verification that the valve is capable of regulating water pressure from "0", very low flow, to the maximum flow demands set upon the device. Designer must prove a single head operation, to the maximum demand calculated (reference item "e" below.
b. Complete data submittals on the PRV, which includes rated flow charts, installation requirements with its intended approved application usage verifying the regulating of water in all applicable flow conditions are required.
c. Designer/Engineer must include clear, precise and details plans of all work incorporating, including details in the added control valve required per NFPA 13:5-14.1.2.4, tamper supervision per UFC 1003.3 and whatever is required to verify minimum code compliance with the installation.
d. Provide drain valve/s and piping meeting the minimum requirements of NFPA 13:5-14.2.4.2, 5-14.2.4.3, which shall be included on plans as addressed in Item "c" above.
e. Calculations provided are for the verification of light hazard protection on the 4th floor and OH-1 protection in the basement. No verification provided of the standpipe system demand and minimum pressures required in meeting NFPA14:5-9.1.1, 5-7, shown attached to this piping. If the piping is not attached to the fire sprinkler piping, how the PRV will be flow tested?
Miscellaneous action  1/31/2003 DONE
Returned plans and calculations (5 each) to the front desk for calling and returning.
Telephone call  1/31/2003 DONE
Plans failed called to return.
Telephone call  1/31/2003 DONE
Faxed copy of review.
Application received  1/29/2003