(F) Reprint permit | | | 4/9/2004 | | DONE |
|
|
|
|
INSP-Alarm Testing | 6/26/2003 | 6/27/2003 | 6/27/2003 | A | PASS |
Troy Cobbley
|
|
|
MATT; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
DOC - Permit Finaled | 6/27/2003 | 6/27/2003 | 6/27/2003 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 6/27/2003 7:27:35 AM
|
INSP-Final Inspection | 6/18/2003 | 6/20/2003 | 6/20/2003 | P | FAIL |
Troy Cobbley
|
|
|
provide tamper switch o the anti-freeze system control valve. Strobes do not sync. Change 110cd strobe to 30cd. Provide verification the ceiling strobes are ok for wall use. Provide a map for the facp. Provide knox key box. 6/20/2003 12:09:58 PM
|
Miscellaneous action | | | 4/29/2003 | | DONE |
Sam Rogers
|
|
|
Resubmittals received that satified the inspection comments. Plans approved again. This project covers BLD02-02661 and BLD02-03081 which is attached to FIR03-00207
|
Plan resubmittals received | | | 4/11/2003 | | DONE |
|
|
|
For Sam Rogers
|
INSP-Alarm Testing | 4/7/2003 | 4/8/2003 | 4/8/2003 | P | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 4/7/2003 at 4:21:06 PM. Contact: ###-####. Troy called and said resubmittals are required for the changes to the alarm system plans 4/8/2003 8:48:06 AM
|
INSP-Alarm Testing | 4/3/2003 | 4/7/2003 | 4/7/2003 | A | FAIL |
Troy Cobbley
|
|
|
###-####. Provide 18ah batteries in FACP. Provide 12 ah batteries in the NAC. Provide map. Duct smoke detectors do not shut down hvac. Provide knox box. a/v's overspaced in the vehicle licence. This one FACP monitors two sprinkler systems in two different addressed buildings 4/7/2003 10:47:38 AM
|
INSP-Conference | 3/4/2003 | 3/4/2003 | 3/4/2003 | P | DONE |
Troy Cobbley
|
|
|
###-#### MATT Spoke to Matt about a/v notification in the basement area 3/4/2003 4:20:00 PM
|
Plan assigned to (SAM) | 2/4/2003 | | 2/19/2003 | | DONE |
|
|
|
2/19/2003 09:25:55 430 - activity updated through activity FIRA22 from case FIR03-00049.
|
Alarm Plan Check | 2/19/2003 | | 2/19/2003 | | PASS |
Sam Rogers
|
|
|
Plans approved with conditions
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/19/2003 | | DONE |
Sam Rogers
|
|
|
|
Inspection Record Card- Fire | 2/19/2003 | | 2/19/2003 | | DONE |
|
|
|
|
Issue and Print Permit | | | 2/19/2003 | | DONE |
|
|
|
|
Alarm Plan Check | 2/13/2003 | | 2/12/2003 | | FAIL |
Sam Rogers
|
|
|
Plans failed pending more information. I left a message for James Mesplay to please contact me to go over the issues noted. No written review.
|
Application received | | | 2/4/2003 | | |
|
|
|
|