Permit Information
Permit NumberFIR03-00049
StatusFinaled
Name FUTURETECH
Site Address 7180 W BARRISTER DR
Project NameADA COUNTY COMPLEX
Customer Number 
ePlanReview 
Description
To provide a new addressable fire alarm system which will consist of monitoring the existing fire sprinkler system and monitoring new duct smoke detectors. Audio/visual devices and a manual alarm system have been provided but are not non-required. The fire alarm system scope of work includes the entire building located at 7180 - 7190 Barrister.

There are two building permits associated with this work. Both building permits are for the 7180 Barrister address. There are no associated building permits for 7190 Barrister.

The first building permit (BLD 02-02661) is to remodel an 8,725 sq.ft. area located on the east side of the existing 26,000 sq. ft. court room building to create a new administrative office tenant space. Work to include selective demolition; construction of a 1-hour tenant separation wall; construction of new interior non-bearing walls to create an exit access hall, lobby, private offices and support areas; to add a new unisex accessible restroom and upgrade two existing restrooms to full accessibility compliance; install suspended grid ceiling system; add two new exterior windows; upgrade electrical, mechanical, plumbing, fire sprinkler and alarm systems to comply with current codes and to meet tenant needs per notes & attached plan review comments / conditions, all part of the approved plans on file. Note: This building is fully sprinklered for allowable area increase.
The second building permit (BLD02-03081) is to remodel a 13,514 sq.ft. area of the building for use as administrative sheriffs offices & training room with support work areas per approved plans, to include notes on plans and attached plan review comments / conditions. To perform selective demolition; construct interior non-bearing walls to create new open office areas, reception area and Lobby; to install door assemblies to regulate public access; to install accessible ramp to raised platform area of training room, verify complying door hardware and install accessibility directional signage to accessible restrooms; to modify suspended ceiling grid system and fixture's to meet tenants needs; to install new exterior exit door & landing at the southwest corner area of the open office; to modify electrical, plumbing, mechanical, fire sprinklers & alarm systems to meet tenant needs and current adopted codes. NOTE: This facility is fully sprinklered. A "Certificate of Occupancy is required for this tenant.

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
(F) Reprint permit  4/9/2004 DONE
INSP-Alarm Testing6/26/20036/27/20036/27/2003APASS
DetailsTroy Cobbley
MATT; Phone #: ###-#### Internet Inspection Request from: Darla Downs
DOC - Permit Finaled6/27/20036/27/20036/27/2003PPASS
DetailsTroy Cobbley
Finaled by inspector at 6/27/2003 7:27:35 AM
INSP-Final Inspection6/18/20036/20/20036/20/2003PFAIL
DetailsTroy Cobbley
provide tamper switch o the anti-freeze system control valve. Strobes do not sync. Change 110cd strobe to 30cd. Provide verification the ceiling strobes are ok for wall use. Provide a map for the facp. Provide knox key box. 6/20/2003 12:09:58 PM
Miscellaneous action  4/29/2003 DONE
DetailsSam Rogers
Resubmittals received that satified the inspection comments. Plans approved again. This project covers BLD02-02661 and BLD02-03081 which is attached to FIR03-00207
Plan resubmittals received  4/11/2003 DONE
For Sam Rogers
INSP-Alarm Testing4/7/20034/8/20034/8/2003PCANC
DetailsRick Jackson
Scheduled by a contractor via Hello! on 4/7/2003 at 4:21:06 PM. Contact: ###-####. Troy called and said resubmittals are required for the changes to the alarm system plans 4/8/2003 8:48:06 AM
INSP-Alarm Testing4/3/20034/7/20034/7/2003AFAIL
DetailsTroy Cobbley
###-####. Provide 18ah batteries in FACP. Provide 12 ah batteries in the NAC. Provide map. Duct smoke detectors do not shut down hvac. Provide knox box. a/v's overspaced in the vehicle licence. This one FACP monitors two sprinkler systems in two different addressed buildings 4/7/2003 10:47:38 AM
INSP-Conference3/4/20033/4/20033/4/2003PDONE
DetailsTroy Cobbley
###-#### MATT Spoke to Matt about a/v notification in the basement area 3/4/2003 4:20:00 PM
Plan assigned to (SAM)2/4/2003 2/19/2003 DONE
2/19/2003 09:25:55 430 - activity updated through activity FIRA22 from case FIR03-00049.
Alarm Plan Check2/19/2003 2/19/2003 PASS
DetailsSam Rogers
Plans approved with conditions
PLANS/APPL TAKEN TO FRONT DESK  2/19/2003 DONE
DetailsSam Rogers
Inspection Record Card- Fire2/19/2003 2/19/2003 DONE
Issue and Print Permit  2/19/2003 DONE
Alarm Plan Check2/13/2003 2/12/2003 FAIL
DetailsSam Rogers
Plans failed pending more information. I left a message for James Mesplay to please contact me to go over the issues noted. No written review.
Application received  2/4/2003