INSP-Final Inspection | 10/6/2003 | 10/6/2003 | 10/6/2003 | A | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 10/6/2003 | 10/6/2003 | 10/6/2003 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 10/6/2003 7:44:43 AM
|
INSP-Final Inspection | 7/18/2003 | 7/18/2003 | 7/18/2003 | P | FAIL |
Troy Cobbley
|
|
|
elevator recall still does not work due to a bad breaker, provide modified map for the facp 7/18/2003 4:20:43 PM
|
INSP-Final Inspection | 7/16/2003 | 7/16/2003 | 7/16/2003 | P | FAIL |
Rick Jackson
|
|
|
need map at FACP; sign on FACP door; descriptors for flows and devices; need breaker location and lockout on breaker; shunt for elevator not working; overhead doors not releasing; need record of completion 7/16/2003 11:30:30 AM
|
INSP-Sprinkler Rough-in/Hydro | 7/10/2003 | 7/11/2003 | 7/11/2003 | P | FAIL |
Troy Cobbley
|
|
|
provide approved review comments, provide signage on the the fire alarm/fire sprinkler room door, heat detector exceeds 24" from the sprinkler head in the elev. mach. room, provide access to the fire smoke damper, provide control for the fire smoke dampers per IBC 715.3.2.1, provide point descriptions for the fire alarm devices, elevator was locked out. Only the above items have been looked at. No other items inspected or tested. 7/11/2003 3:25:01 PM
|
INSP-Conference | 5/29/2003 | 5/29/2003 | 5/29/2003 | P | DONE |
Troy Cobbley
|
|
|
ED; Phone #: ###-#### I spoke with Ed about the placement of exit signs. Dave Miller and I agreed that one sign beside the doors would be ok in lue of mounting the exit signs on long pendants in front of the doors 5/29/2003 2:53:53 PM
|
Inspection Record Card- Fire | 3/14/2003 | | 3/14/2003 | | DONE |
|
|
|
|
Telephone call | | | 3/14/2003 | | DONE |
|
|
|
LEFT MESS THAT PERMIT IS READY
|
Issue permit | | | 3/14/2003 | | |
|
|
|
|
Alarm Plan Check | | | 3/13/2003 | | PASS |
|
|
|
Resubmittal still incorrect. Approved WITH CONDITIONS to be field verified.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/13/2003 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 2/11/2003 | | 3/13/2003 | | DONE |
|
|
|
3/13/2003 16:07:38 SLR - activity updated through activity FIRA22 from case FIR03-00057.
|
Plan resubmittals received | | | 3/7/2003 | | |
|
|
|
|
Alarm Plan Check | | | 2/20/2003 | | FAIL |
|
|
|
Resbumittal required, review comments faxed to Synergy. Approval granted to begin installation prior to issuing approved plans; final inspection not to be conducted until plans are approved and permit issued.
|
Application received | | | 2/11/2003 | | |
|
|
|
|