Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR03-00057
StatusFinaled
Name SYNERGY ENGINEERS
Site Address 8853 W FAIRVIEW AVE
Project Namealm-Lithia Motors
Customer Number 
ePlanReview 
Description
Lithia Motors - This permit is to install a new fire alarm system serving the existing building and new addition. The system will include offsite monitoring of the fire sprinkler system, manual pull stations (without a/v annunciation), elevator recall functions, spot coverage smoke detectors for release of overhead roll-up fire doors, and duct smoke detectors for HVAC air handler shutdown, with a single inside alarm at a normally occupied location, and a remote annunciator panel at the front entry.
The associated building permit (BLD 02-02435) is to remodel and finish an existing 53,875 square foot, one story CMU shell building to create a new service and parts storage areas. This work also includes the construction of a new 2,605 square foot mezzanine within the General Service Area. The permit is also to construct a new 28,665 square foot, two story addition at the west side of the existing building. This area is for Service, Showroom and Administrative Office areas. There is a two-hour area separation wall between the existing building and new addition. This building is fully fire sprinklered.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/6/200310/6/200310/6/2003APASS
DetailsRick Jackson
DOC - Permit Finaled10/6/200310/6/200310/6/2003APASS
DetailsRick Jackson
Finaled by inspector at 10/6/2003 7:44:43 AM
INSP-Final Inspection7/18/20037/18/20037/18/2003PFAIL
DetailsTroy Cobbley
elevator recall still does not work due to a bad breaker, provide modified map for the facp 7/18/2003 4:20:43 PM
INSP-Final Inspection7/16/20037/16/20037/16/2003PFAIL
DetailsRick Jackson
need map at FACP; sign on FACP door; descriptors for flows and devices; need breaker location and lockout on breaker; shunt for elevator not working; overhead doors not releasing; need record of completion 7/16/2003 11:30:30 AM
INSP-Sprinkler Rough-in/Hydro7/10/20037/11/20037/11/2003PFAIL
DetailsTroy Cobbley
provide approved review comments, provide signage on the the fire alarm/fire sprinkler room door, heat detector exceeds 24" from the sprinkler head in the elev. mach. room, provide access to the fire smoke damper, provide control for the fire smoke dampers per IBC 715.3.2.1, provide point descriptions for the fire alarm devices, elevator was locked out. Only the above items have been looked at. No other items inspected or tested. 7/11/2003 3:25:01 PM
INSP-Conference5/29/20035/29/20035/29/2003PDONE
DetailsTroy Cobbley
ED; Phone #: ###-#### I spoke with Ed about the placement of exit signs. Dave Miller and I agreed that one sign beside the doors would be ok in lue of mounting the exit signs on long pendants in front of the doors 5/29/2003 2:53:53 PM
Inspection Record Card- Fire3/14/2003 3/14/2003 DONE
Telephone call  3/14/2003 DONE
LEFT MESS THAT PERMIT IS READY
Issue permit  3/14/2003  
Alarm Plan Check  3/13/2003 PASS
Resubmittal still incorrect. Approved WITH CONDITIONS to be field verified.
PLANS/APPL TAKEN TO FRONT DESK  3/13/2003 DONE
Plan assigned to (SAM)2/11/2003 3/13/2003 DONE
3/13/2003 16:07:38 SLR - activity updated through activity FIRA22 from case FIR03-00057.
Plan resubmittals received  3/7/2003  
Alarm Plan Check  2/20/2003 FAIL
Resbumittal required, review comments faxed to Synergy. Approval granted to begin installation prior to issuing approved plans; final inspection not to be conducted until plans are approved and permit issued.
Application received  2/11/2003