INSP-Final Inspection | 5/16/2003 | 5/16/2003 | 5/16/2003 | P | PASS |
Troy Cobbley
|
|
|
|
DOC - Permit Finaled | 5/16/2003 | 5/16/2003 | 5/16/2003 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 5/16/2003 3:34:13 PM
|
INSP-Final Inspection | 3/13/2003 | 3/14/2003 | 3/14/2003 | A | FAIL |
Troy Cobbley
|
|
|
###-#### One sprinkler pendant is blocked by a new cubicle vertical support 3/14/2003 11:02:40 AM
|
(F) Reprint permit | | | 2/28/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/28/2003 | | 2/28/2003 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in | 2/26/2003 | 2/26/2003 | 2/26/2003 | P | PASS |
Rick Jackson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung okay to cover; sprinkler items corrected as indicated on plans 2/26/2003 1:35:42 PM
|
INSP-Final Inspection | 2/24/2003 | 2/25/2003 | 2/25/2003 | A | FAIL |
Troy Cobbley
|
|
|
additional hangers are required. Two pendants in the office area exceed 15 feet spacing. Provide addtional upright along the east wall. Provide smoke detector for the sprinkler monitoring system and verify testing. Currently the panel is in a trouble condition which needs addressed 2/25/2003 4:31:35 PM
|
Issue and Print Permit | | | 2/14/2003 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 2/12/2003 | | 2/13/2003 | | DONE |
|
|
|
2/13/2003 14:37:12 JWA - activity updated through activity FIRA22 from case FIR03-00058.
|
Sprinkler Plan Check | 2/12/2003 | | 2/13/2003 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/13/2003 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 2/13/2003 | | 2/13/2003 | | DONE |
|
|
|
|
Telephone call | | | 2/13/2003 | | DONE |
|
|
|
permit ready and fees due
|
Application received | | | 2/12/2003 | | |
|
|
|
|