Permit Information
Permit NumberFIR03-00062
StatusFinaled
Name ALARMCO
Site Address 10172 W SMOKE RANCH DR
Project NameAlzheimers Care Facility
Customer Number 
ePlanReview 
Description
This permit is to install a new fire alarm system in a new building. The system will include manual pull stations at all exits, smoke detectors in common corridors and associated areas, system smoke detectors in resident rooms arranged to activate a visible alarm outside the respective room and annunciate as a supervisory signal visible at the nurse station FA annunciators, monitor the fire sprinkler system, HVAC supervision and a/v annunciation throughout the building.
The associated building permits (BLD 02-02471, BLD 02-02473, BLD 02-02474) are to construct a one story Type V1hr fully fire sprinklered care facility.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/2/20039/3/20039/3/2003APASS
DetailsTroy Cobbley
ralp; Phone #: ###-#### Internet Inspection Request from: Annette Moore
INSP-Final Inspection9/2/20039/3/20039/3/2003APASS
DetailsTroy Cobbley
ralp; Phone #: ###-#### Internet Inspection Request from: Annette Moore
DOC - Permit Finaled9/3/20039/3/20039/3/2003PPASS
DetailsTroy Cobbley
Finaled by inspector at 9/3/2003 3:40:25 PM
DOC - Permit Finaled9/3/20039/3/20039/3/2003PPASS
DetailsTroy Cobbley
Finaled by inspector at 9/3/2003 3:40:25 PM
INSP-Final Inspection8/29/20039/2/20039/2/2003AFAIL
DetailsTroy Cobbley
Hvac units did not shut down upon alarm, provide the NFPA 72 record of completion forms 9/2/2003 10:36:28 AM
INSP-Final Inspection8/29/20038/29/20038/29/2003PFAIL
DetailsTroy Cobbley
Repair strobe near room 201, need to comply with notes 12 and 14, switch text for north and south pulls, test all devices in the south wing, verify all review notes have been complied with, need fax of reports
INSP-Final Inspection8/26/20038/27/20038/27/2003AFAIL
DetailsTroy Cobbley
ralph; Phone #: ###-#### Hood system, inside tamper vavles and the wet flow switch worked correctly. Other items such as the low air and the PIV did not. The alarm tech. did not know how to test the batteries on the panel and the D8132 module say 15ah max battery but the cut sheet states 18ah. Tech support never did answer their line for us to get answers 8/27/2003 2:13:44 PM
FIR-Aging Inspection7/7/20037/7/20037/7/2003 FAIL
DetailsTroy Cobbley
work in progress 7/7/2003 8:52:28 AM
Issue permit  3/24/2003 DONE
Inspection Record Card- Fire3/20/2003 3/20/2003 DONE
Telephone call  3/20/2003 DONE
LEFT MESS THAT PERMIT IS READY
Plan assigned to (SAM)2/14/2003 3/20/2003 DONE
3/20/2003 09:53:47 430 - activity updated through activity FIRA22 from case FIR03-00062.
Alarm Plan Check3/20/2003 3/20/2003 PASS
DetailsSam Rogers
Plans approved with conditions
PLANS/APPL TAKEN TO FRONT DESK  3/20/2003 DONE
DetailsSam Rogers
Alarm Plan Check  3/3/2003 FAIL
Review comments faxed to Alarmco. Conditional approval granted for installation to begin prior to issuing a permit and approved plans. Final approval shall not be granted until approved plans and a permit are issued.
Application received  2/14/2003  
Inspection Record Card- Fire3/20/2003