Permit Information
Permit NumberFIR03-00076
StatusFinaled
Name MICRON TECHNOLOGY INC
Site Address 8000 S FEDERAL WAY
Project NameMicron Building #26
Customer NumberPCS4696
ePlanReview 
Description
This permit is to upgrade the existing manual/automatic building fire alarm system on the 2nd floor area, in conjunction with the TI building permit to convert portions of this floor from a B to an F1 occupancy. Plans show alarm devices being revised in selected areas throughout the 2nd floor, beyond the boundaries of the Building permit TI area.
The associated building permit (BLD03-00175) is to convert production engineering office area to manufacturing area. To convert approximately 30,000 square feet of the second floor office area of building #26 to a manufacturing area. This alteration is located between grid lines 11&15 and B&M. There is also a small alteration at the first floor between grid lines 12&13 and B&C.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled11/5/200311/5/200311/5/2003APASS
DetailsRick Jackson
Finaled by inspector at 11/5/2003 9:18:37 AM
INSP-Alarm Testing10/31/200310/31/200310/31/2003PPASS
DetailsRick Jackson
Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
INSP-Alarm Testing8/27/20039/2/20039/2/2003AFAIL
DetailsRick Jackson
Rick Jackson, horn test is at 9:00AM, see if you can be here a little earlier.; Phone #: ###-#### Internet Inspection Request from: Daniel Buccinon detector in corridor not closing dampers; need to verify with Sam Rogers about sync'ing strobes in several areas 9/2/2003 9:35:48 AM
INSP-Final Inspection6/19/20036/19/20036/19/2003APART
DetailsRick Jackson
phase A okay
INSP-Alarm Testing6/12/20036/12/20036/12/2003PPART
DetailsRick Jackson
Rick, this will only be a parcel inspection for phase one.; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino verified horn/strobes in new F area to temp wall - okay; smokes in hallway okay to locker room hallway; will relocate smoke at door hold open to corridor by slider as it is too close to wall 6/12/2003 2:39:53 PM
Issue and Print Permit  4/18/2003  
Alarm Plan Check  4/17/2003 PASS
DetailsSam Rogers
Plans approved with conditions
PLANS/APPL TAKEN TO FRONT DESK  4/17/2003 DONE
DetailsSam Rogers
Inspection Record Card- Fire4/17/2003 4/17/2003 DONE
Telephone call  4/17/2003 DONE
permit ready and fees due
Plan assigned to (SAM)2/21/2003 4/1/2003 DONE
4/1/2003 16:25:45 JWA - activity updated through activity FIRA22 from case FIR03-00144.
Plan resubmittals received  4/1/2003 DONE
For Sam Rogers
Alarm Plan Check  3/11/2003 FAIL
Review comments faxed to Micron.
Application received  2/21/2003