INSP-Final Inspection | 3/15/2004 | 3/18/2004 | 3/18/2004 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 3/15/2004 at 3:34:08 PM. Contact: ###-####.
|
DOC - Permit Finaled | 3/18/2004 | 3/18/2004 | 3/18/2004 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 3/18/2004 10:58:37 AM
|
INSP-Final Inspection | 6/19/2003 | 6/23/2003 | 6/23/2003 | A | FAIL |
Rick Jackson
|
|
|
8:00 per telecon with Ken need updated map of initiating devices at panel; elevator recall not working; wiring above grid ceiling not supported (laying on grid) 6/23/2003 10:26:37 AM
|
INSP-Final Inspection | 6/18/2003 | 6/19/2003 | 6/19/2003 | A | CANC |
Rick Jackson
|
|
|
ken; Phone #: ###-#### Internet Inspection Request from: Barbara Moore per telecon with Ken this is rescheduled for 6/23 at 8 am 6/19/2003 2:28:41 PM
|
INSP-Final Inspection | 6/3/2003 | 6/5/2003 | 6/5/2003 | P | FAIL |
Rick Jackson
|
|
|
###-#### please call 1st troubles tested okay for phone lines, battery loss, ac power; NAC circuit not reporting trouble for circuit #2 as shown on plans appears to be additional EOL on that circuit; need to start testing again after problem is fixed 6/5/2003 5:19:49 PM
|
INSP-Final Inspection | 6/2/2003 | 6/3/2003 | 6/3/2003 | A | CANC |
Rick Jackson
|
|
|
KEN; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
Issue and Print Permit | | | 5/12/2003 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 2/24/2003 | | 5/7/2003 | | DONE |
|
|
|
5/7/2003 10:12:07 SLR - activity updated through activity FIRA22 from case FIR03-00077.
|
Alarm Plan Check | | | 5/7/2003 | | PASS |
|
|
|
2nd resubmittal acceptable.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/7/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/7/2003 | | 5/7/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/7/2003 | | 5/7/2003 | | DONE |
|
|
|
|
Telephone call | | | 5/7/2003 | | DONE |
|
|
|
left mess that permit is ready
|
Plan resubmittals received | | | 4/28/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 4/8/2003 | | FAIL |
Sam Rogers
|
|
|
4/8/2003 - Plan review comments faxed to Allied General
|
Alarm Plan Check | | | 3/5/2003 | | FAIL |
|
|
|
3/5/03-Called Ken Webster, Allied Genreal to discuss review; n/a left message to call back. 3/6/03-Faxed review to Allied.
|
Application received | | | 2/24/2003 | | |
|
|
|
|