Description
GENERAL FIRE & CASUALTY- To replace the existing alarm system with a new fire alarm system. The new system will be a manual alarm system with full a/v annunciation, and will include offsite fire sprinkler monitoring, elevator recall, HVAC duct detector monitoring.
The associated building permit (BLD 02-00826) is to perform construction in basement, 1st & 2nd floors of existing building for new owner/tenant per approved plans. A Certificate of Occupancy for this tenant is required prior to occupying, The area of this tenant will be 25,414 sq ft. Work will include construction of one-hour fire -resistive occupancy separation walls and installing one-hour rated door assemblies creating a 675 sq.ft. storage area in basement, construction of new walls on the 1st and 2nd floors for individual office spaces, this will also create one future leasable area of approximately 2786 sq ft that will be located on the second floor, NOTE A SEPARATE APPLICATION AND PERMIT WILL BE REQUIRED TO OBTAIN A CERTIFICATE OF OCCUPANCY FOR THE VACANT LEASABLE SPACE, Miscellaneous related interior finishes. This building is fully fire sprinklered for one-hour substitution.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/15/20043/18/20043/18/2004APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 3/15/2004 at 3:34:08 PM. Contact: ###-####.
DOC - Permit Finaled3/18/20043/18/20043/18/2004APASS
DetailsRick Jackson
Finaled by inspector at 3/18/2004 10:58:37 AM
INSP-Final Inspection6/19/20036/23/20036/23/2003AFAIL
DetailsRick Jackson
8:00 per telecon with Ken need updated map of initiating devices at panel; elevator recall not working; wiring above grid ceiling not supported (laying on grid) 6/23/2003 10:26:37 AM
INSP-Final Inspection6/18/20036/19/20036/19/2003ACANC
DetailsRick Jackson
ken; Phone #: ###-#### Internet Inspection Request from: Barbara Moore per telecon with Ken this is rescheduled for 6/23 at 8 am 6/19/2003 2:28:41 PM
INSP-Final Inspection6/3/20036/5/20036/5/2003PFAIL
DetailsRick Jackson
###-#### please call 1st troubles tested okay for phone lines, battery loss, ac power; NAC circuit not reporting trouble for circuit #2 as shown on plans appears to be additional EOL on that circuit; need to start testing again after problem is fixed 6/5/2003 5:19:49 PM
INSP-Final Inspection6/2/20036/3/20036/3/2003ACANC
DetailsRick Jackson
KEN; Phone #: ###-#### Internet Inspection Request from: Darla Downs
Issue and Print Permit  5/12/2003 DONE
Plan assigned to (SAM)2/24/2003 5/7/2003 DONE
5/7/2003 10:12:07 SLR - activity updated through activity FIRA22 from case FIR03-00077.
Alarm Plan Check  5/7/2003 PASS
2nd resubmittal acceptable.
PLANS/APPL TAKEN TO FRONT DESK  5/7/2003 DONE
Inspection Record Card- Fire5/7/2003 5/7/2003 DONE
Inspection Record Card- Fire5/7/2003 5/7/2003 DONE
Telephone call  5/7/2003 DONE
left mess that permit is ready
Plan resubmittals received  4/28/2003 DONE
Alarm Plan Check  4/8/2003 FAIL
DetailsSam Rogers
4/8/2003 - Plan review comments faxed to Allied General
Alarm Plan Check  3/5/2003 FAIL
3/5/03-Called Ken Webster, Allied Genreal to discuss review; n/a left message to call back. 3/6/03-Faxed review to Allied.
Application received  2/24/2003