Permit Information
Permit NumberFIR03-00081
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 12423 W LEWIS & CLARK DR
Project NameSPR Americare Homes L. L. C.
Customer Number 
ePlanReview 
Description
Americare LLC * To install an approved NFPA 13D-1999 system in an existing 3,725-ft/2, (with an attached 369-ft/2 garage), single family residence to a ten bed, Group R-3, assisted living/congregate residence facility, for ambulatory people. The fire sprinkler flow alarm shall be interconnected to the required residence smoke detection system. All fire sprinkler work and related (which includes dual service water supply, backflow prevention (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review notes, as regulated by the Fire
Department. This permit is attached to: BLD02-02919.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/11/200312/11/200312/11/2003PPASS
DetailsRick Jackson
DOC - Permit Finaled12/11/200312/11/200312/11/2003PPASS
DetailsRick Jackson
Finaled by inspector at 12/11/2003 2:58:04 PM
Issue and Print Permit  12/11/2003 DONE
Issue and Print Permit  12/11/2003 DONE
INSP-Alarm Testing12/10/200312/10/200312/10/2003PCANC
DetailsTroy Cobbley
Scott said that they would like to reschedule for tomorrow with the alarm inspection. I told him to call it in 12/10/2003 10:41:38 AM
Sprinkler Plan Check12/9/2003 12/10/2003 PASS
Water supply verification requrested in the origignal review.
Plan assigned to (Bill)12/9/2003 12/10/2003 DONE
PLANS/APPL TAKEN TO FRONT DESK  12/10/2003 DONE
Inspection Record Card- Fire12/10/2003 12/10/2003 DONE
Permit Ready to Issue  12/10/2003 DONE
Telephone call  12/10/2003 DONE
Spoke with Don told him permit is ready & there are no fees due per Bill//12/10/03 BAM
Telephone call  12/8/2003 DONE
Recieved a call from a pump installer (referencing item #1 review notes) and asked what I needed to verify supply matching the calculations Shilo provided. I indicated that a static, residual and flow for a minimum 10 minutes is required for residence. He did not know what the static would be, but had the residual flows and pressures for 15 minutes and on. Instructed him to submit those to Shilo Automatic Sprinkler.
INSP-Final Inspection12/5/200312/5/200312/5/2003PFAIL
DetailsTroy Cobbley
Provide pendant outside of laundry room and supply required pump information to Bill Alexander for approval 12/5/2003 1:38:18 PM
INSP-Sprinkler Rough-in/Hydro12/1/200312/1/200312/1/2003PCANC
DetailsTroy Cobbley
Please call about 1 hour prior to arrival.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
INSP-Sprinkler Rough-in/Hydro11/20/200311/20/200311/20/2003PPART
DetailsTroy Cobbley
sprinkler piping in attic appears to be properly tented. I notified the contractor (Trent Bice) that the insulation would have to be brought up over the tenting and the pipe to prevent freezing 11/20/2003 4:30:58 PM
Sprinkler Plan Check8/18/2003 8/29/2003 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  8/29/2003 DONE
DetailsBill Alexander
Issue and Print Permit  8/29/2003 DONE
INSP-Sprinkler Rough-in/Hydro8/18/20038/19/20038/19/2003PFAIL
DetailsTroy Cobbley
No items on the correction notice have been completed. The insulation contractor blew in the attic insulation with out tenting the sprinkler piping. Shilo to provide up to date cpvc sprinkler pipe hanger data 8/19/2003 3:42:58 PM
Plan resubmittals received  8/18/2003 DONE
INSP-Sprinkler Rough-in8/6/20038/7/20038/7/2003AFAIL
DetailsTroy Cobbley
tate; Phone #: ###-#### Provide updated fire sprinkler drawings to the city with a floor plan that matches the actual wall layout and sprinkler piping layout. Pendant is missing a hanger in closet in east side of the building. In the same location piping is attached to wood supprt that is not completly attached to the trusses. All existing insulation needs to be removed from below the sprinkler piping. Provide access and ladder so all piping can be inspected. Provide tenting for sprinkler piping per approved plans and nfpa 13d with access for inspection 8/7/2003 3:21:54 PM
FIR-Aging Inspection6/9/20036/9/20036/9/2003 NR
DetailsTroy Cobbley
I spoke to Bob Knight with Shilo and he stated that the contractor is not ready for them to start work yet. 6/9/2003 10:43:55 AM
Override - Parcel Holds  3/10/2003  
Issue permit  3/10/2003  
Inspection Record Card- Fire3/7/2003 3/7/2003 DONE
Telephone call  3/7/2003 DONE
LEFT MESS THAT PERMIT IS READY
Override - Parcel Holds  3/7/2003  
Plan assigned to (Bill)2/26/2003 3/6/2003 DONE
3/6/2003 16:38:10 JWA - activity updated through activity FIRA22 from case FIR03-00081.
Sprinkler Plan Check2/26/2003 3/6/2003 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  3/6/2003 DONE
DetailsBill Alexander
Application received  2/26/2003  
Inspection Record Card- Fire3/7/2003