INSP-Final Inspection | 10/21/2003 | 10/22/2003 | 10/22/2003 | A | PASS |
Troy Cobbley
|
|
|
Peter; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
DOC - Permit Finaled | 10/22/2003 | 10/22/2003 | 10/22/2003 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 10/22/2003 11:44:03 AM
|
INSP-Final Inspection | 4/28/2003 | 4/30/2003 | 4/30/2003 | A | FAIL |
Troy Cobbley
|
|
|
Provide map, signals that arrive at the monitoring company do not match the signals sent. All zones existing and new need verified to match. The supposed duct detector zone came in as a refrigerent trouble 4/30/2003 4:05:29 PM
|
INSP-Final Inspection | 4/28/2003 | 4/29/2003 | 4/29/2003 | A | CANC |
Rick Jackson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
|
Telephone call | | | 4/3/2003 | | DONE |
|
|
|
Call from Gail Bogel, rep for prop owner, conf'd in Rob Ahten, Protex, re system upgrades required by PDS Fire Inspector. They have estimate to do upgrades and to replace panel but do not want to incur cost of a complete system upgrade at time of panel replacement. Advised them to write Dave Miller to requrest delayed upgrade agreement and address all deficiences, with timetable for completeion. Subsequently learned from inspectors that there are three, possibly four, FAC panels in this mall which reportedly is constructed as one building. Immediately called back Gail Bogel, conferenced with Steven Phillips, architect; advised them of additional FAC panels which would have to be included in the panel replacement system design. Architect didn't want to replace those at time of new panel installation. I strongly advised them to connect all existing initiating devices to the single new panel at time of panel replacement, to improve chances of FD approval of a programmed upgrade proposal; suggested there is no Listed way to interconnect the panels to operate as a single sytem as required by 72, and FD not likely to agree to continuing to accept 3 or 4 panels in single building. Advised to be sure to address this issue in letter to Dave Miller.
|
INSP-Final Inspection | 3/14/2003 | 3/17/2003 | 3/17/2003 | A | FAIL |
Troy Cobbley
|
|
|
Test south duct detector, Provide 60 hour battery backup per review note #7. The actual standby current draw is 400Ma which requires 28.8 AH batteries. Existing duct detector zone is labeled tamper/supervisory, relabel for the devices, provide map per review note #4, mount smoke detector on deck, provide dedicated circuit per review note #11 and as stated on the plans, verify signals 3/17/2003 11:16:10 AM
|
Plan assigned to (SAM) | 3/3/2003 | | 3/11/2003 | | DONE |
|
|
|
3/11/2003 09:27:24 430 - activity updated through activity FIRA22 from case FIR03-00086.
|
Alarm Plan Check | 3/11/2003 | | 3/11/2003 | | PASS |
Sam Rogers
|
|
|
Approved with conditions
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/11/2003 | | DONE |
Sam Rogers
|
|
|
|
Inspection Record Card- Fire | 3/11/2003 | | 3/11/2003 | | DONE |
|
|
|
|
Telephone call | | | 3/11/2003 | | DONE |
|
|
|
|
Issue and Print Permit | | | 3/11/2003 | | DONE |
|
|
|
|
Application received | | | 3/3/2003 | | |
|
|
|
|