Permit Information
Permit NumberFIR03-00086
StatusFinaled
Name PROTEX
Site Address 5180 W OVERLAND RD
Project NameHILLCREST SHOPPING CENTER
Customer Number 
ePlanReview 
Description
To supervise two new duct smoke detectors in the new tenant space. The detectors are to be connected to an existing fire alarm system.
The associated building permit (BLD 02-03048) is to remodel an existing 4,806 square foot tenant space for an existing tenant. This tenant space is located in a 288,657 square foot, one story, retail sales strip mall shopping center. Work is to include a restroom accessible to the disabled, a new landing at the main entrance doors (South wall), new doors in an existing opening in the North wall, a new landing at the new doors, and new lay-in ceiling tile all per approved drawings and plan review conditions on file. The location of fire sprinkler heads shall comply with NFPA 13 as regulated by the Fire Department.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/21/200310/22/200310/22/2003APASS
DetailsTroy Cobbley
Peter; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
DOC - Permit Finaled10/22/200310/22/200310/22/2003PPASS
DetailsTroy Cobbley
Finaled by inspector at 10/22/2003 11:44:03 AM
INSP-Final Inspection4/28/20034/30/20034/30/2003AFAIL
DetailsTroy Cobbley
Provide map, signals that arrive at the monitoring company do not match the signals sent. All zones existing and new need verified to match. The supposed duct detector zone came in as a refrigerent trouble 4/30/2003 4:05:29 PM
INSP-Final Inspection4/28/20034/29/20034/29/2003ACANC
DetailsRick Jackson
Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
Telephone call  4/3/2003 DONE
Call from Gail Bogel, rep for prop owner, conf'd in Rob Ahten, Protex, re system upgrades required by PDS Fire Inspector. They have estimate to do upgrades and to replace panel but do not want to incur cost of a complete system upgrade at time of panel replacement. Advised them to write Dave Miller to requrest delayed upgrade agreement and address all deficiences, with timetable for completeion. Subsequently learned from inspectors that there are three, possibly four, FAC panels in this mall which reportedly is constructed as one building. Immediately called back Gail Bogel, conferenced with Steven Phillips, architect; advised them of additional FAC panels which would have to be included in the panel replacement system design. Architect didn't want to replace those at time of new panel installation. I strongly advised them to connect all existing initiating devices to the single new panel at time of panel replacement, to improve chances of FD approval of a programmed upgrade proposal; suggested there is no Listed way to interconnect the panels to operate as a single sytem as required by 72, and FD not likely to agree to continuing to accept 3 or 4 panels in single building. Advised to be sure to address this issue in letter to Dave Miller.
INSP-Final Inspection3/14/20033/17/20033/17/2003AFAIL
DetailsTroy Cobbley
Test south duct detector, Provide 60 hour battery backup per review note #7. The actual standby current draw is 400Ma which requires 28.8 AH batteries. Existing duct detector zone is labeled tamper/supervisory, relabel for the devices, provide map per review note #4, mount smoke detector on deck, provide dedicated circuit per review note #11 and as stated on the plans, verify signals 3/17/2003 11:16:10 AM
Plan assigned to (SAM)3/3/2003 3/11/2003 DONE
3/11/2003 09:27:24 430 - activity updated through activity FIRA22 from case FIR03-00086.
Alarm Plan Check3/11/2003 3/11/2003 PASS
DetailsSam Rogers
Approved with conditions
PLANS/APPL TAKEN TO FRONT DESK  3/11/2003 DONE
DetailsSam Rogers
Inspection Record Card- Fire3/11/2003 3/11/2003 DONE
Telephone call  3/11/2003 DONE
Issue and Print Permit  3/11/2003 DONE
Application received  3/3/2003