INSP-Final Inspection | 1/9/2004 | 1/9/2004 | 1/9/2004 | P | PASS |
Rick Jackson
|
|
|
FDC hydro okay; received all test certificates 1/9/2004 1:14:47 PM
|
DOC - Permit Finaled | 1/9/2004 | 1/9/2004 | 1/9/2004 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 1/9/2004 1:14:52 PM
|
INSP-Final Inspection | 1/8/2004 | 1/8/2004 | 1/8/2004 | A | FAIL |
Rick Jackson
|
|
|
need heaqds replaced that are painted in basement and tape remove from others; hydro FDC; need signage on drains and blue tag on risers; SR head in elevator room; will need test papers at final;resubmittals for basement and fourth floor 1/8/2004 11:11:09 AM
|
INSP-Sprinkler Rough-in/Hydro | 1/8/2004 | 1/8/2004 | 1/8/2004 | P | FAIL |
Rick Jackson
|
|
|
FDC hydro failed to hold pressure 1/8/2004 3:41:06 PM
|
INSP-Sprinkler Rough-in/Hydro | 1/6/2004 | 1/7/2004 | 1/7/2004 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 1/6/2004 at 3:29:17 PM. Contact: ###-####. hydro on floors okay; small leak at Vic on 6 inch right near the check valve 1/7/2004 1:16:22 PM
|
INSP-Sprinkler Rough-in/Hydro | 12/22/2003 | 12/23/2003 | 12/23/2003 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 12/22/2003 at 3:39:43 PM. UG hydro and flush okay; still need resubmittals for changes to 4-5 floor residence; dry inspectors test relocated; basement branch line relocated due to heaters and 286 heads used if within 7 ft of heater 12/23/2003 3:59:36 PM
|
INSP-Sprinkler Rough-in/Hydro | 12/2/2003 | 12/4/2003 | 12/4/2003 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 12/2/2003 at 2:40:52 PM. Contact: ###-####. fourth floor - 1 head on 1inch line in stair as plans show 1.25 inch line; minor modifications around ducts, etc. 12/4/2003 4:04:01 PM
|
INSP-Conference | 11/10/2003 | 11/12/2003 | 11/12/2003 | A | PART |
Rick Jackson
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes met with GC and Dave Hannah about shell sign-off and third floor occupancy 11/12/2003 2:51:32 PM
|
INSP-Sprinkler Rough-in/Hydro | 10/27/2003 | 10/28/2003 | 10/28/2003 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/27/2003 at 1:25:30 PM. r/i for 1-2-3 floors; TI work in progress on 3rd 10/28/2003 11:00:57 AM
|
INSP-Sprinkler Rough-in | 9/18/2003 | 9/22/2003 | 9/22/2003 | A | FAIL |
Rick Jackson
|
|
|
###-#### chris basement: need hangers at end of pipe and fix busted hangers; standpipe hose outlets to be 3-5 ft from floor; beams creating obstructions; 6 inch main shifted to the north next to 3 inch due to beams; additional EQ on riser 9/22/2003 3:57:26 PM
|
Override - Parcel Holds | | | 9/18/2003 | | |
|
|
|
|
Issue and Print Permit | | | 9/2/2003 | | DONE |
|
|
|
|
Sprinkler Plan Check | 8/18/2003 | | 8/29/2003 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/29/2003 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 8/29/2003 | | DONE |
|
|
|
left mess that permit is ready
|
Plan resubmittals received | | | 8/18/2003 | | |
|
|
|
|
Plan resubmittals received | | | 8/18/2003 | | DONE |
Bill Alexander
|
|
|
|
INSP-Supply line flush | 5/13/2003 | 5/13/2003 | 5/13/2003 | P | PASS |
Troy Cobbley
|
|
|
The inspection was not for a flush but for a cover of the underground. Piping is ok for cover 5/13/2003 3:03:53 PM
|
Issue permit | | | 3/20/2003 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 3/5/2003 | | 3/19/2003 | | DONE |
|
|
|
3/19/2003 09:36:04 JWA - activity updated through activity FIRA22 from case FIR03-00093.
|
Sprinkler Plan Check | 3/5/2003 | | 3/19/2003 | | PART |
Bill Alexander
|
|
|
Requires resubmittal of key items (reference review notes).
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/19/2003 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 3/19/2003 | | 3/19/2003 | | DONE |
|
|
|
|
Telephone call | | | 3/19/2003 | | DONE |
|
|
|
LEFT MESS THAT PERMIT IS READY
|
Application received | | | 3/5/2003 | | |
|
|
|
|