Permit Information
Permit NumberFIR03-00107
StatusFinaled
Name ADT SECURITY SERVICES INC
Site Address 3658 S FINDLEY AVE
Project Namealm-FAMILY CENTER-BLDG A1
Customer Number 
ePlanReview 
Description
Fitness 19 at FAMILY CENTER-BLDG A1 - To add duct smoke detectors for HVAC air handler shut down to the existing fire alarm system. In addition, larger batteries are being provided, which are to be located in a separate battery cabinet.
The associated building permit (BLD 02-02766) is to create a new 6,900 sq. ft. assembly fitness studio space in existing vacant shell building space per approved plans on file. Work to include new one-hour rated tenant demising walls, new interior walls, new interior doors and windows, interior finish, new accessible restrooms, new suspended ceiling, fire sprinkler work, new plumbing, new mechanical, and new electrical work. A Certificate of Occupancy is to be issued when completed and approved.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/14/20035/15/20035/15/2003PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 5/14/2003 at 8:11:57 AM. Contact: ###-####.
DOC - Permit Finaled5/15/20035/15/20035/15/2003PPASS
DetailsRick Jackson
Finaled by inspector at 5/15/2003 3:43:10 PM
INSP-Final Inspection5/8/20035/9/20035/9/2003PCANC
DetailsRick Jackson
Scheduled by a contractor via Hello! on 5/8/2003 at 2:18:36 PM. Contact: ###-####. rescheduled for next week 5/12/2003 12:23:13 PM
Inspection Record Card- Fire4/30/2003 4/30/2003 DONE
Telephone call  4/30/2003 DONE
permit ready
Issue permit  4/30/2003 DONE
Plan resubmittals received  4/29/2003 DONE
resubmittal mailed in.
Alarm Plan Check4/29/2003 4/29/2003 DONE
resubmittal acceptable.
PLANS/APPL TAKEN TO FRONT DESK  4/29/2003 DONE
Plan assigned to (SAM)3/11/2003 4/29/2003 DONE
4/29/2003 14:56:42 SLR - activity updated through activity FIRA22 from case FIR03-00107.
Telephone call  4/17/2003 DONE
Dave Whiting returned my 3/13/2003 phaone call. Discussed the problem with him. He will review and decide what to do and them resubmit accordingly. I will continue to hold plans for resubmittal.
Alarm Plan Check  3/13/2003 HOLD
Plan to change batteries is not acceptable. Called Dave Whiting to discuss. See Telephone call logs.
Telephone call  3/13/2003 DONE
called Dave Whiting; n/a, left vm to call back to discuss. Plans call for changing existing 17AH batteries to 18 AH, however, FAC panel cannot hold larger than 17.0. therefore an external cabinet/charger will be required. If he wants to make this modification, will need to submit revised plans and cut sheets for equipment.
Application received  3/11/2003