INSP-Final Inspection | 5/22/2003 | 5/22/2003 | 5/22/2003 | P | PASS |
Rick Jackson
|
|
|
all items from previous inspection completed
|
DOC - Permit Finaled | 5/22/2003 | 5/22/2003 | 5/22/2003 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 5/22/2003 3:58:26 PM
|
INSP-Sprinkler Rough-in/Hydro | 5/7/2003 | 5/8/2003 | 5/8/2003 | A | FAIL |
Troy Cobbley
|
|
|
four hangers for 1" pipe appear to exceed 24" max hanging length. One piece of 1" pipe is hung from a wall top plate 5/8/2003 4:17:21 PM
|
INSP-Sprinkler Rough-in/Hydro | 5/6/2003 | 5/7/2003 | 5/7/2003 | A | FAIL |
Troy Cobbley
|
|
|
No approved plans on site. No inspection done. I requested that the contractor not cover anything up. 5/7/2003 9:48:07 AM
|
Override - Parcel Holds | | | 3/28/2003 | | |
|
|
|
|
Inspection Record Card- Fire | 3/28/2003 | | 3/28/2003 | | DONE |
|
|
|
|
Telephone call | | | 3/28/2003 | | |
|
|
|
|
Override - Parcel Holds | | | 3/28/2003 | | |
|
|
|
|
Issue permit | | | 3/28/2003 | | |
|
|
|
|
Plan assigned to (Bill) | 3/14/2003 | | 3/27/2003 | | DONE |
|
|
|
3/27/2003 14:34:33 JWA - activity updated through activity FIRA22 from case FIR03-00118.
|
Sprinkler Plan Check | 3/27/2003 | | 3/27/2003 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/27/2003 | | DONE |
Bill Alexander
|
|
|
|
Plan resubmittals received | | | 3/26/2003 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/14/2003 | | 3/25/2003 | | FAIL |
Bill Alexander
|
|
|
Calculations provide are not accepted. Provide calculations in accordance with requirements of NFPA 13:8-1.1.1, 8-3, 8-3.2, 8-3.3, 8-3.4, IFC 105.4, 901.2.
Sprinkler head data submittals are obsolete. Plans sprinkler schedule and legend also reflects obsolete data. Provide current sprinkler data submittals and information. (IFC 105.4, 901.2)
|
Miscellaneous action | | | 3/25/2003 | | DONE |
|
|
|
Returned plans to front desk for calling and return.
|
Telephone call | | | 3/25/2003 | | DONE |
|
|
|
LEFT MESS WITH DEBEST THAT PLANS ARE REJECTED/NEED TO PICKUP
|
Application received | | | 3/14/2003 | | |
|
|
|
|