INSP-Final Inspection | 9/28/2005 | 9/28/2005 | 9/28/2005 | A | PASS |
Forrest France
|
|
|
Additional pump flow test performed with Jim Danes of DeBest fire, 100% and 150% rated flow verified with residual pressure at 100% satisfactory.
|
Meeting | | | 11/29/2004 | | DONE |
|
|
|
Met with Dave Miller. reviewed results of last pump test. Pump performace meets 100% design and flow is adequate for AS and hose. Water supply inadequate for 150% pump test and to meet IFC required 1500 fire flow. Garden City, Brian Burger indicated in previous phone calls (October 2004) that they are working on repairing the defective well (which failed prior to the original pump acceptance test we witnessed last summer) but they cannot give a date on when repairs will be completed. Dave Miller to follow up with Brian on latest status. No change in status of this permit or the TOC situation until Dave Miller advises us further.
|
INSP-Final Inspection | 11/15/2004 | 11/16/2004 | 11/16/2004 | A | FAIL |
Rick Jackson
|
|
|
Fire Pump Final - Contact Brian - would like to have scheduled at 9 am; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Pump test at 150 percent resulted in negative pressure on suction side of pump; Sam Rogers recorded all pump test data 11/16/2004 10:24:33 AM
|
Telephone call | | | 5/6/2004 | | DONE |
|
|
|
This Department (PDS/FD IFC Review) called Garden City Public Works 2:35pm of which a Gary Todd returned my call. I referenced him the permitted project at 2288 N. Garden St. (Joes Crab Shack - FIR03-00123, BLD02-03091) and the ongoing problem that Garden City's water supply available. Also indicated that the property addressed will not be given any more extended "Temporary Occupancies," due to what was insufficient water supplies. I gave them the 1995 and the 2003 water supplies differences. I indicated we do not have the copies of the failed performance test certificates, which may be obtained from De Best Fire Protection (###-####) and/or the fire pump manufactures representative. The failure was due to the insufficient water supply available and pressure readings which will not meet Idaho Administrative Code IDAPA 58.01.08, Operating Criteria For Public Water Systems 552, Quantity And Pressure Requirements 01(i).
His response was that he will take this information to Mr. Bybee. They may possibly do another system check, verifying valves are open, etc., and perform another test in the local area get back in contact with me.
|
INSP-Final Inspection | 8/19/2003 | 8/21/2003 | 8/20/2003 | A | FAIL |
Rick Jackson
|
|
|
jim--fn with a fire pump; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Need fire pump data and jockey/fire pump controller test lines to drain; fire pump couldn't pump to 150 percent capacity as the suction was at zero. 8/21/2003 7:25:53 AM
|
Meeting | | | 7/29/2003 | | DONE |
Bill Alexander
|
|
|
Had a conversation with Dave Miller (2:25 pm) regarding the pump room requiring an outside direct access. He indicated he was willing to allow the deficiency due to the facility is existing, and basically a small and low hazard with an emphasis on "it's requirement". It shall be noted that the Owner/Manager must be notified that under fire conditions, this may affect the performance of the building protection, since access to the pump room may be impossible.
|
Miscellaneous action | | | 7/29/2003 | | DONE |
|
|
|
Emailed De Best Fire, with the approval allowing the deficiency for pump room access per Dave Miller. See "Telephone" action attached.
|
Telephone call | | | 7/25/2003 | | DONE |
|
|
|
left mess that is ready
|
Inspection Record Card- Fire | 7/25/2003 | | 7/25/2003 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/25/2003 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/24/2003 | | DONE |
Bill Alexander
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 7/7/2003 | 7/7/2003 | 7/7/2003 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 7/7/2003 at 10:45:26 AM. Contact: ###-####. wet and antifreeze systems will require annual inspection; heads overspaced above ceiling in kitchen per plan review notes; mezzanine area not fully sprinklered; head obstructed by partition in mens room; remove paper from heads throughout; sprinklers or noncumbustible area by dishwasher along wall; repair head in storage room; submit data for fire pump to plan review 7/7/2003 3:38:26 PM
|
Issue and Print Permit | | | 6/27/2003 | | DONE |
|
|
|
|
Sprinkler Plan Check | 6/20/2003 | | 6/25/2003 | | PART |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/25/2003 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 6/25/2003 | | 6/25/2003 | | DONE |
|
|
|
|
Telephone call | | | 6/25/2003 | | DONE |
|
|
|
permit ready and fees due
|
Plan resubmittals received | | | 6/20/2003 | | DONE |
|
|
|
|
Telephone call | | | 6/19/2003 | | DONE |
|
|
|
left mess that permit is ready
|
Sprinkler Plan Check | 6/13/2003 | | 6/18/2003 | | PART |
Bill Alexander
|
|
|
Construction phase permit. Approved to proceed. To many issues need verified to allow an approved stamped set. Resubmittal required.
|
Miscellaneous action | | | 6/18/2003 | | DONE |
|
|
|
Took partially approved plans (proceed at own risk) to front desk for calling and returning. Emailed copy of review and information to John Venche (De Best Fire Protection).
|
Plan assigned to (Bill) | 6/17/2003 | | 6/17/2003 | | DONE |
|
|
|
Construction phase permit
|
Plan resubmittals received | | | 6/13/2003 | | DONE |
Bill Alexander
|
|
|
|
Application received | | | 3/18/2003 | | |
|
|
|
|
Plan assigned to (Bill) | 3/18/2003 | | 3/18/2003 | | DONE |
|
|
|
Demolition phase permit. 3/18/2003 09:42:19 JWA - activity updated through activity FIRA22 from case FIR03-00123.
|
Sprinkler Plan Check | 3/18/2003 | | 3/18/2003 | | PASS |
Bill Alexander
|
|
|
Demolition phase permit
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/18/2003 | | DONE |
Bill Alexander
|
|
|
Demolition phase permit
|
Inspection Record Card- Fire | 3/18/2003 | | 3/18/2003 | | DONE |
|
|
|
|
Telephone call | | | 3/18/2003 | | DONE |
|
|
|
Demolition phase permit ready
|
Issue permit | | | 3/18/2003 | | |
|
|
|
|
Inspection Record Card- Fire | 7/25/2003 | | | | |
|
|
|
|