INSP-Final Inspection | 9/17/2003 | 9/17/2003 | 9/17/2003 | P | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 9/17/2003 | 9/17/2003 | 9/17/2003 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 9/17/2003 2:16:44 PM
|
INSP-Final Inspection | 9/8/2003 | 9/8/2003 | 9/8/2003 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/8/2003 at 10:16:11 AM. Contact: ###-####. need initiating devices only for maps - they currently have notification devices and initiating; relocate PIV to NW corner of building 9/8/2003 4:18:59 PM
|
INSP-Final Inspection | 8/28/2003 | 8/28/2003 | 8/28/2003 | A | PART |
Rick Jackson
|
|
|
per Dave Miller a temp is approved for fire/life safety pending Simplex supplying as builts due to changes and providing maps of initiating devices 8/28/2003 8:59:07 AM
|
INSP-Final Inspection | 8/27/2003 | 8/27/2003 | 8/27/2003 | A | FAIL |
Rick Jackson
|
|
|
left correction notice with GC; detectors overspaced in corridor; strobes overspaced in corridor and hospitality room; need descriptors for PIV and hall detectors; strobes acitivate when alarm silence is pushed after ADA room detector is in alarm??; open splices in fire wire throughout; need map and as-builts due to many changes for mapnet ID #'s and location of devices and splitting of NAC's; will need to test panel for troubles - phone lines, batt's, NAC's for voltage drop, etc; record of completion 8/27/2003 3:40:20 PM
|
Plan resubmittals received | | | 8/12/2003 | | |
|
|
|
|
Miscellaneous action | | | 8/12/2003 | | |
|
|
|
Phoned Chris Willis to advise of approval to proceed with work on plan modifications prior to approval of plans. Received plan modifications 8/12/2003.
|
Telephone call | | | 8/12/2003 | | |
|
|
|
Confirmed with Chris Willis approval to proceed based upon system smoke detectors for each hotel room to sound a horn in its appropriate space only. He will e-mail me an updated matrix to show the room smoke and horn functionality. FAS should be designed under UFC 1997.
|
FIR-Aging Inspection | 7/11/2003 | 7/11/2003 | 7/11/2003 | | PASS |
Rick Jackson
|
|
|
work is in progress 7/11/2003 7:51:33 AM
|
Issue permit | | | 4/11/2003 | | |
|
|
|
|
Alarm Plan Check | | | 4/10/2003 | | PASS |
Sam Rogers
|
|
|
Plans approved with conditions
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/10/2003 | | DONE |
Sam Rogers
|
|
|
|
Inspection Record Card- Fire | 4/10/2003 | | 4/10/2003 | | DONE |
|
|
|
|
Telephone call | | | 4/10/2003 | | |
|
|
|
|
Plan assigned to (SAM) | 3/24/2003 | | 4/3/2003 | | DONE |
|
|
|
4/3/2003 15:21:27 JWA - activity updated through activity FIRA22 from case FIR03-00152.
|
Application received | | | 3/24/2003 | | |
|
|
|
|