Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberFIR03-00141
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 2906 S VISTA AVE
Project NameComfort Suites
Customer Number 
ePlanReview 
Description
To provide an addressable fire alarm system which will include smoke detectors in common areas, smoke detectors in individual suites, induct smoke detectors for damper control, duct smoke detectors for HVAC shutdown, elevator recall, sprinkler monitoring and notification devices.
The associated building permit (BLD 02-02863) is to construct a new, 51,500 sq.ft., three-story, 83 rooms hotel, with conference room, covered Porte Cochere and area for future indoor swimming pool. NOTE: This building is fully fire sprinklered for area increase. All construction per the approved plans and attached comment. This permit does not include the construction of the indoor swimming pool and spa.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/17/20039/17/20039/17/2003PPASS
DetailsRick Jackson
DOC - Permit Finaled9/17/20039/17/20039/17/2003PPASS
DetailsRick Jackson
Finaled by inspector at 9/17/2003 2:16:44 PM
INSP-Final Inspection9/8/20039/8/20039/8/2003PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 9/8/2003 at 10:16:11 AM. Contact: ###-####. need initiating devices only for maps - they currently have notification devices and initiating; relocate PIV to NW corner of building 9/8/2003 4:18:59 PM
INSP-Final Inspection8/28/20038/28/20038/28/2003APART
DetailsRick Jackson
per Dave Miller a temp is approved for fire/life safety pending Simplex supplying as builts due to changes and providing maps of initiating devices 8/28/2003 8:59:07 AM
INSP-Final Inspection8/27/20038/27/20038/27/2003AFAIL
DetailsRick Jackson
left correction notice with GC; detectors overspaced in corridor; strobes overspaced in corridor and hospitality room; need descriptors for PIV and hall detectors; strobes acitivate when alarm silence is pushed after ADA room detector is in alarm??; open splices in fire wire throughout; need map and as-builts due to many changes for mapnet ID #'s and location of devices and splitting of NAC's; will need to test panel for troubles - phone lines, batt's, NAC's for voltage drop, etc; record of completion 8/27/2003 3:40:20 PM
Plan resubmittals received  8/12/2003  
Miscellaneous action  8/12/2003  
Phoned Chris Willis to advise of approval to proceed with work on plan modifications prior to approval of plans. Received plan modifications 8/12/2003.
Telephone call  8/12/2003  
Confirmed with Chris Willis approval to proceed based upon system smoke detectors for each hotel room to sound a horn in its appropriate space only. He will e-mail me an updated matrix to show the room smoke and horn functionality. FAS should be designed under UFC 1997.
FIR-Aging Inspection7/11/20037/11/20037/11/2003 PASS
DetailsRick Jackson
work is in progress 7/11/2003 7:51:33 AM
Issue permit  4/11/2003  
Alarm Plan Check  4/10/2003 PASS
DetailsSam Rogers
Plans approved with conditions
PLANS/APPL TAKEN TO FRONT DESK  4/10/2003 DONE
DetailsSam Rogers
Inspection Record Card- Fire4/10/2003 4/10/2003 DONE
Telephone call  4/10/2003  
Plan assigned to (SAM)3/24/2003 4/3/2003 DONE
4/3/2003 15:21:27 JWA - activity updated through activity FIRA22 from case FIR03-00152.
Application received  3/24/2003