Permit Information
Permit NumberFIR03-00153
StatusFinaled
Name SYNERGY ENGINEERS
Site Address 252 E FRONT ST
Project Namealm ID WATER CENTER-PA2 BLDG A
Customer Number 
ePlanReview 
Description
CIVIC PLAZA PA-2 APARTMENTS-This permit is to install a new manual fire alarm system and single/multiple station smoke detection in dwelling units, as part of the construction of the R-1 apartment building. The new alarm system will cover the basement parking structure ground floor parking area and the 5-story apartment building. The manual alarm system includes pull stations at all exits, audible alarms in all building areas, visual annunciation in common and public use areas and hearing impaired dwelling units, elevator recall functions, and monitoring of the fire sprinkler system and fire pump.
There are separate permits and a Certificate of Occupancy required to finish and occupy each future tenant space.
The associated building permits are:
BLD 02-00369 (shell & core) - To construct a new 30,873 sq. ft. parking garage and retail sales area, with a three hour occupancy separation per UBC Section 311.2.2.1, on top of an existing Type I-FR. underground parking structure. To complete center core, restroom and laundry facilities for the upper floor apartments. The parking area is 9,300 sq. ft. and there is 12,600 sq. ft. for future tenant space.
BLD02-00370 (Section 1 of 6) - To construct two four-hour area separation walls to divide this building into six separate buildings. This section is 5 stories and 25 units, @ 3,869 sq.ft. per floor, above a three-hour occupancy separation per UBC Section 311.2.2.1.
BLD02-00371 (Section 2 of 6) To construct two four-hour area separation walls to divide this building into six separate buildings. This section is 5 stories and 25 units, @ 4,767 sq.ft. per floor, above a three-hour occupancy separation per UBC Section 311.2.2.1.
BLD02-00372 (Section 3 of 6) - To construct two four-hour area separation walls to divide this building into six separate buildings. This section is 5 stories and 20 units, @ 4,413 sq.ft. per floor, above a three-hour occupancy separation per UBC Section 311.2.2.1.
BLD02-00373 (Section 4 of 6) - To construct two four-hour area separation walls to divide this building into six separate buildings. This section is 5 stories and 25 units, @ 4,666 sq.ft. per floor, above a three-hour occupancy separation per UBC Section 311.2.2.1.
BLD02-00374 (Section 5 of 6) - To construct two four-hour area separation walls to divide this building into six separate buildings. This section is 5 stories and 20 units, @ 3,866 sq.ft. per floor, above a three-hour occupancy separation per UBC Section 311.2.2.1.
BLD02-00375 (Section 6 of 6) - To construct two four-hour area separation walls to divide this building into six separate buildings. This section is 5 stories and 29 units, @ 4,180 sq.ft. per floor, above a three-hour occupancy separation per UBC Section 311.2.2.1.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  3/23/2004 DONE
Received fax from Shawn Meador (Synergy) that the annunciator located in the garage entry way will be removed due to the environmental conditions. (Coment #3 in the Fire Alarm Permit Review).
INSP-Final Inspection2/24/20042/24/20042/24/2004PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 2/24/2004 at 8:20:12 AM. Contact: ###-####.
DOC - Permit Finaled2/24/20042/24/20042/24/2004PPASS
DetailsRick Jackson
Finaled by inspector at 2/24/2004 4:33:53 PM
INSP-Final Inspection2/23/20042/23/20042/23/2004PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 2/23/2004 at 11:06:48 AM. Contact: ###-####. need updated map as in-duct adresses have changed from plans; horn not working by room 303; floor designations on maps not correct and missing 2nd floor 2/23/2004 4:56:04 PM
INSP-Final Inspection2/19/20042/20/20042/20/2004AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 2/19/2004 at 3:54:18 PM. Contact: ###-####. contractor hasn't completed testing 2/20/2004 4:22:06 PM
INSP-Final Inspection2/17/20042/19/20042/19/2004AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 2/17/2004 at 6:22:16 PM. Contact: ###-####. strobes not within 15 ft from ends of corridors; need to test devices/notification 2/19/2004 3:46:25 PM
Issue and Print Permit  2/17/2004 DONE
Alarm Plan Check  2/11/2004 PASS
Plan Modification - Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  2/11/2004 DONE
Permit Ready to Issue  2/11/2004 DONE
Inspection Record Card- Fire2/11/2004 2/11/2004 DONE
Telephone call  2/11/2004 DONE
Spoke with Becca and told her that permits are ready & fee//2/11/04 2:07pm BAM
Plan resubmittals received  2/4/2004 DONE
INSP-Alarm Testing1/5/20041/6/20041/6/2004ANR
DetailsRick Jackson
mark 208/941/1847
Override - Parcel Holds  1/5/2004  
FIR-Aging Inspection8/26/20038/26/20038/26/2003 PASS
DetailsRick Jackson
the building is still under construction 8/26/2003 7:46:13 AM
Issue permit  5/27/2003  
Inspection Record Card- Fire5/23/2003 5/23/2003 DONE
Telephone call  5/23/2003 DONE
permit ready
Alarm Plan Check  5/22/2003 PASS
3rd review- satisfactory pending field verification of conditional items.
PLANS/APPL TAKEN TO FRONT DESK  5/22/2003 DONE
Plan assigned to (SAM)4/3/2003 5/22/2003 DONE
5/22/2003 16:30:05 M_F - activity updated through activity FIRA22 from case FIR03-00153.
Plan resubmittals received  5/12/2003  
Alarm Plan Check  5/9/2003 FAIL
Conditional approval granted to begin installation.
Alarm Plan Check4/17/2003 4/17/2003 FAIL
DetailsSam Rogers
Failed review notes faxed to Synergy, ###-####
Application received  4/3/2003