INSP-Final Inspection | 4/1/2004 | 4/1/2004 | 4/1/2004 | A | PASS |
Rick Jackson
|
|
|
All items corrected; final okay 4/1/2004 8:31:42 AM
|
DOC - Permit Finaled | 4/1/2004 | 4/1/2004 | 4/1/2004 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 4/1/2004 8:31:45 AM
|
INSP-Final Inspection | 2/24/2004 | 2/24/2004 | 2/24/2004 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 2/24/2004 at 8:23:26 AM. Contact: ###-####. The access control elevator lobby doors will need to be tested to verify they release on fire alarm; they will not be active until after the acceptance by the inspector; the remote annunciator at the ramp is not listed for out in the elements 2/24/2004 4:29:07 PM
|
INSP-Final Inspection | 2/23/2004 | 2/23/2004 | 2/23/2004 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 2/23/2004 at 11:10:03 AM. Contact: ###-####. need updated map as in-duct adresses have changed from plans; horn not working by room 303; floor designations on maps not correct and missing 2nd floor 2/23/2004 4:55:20 PM
|
INSP-Final Inspection | 2/19/2004 | 2/20/2004 | 2/20/2004 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 2/19/2004 at 3:59:58 PM. Contact: ###-####. contractor hasn't finished complete test 2/20/2004 4:20:21 PM
|
INSP-Final Inspection | 2/17/2004 | 2/19/2004 | 2/19/2004 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 2/17/2004 at 6:25:42 PM. Contact: ###-####. need to test sprinkler flows/pump/tampers and notification on first floor; devices not completed in laundry room 2/19/2004 3:44:38 PM
|
Issue and Print Permit | | | 2/17/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 2/11/2004 | | PASS |
|
|
|
Plan Modification - Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/11/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/11/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/11/2004 | | 2/11/2004 | | DONE |
|
|
|
|
Telephone call | | | 2/11/2004 | | DONE |
|
|
|
Spoke with Becca and told her that permits are ready & fees//2/11/04 2:06pm BAM
|
Plan resubmittals received | | | 2/4/2004 | | DONE |
|
|
|
|
INSP-Alarm Testing | 1/5/2004 | 1/6/2004 | 1/6/2004 | A | FAIL |
Rick Jackson
|
|
|
mark 208/941/1847 horns in parkong not listed for belwo 32 degrees; need lockouts on breakers; need heat in FACP room to maintain above 32 degrees; 1/6/2004 4:14:23 PM
|
FIR-Aging Inspection | 9/5/2003 | 9/5/2003 | 9/5/2003 | | PASS |
Rick Jackson
|
|
|
this building is still under construction 9/5/2003 7:18:41 AM
|
Issue permit | | | 5/27/2003 | | |
|
|
|
|
Inspection Record Card- Fire | 5/23/2003 | | 5/23/2003 | | DONE |
|
|
|
|
Telephone call | | | 5/23/2003 | | DONE |
|
|
|
permit ready
|
Alarm Plan Check | | | 5/22/2003 | | PASS |
|
|
|
3rd review- satisfactory pending field verification of conditional items.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/22/2003 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 4/3/2003 | | 5/22/2003 | | DONE |
|
|
|
5/22/2003 16:34:52 M_F - activity updated through activity FIRA22 from case FIR03-00159.
|
Alarm Plan Check | | | 5/9/2003 | | FAIL |
|
|
|
Conditional approval granted to begin installation.
|
Alarm Plan Check | | | 4/17/2003 | | FAIL |
Sam Rogers
|
|
|
Failed review notes faxed to Synergy, ###-####
|
Application received | | | 4/3/2003 | | |
|
|
|
|