Case Summary | | | 7/26/2004 | | DONE |
|
|
|
|
INSP-Final Inspection | 11/17/2003 | 11/18/2003 | 11/18/2003 | P | PASS |
Rick Jackson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Robert Bailey
|
DOC - Permit Finaled | 11/18/2003 | 11/18/2003 | 11/18/2003 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 11/18/2003 3:59:42 PM
|
INSP-Alarm Testing | 10/29/2003 | 10/31/2003 | 10/31/2003 | A | FAIL |
Troy Cobbley
|
|
|
The new battery cabinet still does not report to the facp when the batteries have been disconnected. All other items and devices tested ok 10/31/2003 10:21:17 AM
|
INSP-Final Inspection | 10/14/2003 | 10/15/2003 | 10/15/2003 | P | CANC |
Troy Cobbley
|
|
|
Would like inspection for 2:00pm, Simplex Grinnell will be onsite for their final at this time; Phone #: ###-#### Internet Inspection Request from: Robert Bailey
|
INSP-Final Inspection | 10/14/2003 | 10/15/2003 | 10/15/2003 | P | FAIL |
Troy Cobbley
|
|
|
Provide map per note #17, provide breaker lock on the main breaker, the new battery charger and the existing NAC panel do not report a trouble at the main facp panel nor at the central station. Grinnell did not show up for their part of the test. No devices have been tested10/15/2003 3:36:28 PM 10/15/2003 3:37:47 PM
|
Plan assigned to (SAM) | 4/7/2003 | | 10/8/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 10/8/2003 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/8/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/8/2003 | | 10/8/2003 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/8/2003 | | DONE |
|
|
|
|
Telephone call | | | 10/8/2003 | | DONE |
|
|
|
permit ready and fee due
|
Issue and Print Permit | | | 10/8/2003 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/25/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 8/29/2003 | | FAIL |
|
|
|
Resubmittal required. Comments faxed to Bob Coulter 8/29/2003.
|
Plan resubmittals received | | | 8/14/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/6/2003 | | FAIL |
|
|
|
Resubmittal required. Plans do not include entire building as required by FD upgrade agreement; several design and plan deficiencies. Review comments faxed to Mountain Alarm, Bob Coulter.
|
Application received | | | 4/7/2003 | | |
|
|
|
|