DOC - Permit Finaled | 8/1/2003 | 8/1/2003 | 8/1/2003 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 8/1/2003 2:22:20 PM
|
INSP-Final Inspection | 8/1/2003 | 8/1/2003 | 8/1/2003 | P | PASS |
Rick Jackson
|
|
|
|
INSP-Final Inspection | 7/30/2003 | 7/30/2003 | 7/30/2003 | A | FAIL |
Rick Jackson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Trent Bice need one hour fire sprinkler riser room; ball drip on FDC; additional EQ on FDC; spare heads in head box; calc sticker; fire marshall tag on riser; sign on riser room door; escutcheons; some heads obstructed; straps needed; 7/30/2003 11:46:45 AM
|
INSP-Sprinkler Rough-in/Hydro | 7/23/2003 | 7/24/2003 | 7/24/2003 | A | PART |
Troy Cobbley
|
|
|
above ground hydro test ok after 2nd try 7/24/2003 2:40:52 PM
|
INSP-Sprinkler Rough-in/Hydro | 5/19/2003 | 5/19/2003 | 5/19/2003 | P | PART |
Rick Jackson
|
|
|
This is for your walkthrough that you performed on friday; Phone #: ###-#### Internet Inspection Request from: Trent Bice flange fitting at UG connection to meet NFPA 13 Table 3-5.1; r/i okay 5/19/2003 12:25:57 PM
|
Inspection Record Card- Fire | 4/15/2003 | | 4/15/2003 | | DONE |
|
|
|
|
Telephone call | | | 4/15/2003 | | DONE |
|
|
|
permit ready
|
Issue permit | | | 4/15/2003 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 4/11/2003 | | 4/14/2003 | | DONE |
|
|
|
4/14/2003 16:27:56 JWA - activity updated through activity FIRA22 from case FIR03-00174.
|
Sprinkler Plan Check | 4/11/2003 | | 4/14/2003 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/14/2003 | | DONE |
Bill Alexander
|
|
|
|
Application received | | | 4/11/2003 | | |
|
|
|
|