INSP-Final Inspection | 10/17/2003 | 10/23/2003 | 10/23/2003 | A | PASS |
Rick Jackson
|
|
|
This is Grants cell This inspection needs to be done at 7:00 am if possiable thank you and have a great weekend!; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
|
DOC - Permit Finaled | 10/23/2003 | 10/23/2003 | 10/23/2003 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 10/23/2003 10:39:07 AM
|
INSP-Final Inspection | 10/14/2003 | 10/17/2003 | 10/17/2003 | A | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/14/2003 at 1:48:31 PM. Contact: ###-####. Inspection cancelled from web by: Terry Owsley
|
Issue permit | | | 10/6/2003 | | |
|
|
|
|
Inspection Record Card- Fire | 10/1/2003 | | 10/1/2003 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/1/2003 | | DONE |
|
|
|
|
Telephone call | | | 10/1/2003 | | DONE |
|
|
|
grant
|
Alarm Plan Check | | | 9/30/2003 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
Plan assigned to (SAM) | 4/23/2003 | | 9/30/2003 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/24/2003 | | DONE |
|
|
|
|
Telephone call | | | 9/18/2003 | | DONE |
|
|
|
Received phone call from David (GC) regarding status. We discussed the voltage drop calc and the battery calculation requirement. He will either drop off the required information, or fax it to me.
|
Alarm Plan Check | | | 8/12/2003 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Rob Ahten, Protex 8/12/2003.
|
Plan resubmittals received | | | 8/5/2003 | | DONE |
|
|
|
battery calcs. Mary took them
|
Alarm Plan Check | | | 5/14/2003 | | FAIL |
|
|
|
Resubmittal required.
|
Miscellaneous action | | | 5/1/2003 | | DONE |
Sam Rogers
|
|
|
I faxed the fire alarm permit application back to Protex with areas clouded that needed filled out. ###-####
|
Application received | | | 4/23/2003 | | |
|
|
|
|