Permit Information
Permit NumberFIR03-00213
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 1063 W BOEING ST
Project NameSPR BOEING W.H.#7 PAINT BOOTH
Customer Number 
ePlanReview 
Description
(OFFICE ENVIRONMENT COMPANY)(BOEING WAREHOUSE #7) To install a fire sprinkler system in a #IPB-1000, Standard Tools / Tools USA brand, pre-manufactured spray paint booth, located in the northeast corner of the tenant warehouse per plans on file. This building is fully sprinklered for allowable area increase & high pile storage. A LETTER OF COMPLETION / COMPLIANCE" IS REQUIRED FOR THIS PROJECT AS A CONDITION OF THE BUILDING PERMIT OF WHICH THIS FIRE PERMIT IS ATTACHED - BLD01-02873. All fire sprinkler system work shall be in accordance to NFPA 13-1999, complying with the 1997 - UFC and attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to Building Permit: BLD01-02873.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/5/20044/5/20044/5/2004APASS
DetailsRick Jackson
DOC - Permit Finaled4/5/20044/5/20044/5/2004APASS
DetailsRick Jackson
Finaled by inspector at 4/5/2004 9:45:12 AM
INSP-Final Inspection7/10/20037/10/20037/10/2003PPART
DetailsRick Jackson
todd; Phone #: ###-#### Internet Inspection Request from: Barbara Moore need tamper submittals 7/10/2003 3:57:33 PM
Inspection Record Card- Fire6/3/2003 6/3/2003 DONE
Telephone call  6/3/2003 DONE
LEFT MESS THAT PERMIT IS READY
Issue and Print Permit  6/3/2003 DONE
Sprinkler Plan Check5/29/2003 6/2/2003 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  6/2/2003 DONE
DetailsBill Alexander
Plan assigned to (Bill)4/30/2003 6/2/2003 DONE
DetailsBill Alexander
6/2/2003 15:41:04 JWA - activity updated through activity FIRA22 from case FIR03-00213.
Plan resubmittals received  5/29/2003  
Telephone call  5/23/2003 DONE
LEFT MESS THAT PLANS HAVE BEEN DENIED & NEED PICKED UP
Sprinkler Plan Check5/20/2003 5/22/2003 FAIL
DetailsBill Alexander
Provided revised sprinkler heads (Central Model "BV", ½" S.R. 5.6 K-factor). These sprinklers are also listed for Light and Ordinary Hazard protection only. Reference data submittal, 1st paragraph page #2 (Design Criteria). (NFPA 13:3-1.1) Revise and resubmit sprinkler heads that are listed for the application and occupancy hazard.
No indication provided that tamper supervision will be installed. If this facility has more than 100 fire sprinklers, tamper supervision will be required. (UFC 1003.3.1) Provide clarification/data submittal on an approved control valve and tamper device installing.
Miscellaneous action  5/22/2003 DONE
DetailsBill Alexander
Took plans to front desk for calling and returning. Emailed copy to Grinnell.
Plan resubmittals received  5/20/2003  
DetailsBill Alexander
Sprinkler Plan Check4/30/2003 5/1/2003 FAIL
DetailsBill Alexander
Plan, submittals failed. Lack installation to codes.
Miscellaneous action  5/1/2003 DONE
Took plans to front desk for calling and returning. Faxed copy to Grinnell.
Telephone call  5/1/2003 DONE
left mess that permit is ready
Application received  4/30/2003