INSP-Final Inspection | 4/5/2004 | 4/5/2004 | 4/5/2004 | A | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 4/5/2004 | 4/5/2004 | 4/5/2004 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 4/5/2004 9:45:12 AM
|
INSP-Final Inspection | 7/10/2003 | 7/10/2003 | 7/10/2003 | P | PART |
Rick Jackson
|
|
|
todd; Phone #: ###-#### Internet Inspection Request from: Barbara Moore need tamper submittals 7/10/2003 3:57:33 PM
|
Inspection Record Card- Fire | 6/3/2003 | | 6/3/2003 | | DONE |
|
|
|
|
Telephone call | | | 6/3/2003 | | DONE |
|
|
|
LEFT MESS THAT PERMIT IS READY
|
Issue and Print Permit | | | 6/3/2003 | | DONE |
|
|
|
|
Sprinkler Plan Check | 5/29/2003 | | 6/2/2003 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/2/2003 | | DONE |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 4/30/2003 | | 6/2/2003 | | DONE |
Bill Alexander
|
|
|
6/2/2003 15:41:04 JWA - activity updated through activity FIRA22 from case FIR03-00213.
|
Plan resubmittals received | | | 5/29/2003 | | |
|
|
|
|
Telephone call | | | 5/23/2003 | | DONE |
|
|
|
LEFT MESS THAT PLANS HAVE BEEN DENIED & NEED PICKED UP
|
Sprinkler Plan Check | 5/20/2003 | | 5/22/2003 | | FAIL |
Bill Alexander
|
|
|
Provided revised sprinkler heads (Central Model "BV", ½" S.R. 5.6 K-factor). These sprinklers are also listed for Light and Ordinary Hazard protection only. Reference data submittal, 1st paragraph page #2 (Design Criteria). (NFPA 13:3-1.1) Revise and resubmit sprinkler heads that are listed for the application and occupancy hazard.
No indication provided that tamper supervision will be installed. If this facility has more than 100 fire sprinklers, tamper supervision will be required. (UFC 1003.3.1) Provide clarification/data submittal on an approved control valve and tamper device installing.
|
Miscellaneous action | | | 5/22/2003 | | DONE |
Bill Alexander
|
|
|
Took plans to front desk for calling and returning. Emailed copy to Grinnell.
|
Plan resubmittals received | | | 5/20/2003 | | |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 4/30/2003 | | 5/1/2003 | | FAIL |
Bill Alexander
|
|
|
Plan, submittals failed. Lack installation to codes.
|
Miscellaneous action | | | 5/1/2003 | | DONE |
|
|
|
Took plans to front desk for calling and returning. Faxed copy to Grinnell.
|
Telephone call | | | 5/1/2003 | | DONE |
|
|
|
left mess that permit is ready
|
Application received | | | 4/30/2003 | | |
|
|
|
|