INSP-Final Inspection | 10/1/2003 | 10/2/2003 | 10/2/2003 | A | PASS |
Rick Jackson
|
|
|
This is Bobs # from Lea Electric; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
|
DOC - Permit Finaled | 10/2/2003 | 10/2/2003 | 10/2/2003 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 10/2/2003 10:53:42 AM
|
INSP-Final Inspection | 9/30/2003 | 9/30/2003 | 9/30/2003 | P | FAIL |
Troy Cobbley
|
|
|
fire alarm signals are still not being reported correctly or the monitoring company does not know what they are doing. 9/30/2003 3:52:04 PM
|
INSP-Final Inspection | 9/26/2003 | 9/26/2003 | 9/26/2003 | P | FAIL |
Troy Cobbley
|
|
|
The monitoring company had the account messed up. No inspection performed 9/26/2003 3:19:11 PM
|
INSP-Final Inspection | 9/23/2003 | 9/24/2003 | 9/24/2003 | A | NR |
Rick Jackson
|
|
|
This is Grants Cell Have a great Afternoon; Phone #: ###-#### Internet Inspection Request from: Terry Owsley 9/24/2003 9:46:03 AM
|
INSP-Final Inspection | 9/24/2003 | 9/24/2003 | 9/24/2003 | P | FAIL |
Troy Cobbley
|
|
|
duct detector signals arrive at the monitoring station as gatevavles, pull in lobby comes in as pull - fire, smoke in lobby comes in as general alarm, update the map to show the duct detectors, verify that the 8521 address is reported separatly 9/24/2003 2:54:13 PM
|
Issue and Print Permit | | | 9/23/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 9/22/2003 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/22/2003 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/17/2003 | | DONE |
|
|
|
Resubmitual received: Fax from Protex that contains a letter from Silent Knight that states the pull station PS-DA can be used with a plastic cover to divert moisture. Temperature is not a factor.
|
Plan resubmittals received | | | 9/11/2003 | | DONE |
|
|
|
|
INSP-Final Inspection | 9/4/2003 | 9/5/2003 | 9/5/2003 | A | FAIL |
Troy Cobbley
|
|
|
Inspection was for the clubhouse. Duct smoke detectors need to be provided. Review notes have not been followed. I stopped the inspection. Inspection to be called in after verifying all comments have been addressed 9/5/2003 2:15:25 PM
|
Issue permit | | | 9/4/2003 | | |
|
|
|
|
Plan assigned to (SAM) | 5/1/2003 | | 9/3/2003 | | DONE |
|
|
|
9/3/2003 11:06:30 M_F - activity updated through activity FIRA22 from case FIR03-00216.
|
Alarm Plan Check | | | 9/3/2003 | | PASS |
|
|
|
Resubmittal required on item #14, UL listing on pull station for outside usage with cover, prior to a final on the fire alarm system. All other items are approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/3/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/3/2003 | | 9/3/2003 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/3/2003 | | DONE |
|
|
|
|
Telephone call | | | 9/3/2003 | | DONE |
|
|
|
permit ready and fees due
|
Plan resubmittals received | | | 8/14/2003 | | DONE |
|
|
|
|
Telephone call | | | 8/7/2003 | | |
|
|
|
Called Rob Ahten to notify him that the drawings that he submitted are not clouded as he stated. I requested that he re-submit with 2 complete sets as required. He stated he would.
|
Plan resubmittals received | | | 8/5/2003 | | |
|
|
|
|
Telephone call | | | 7/29/2003 | | |
|
|
|
Called to remind Rob that he was to stop by and "cloud" the changes on the Aspen Springs Apartment resubmittal (he agreed to do so 7/17/2003). Left a message.
|
Telephone call | | | 7/17/2003 | | |
|
|
|
Phoned Rob Ahten at Protex to request that he "cloud" his changes from the previous submittal per the FA permit Plan Review Requirements. He stated he would be down after lunch.
|
Miscellaneous action | | | 6/19/2003 | | DONE |
|
|
|
Request approved to begin installation without approved plans with Protex assuming full finacial responsibility for any potential changes necessary to comply with approved plans.
|
Plan resubmittals received | | | 6/18/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/29/2003 | | FAIL |
|
|
|
Resubmittal required.
|
Plan resubmittals received | | | 5/28/2003 | | |
|
|
|
|
Alarm Plan Check | | | 5/14/2003 | | FAIL |
|
|
|
Application information incorrect, incomplete. Faxed to Rob Ahten, Protex 5/14/2003.
|
Application received | | | 5/1/2003 | | |
|
|
|
|