Permit Information
Permit NumberFIR03-00216
StatusFinaled
Name PROTEX
Site Address 8519 W FAIRVIEW AVE
Project Namealm - ASPEN SPRINGS APARTMENTS
Customer Number 
ePlanReview 
Description
The data has been moved to a Word document attached to this case.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/1/200310/2/200310/2/2003APASS
DetailsRick Jackson
This is Bobs # from Lea Electric; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
DOC - Permit Finaled10/2/200310/2/200310/2/2003APASS
DetailsRick Jackson
Finaled by inspector at 10/2/2003 10:53:42 AM
INSP-Final Inspection9/30/20039/30/20039/30/2003PFAIL
DetailsTroy Cobbley
fire alarm signals are still not being reported correctly or the monitoring company does not know what they are doing. 9/30/2003 3:52:04 PM
INSP-Final Inspection9/26/20039/26/20039/26/2003PFAIL
DetailsTroy Cobbley
The monitoring company had the account messed up. No inspection performed 9/26/2003 3:19:11 PM
INSP-Final Inspection9/23/20039/24/20039/24/2003ANR
DetailsRick Jackson
This is Grants Cell Have a great Afternoon; Phone #: ###-#### Internet Inspection Request from: Terry Owsley 9/24/2003 9:46:03 AM
INSP-Final Inspection9/24/20039/24/20039/24/2003PFAIL
DetailsTroy Cobbley
duct detector signals arrive at the monitoring station as gatevavles, pull in lobby comes in as pull - fire, smoke in lobby comes in as general alarm, update the map to show the duct detectors, verify that the 8521 address is reported separatly 9/24/2003 2:54:13 PM
Issue and Print Permit  9/23/2003 DONE
Alarm Plan Check  9/22/2003 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  9/22/2003 DONE
Plan resubmittals received  9/17/2003 DONE
Resubmitual received: Fax from Protex that contains a letter from Silent Knight that states the pull station PS-DA can be used with a plastic cover to divert moisture. Temperature is not a factor.
Plan resubmittals received  9/11/2003 DONE
INSP-Final Inspection9/4/20039/5/20039/5/2003AFAIL
DetailsTroy Cobbley
Inspection was for the clubhouse. Duct smoke detectors need to be provided. Review notes have not been followed. I stopped the inspection. Inspection to be called in after verifying all comments have been addressed 9/5/2003 2:15:25 PM
Issue permit  9/4/2003  
Plan assigned to (SAM)5/1/2003 9/3/2003 DONE
9/3/2003 11:06:30 M_F - activity updated through activity FIRA22 from case FIR03-00216.
Alarm Plan Check  9/3/2003 PASS
Resubmittal required on item #14, UL listing on pull station for outside usage with cover, prior to a final on the fire alarm system. All other items are approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  9/3/2003 DONE
Inspection Record Card- Fire9/3/2003 9/3/2003 DONE
Permit Ready to Issue  9/3/2003 DONE
Telephone call  9/3/2003 DONE
permit ready and fees due
Plan resubmittals received  8/14/2003 DONE
Telephone call  8/7/2003  
Called Rob Ahten to notify him that the drawings that he submitted are not clouded as he stated. I requested that he re-submit with 2 complete sets as required. He stated he would.
Plan resubmittals received  8/5/2003  
Telephone call  7/29/2003  
Called to remind Rob that he was to stop by and "cloud" the changes on the Aspen Springs Apartment resubmittal (he agreed to do so 7/17/2003). Left a message.
Telephone call  7/17/2003  
Phoned Rob Ahten at Protex to request that he "cloud" his changes from the previous submittal per the FA permit Plan Review Requirements. He stated he would be down after lunch.
Miscellaneous action  6/19/2003 DONE
Request approved to begin installation without approved plans with Protex assuming full finacial responsibility for any potential changes necessary to comply with approved plans.
Plan resubmittals received  6/18/2003 DONE
Alarm Plan Check  5/29/2003 FAIL
Resubmittal required.
Plan resubmittals received  5/28/2003  
Alarm Plan Check  5/14/2003 FAIL
Application information incorrect, incomplete. Faxed to Rob Ahten, Protex 5/14/2003.
Application received  5/1/2003