Permit Information
Permit NumberFIR03-00217
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 405 S 8TH ST
Project NameSPR PIECE UNIQUE
Customer Number 
ePlanReview 
Description
(PIECE UNIQUE)(8TH STREET MARKETPLACE-SUITE 155) To add fire sprinkler protection in new infill of an existing floor opening in the remodel of an 893-ft/2-retail space for new tenant per plans on file. This building is fully sprinklered as substitution for 1-hour construction per records on file. The fire sprinkler system work shall be installed in accordance to NFPA 13-1999, complying with the IFC-2000 and attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to garage shell permit: BLD03-00703.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/11/20036/12/20036/12/2003APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 6/11/2003 at 2:42:40 PM.
DOC - Permit Finaled6/12/20036/12/20036/12/2003PPASS
DetailsRick Jackson
Finaled by inspector at 6/12/2003 12:55:46 PM
Issue and Print Permit  6/9/2003 DONE
PLANS/APPL TAKEN TO FRONT DESK  6/6/2003 DONE
Telephone call  6/6/2003 DONE
permit ready
Plan assigned to (Bill)6/3/2003 6/3/2003 DONE
DetailsBill Alexander
Plan resubmittals received  6/3/2003  
Telephone call  5/30/2003 DONE
Received call from Ross Ferris to through this submittal away.
Plan resubmittals received  5/28/2003 DONE
Contractor called and requested to hold off on review untill further notice. Changes coming.
Telephone call  5/28/2003 DONE
Contractor called and requested to hold off on review untill further notice. Changes coming.
Sprinkler Plan Check5/20/2003 5/23/2003 FAIL
DetailsBill Alexander
This tenant work scope shall include upgrading of the existing piping (in the tenant "Permitted" work scope area/s, to conform to current Ordinary Group 2 "Pipe Scheduled" piping or an Ordinary Group 2 calculated design (contractors choice). (NFPA 13:7-2.2.1, 8-5, IFC 903.3.1.1 and 901.4)
The basement 2" end-of-main nipple-and-cap located in the wrong position. Need to relocate nipple-and-cap "inline" with the existing 2" main.
Need to meet the requirements of the State Fire Marshal and NFPA 13:7-2.2.1, 8-5, 8-5.1.1 and 8-5.3, which is detailed information on number of heads on existing lines and mains, etc. Plan does not provide enough information to verify the appropriate pipe schedule design.
Miscellaneous action  5/23/2003 DONE
DetailsBill Alexander
Took plans to inspection/plans desk for calling and returning to De Best Fire Protection. Emailed copy of review notes to Ross Farris-DeBest Fire Protection 10:00 am.
Telephone call  5/23/2003 DONE
LEFT MESS THAT PERMIT IS READY
Plan resubmittals received  5/20/2003  
Issue and Print Permit  5/5/2003 DONE
Inspection Record Card- Fire5/2/2003 5/2/2003 DONE
Telephone call  5/2/2003 DONE
LEFT MESS THAT PERMIT IS READY
Sprinkler Plan Check5/1/2003 5/2/2003 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  5/2/2003 DONE
DetailsBill Alexander
Plan assigned to (Bill)5/1/2003 5/1/2003 DONE
DetailsBill Alexander
Application received  5/1/2003  
DetailsBill Alexander
Sprinkler Plan Check6/3/2003 6/6/2002 PASS
DetailsBill Alexander
This was a plan design verification of 2nd submittal of work added which failed.
Inspection Record Card- Fire5/2/2003