Permit NumberFIR03-00220
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 190 E BANNOCK ST
Project NameSPR ST LUKES E. TOWER 4TH FLR
Customer Number 
ePlanReview 
Description
(ST LUKES-EAST TOWER-4TH FLR)(PEDIATRIC & PICU EXPANSION) To install new fire sprinkler protection in an 18,000-ft/2, 4th floor previously installed of the ETE-2000 shell & core (FIR01-00323). Work is related to instillation and completion of exit corridor, patient suites, restrooms, and support areas throughout. This building is fully sprinklered. The fire sprinkler system work shall comply with NFPA 13-1999, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD02-00055. (4/7/03 - Plan modification submitted by Architect).
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
(F) Reprint permit  3/29/2005  
INSP-Final Inspection11/21/200311/21/200311/21/2003APASS
DetailsRick Jackson
DOC - Permit Finaled11/21/200311/21/200311/21/2003APASS
DetailsRick Jackson
Finaled by inspector at 11/21/2003 10:01:30 AM
Sprinkler Plan Check10/27/2003 10/27/2003 PASS
As-builts - plan modifications, faxed 10/27/2003, from Brad B. - Viming.
INSP-Final Inspection10/23/200310/24/200310/24/2003PPART
DetailsRick Jackson
Merl; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes will need as-builts submitted before final occupancy; hydro okay; minor changes made to plans due to duct work, etc. 10/24/2003 2:53:58 PM
INSP-Sprinkler Rough-in10/15/200310/16/200310/16/2003PPART
DetailsRick Jackson
###-#### merle okay to cover rooms on north side; one room on west side shows two heads and one installed - calc room size and if over design then add head as shown on plans; heads within 1 ft of diffusers to be intermidiate temp 10/16/2003 11:07:45 AM
Issue and Print Permit  10/15/2003 DONE
Sprinkler Plan Check10/6/2003 10/6/2003 PASS
DetailsBill Alexander
Additional work review and approved as submitted on 10/1/2003
PLANS/APPL TAKEN TO FRONT DESK  10/6/2003 DONE
DetailsBill Alexander
Inspection Record Card- Fire10/6/2003 10/6/2003 DONE
Permit Ready to Issue  10/6/2003 DONE
Telephone call  10/6/2003 DONE
Spoke with Diane told permit ready & fees
Plan resubmittals received  10/1/2003 DONE
FIR-Aging Inspection9/12/20039/12/20039/12/2003 PASS
DetailsRick Jackson
work in progress 9/12/2003 7:33:41 AM
CHANGE STATUS TO (ISS)  7/7/2003 DONE
Telephone call  7/3/2003 DONE
LEFT MESS THAT PERMIT IS READY
Sprinkler Plan Check7/1/2003 7/2/2003 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  7/2/2003 DONE
DetailsBill Alexander
Plan resubmittals received  7/1/2003 DONE
Issue permit  6/13/2003 DONE
Plan assigned to (Bill)5/5/2003 6/6/2003 DONE
6/6/2003 14:36:40 JWA - activity updated through activity FIRA22 from case FIR03-00220.
Sprinkler Plan Check6/4/2003 6/6/2003 PASS
DetailsBill Alexander
Clarified plans for interpretating installation code. Reference review dated 05/15/03.
PLANS/APPL TAKEN TO FRONT DESK  6/6/2003 DONE
Inspection Record Card- Fire6/6/2003 6/6/2003 DONE
Telephone call  6/6/2003 DONE
permit ready and fees due
Plan resubmittals received  6/4/2003 DONE
Telephone call  5/16/2003 DONE
called to pick up denied plans
Sprinkler Plan Check5/5/2003 5/15/2003 FAIL
DetailsBill Alexander
Overspacing from original design without verification. Plans are not definitive and readable as submitted in determining code.
Miscellaneous action  5/15/2003 DONE
faxed copy of review to Viking and took plans to front desk for calling and returning for corrections.
Application received  5/5/2003