(F) Reprint permit | | | 3/29/2005 | | |
|
|
|
|
INSP-Final Inspection | 11/21/2003 | 11/21/2003 | 11/21/2003 | A | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 11/21/2003 | 11/21/2003 | 11/21/2003 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 11/21/2003 10:01:30 AM
|
Sprinkler Plan Check | 10/27/2003 | | 10/27/2003 | | PASS |
|
|
|
As-builts - plan modifications, faxed 10/27/2003, from Brad B. - Viming.
|
INSP-Final Inspection | 10/23/2003 | 10/24/2003 | 10/24/2003 | P | PART |
Rick Jackson
|
|
|
Merl; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes will need as-builts submitted before final occupancy; hydro okay; minor changes made to plans due to duct work, etc. 10/24/2003 2:53:58 PM
|
INSP-Sprinkler Rough-in | 10/15/2003 | 10/16/2003 | 10/16/2003 | P | PART |
Rick Jackson
|
|
|
###-#### merle okay to cover rooms on north side; one room on west side shows two heads and one installed - calc room size and if over design then add head as shown on plans; heads within 1 ft of diffusers to be intermidiate temp 10/16/2003 11:07:45 AM
|
Issue and Print Permit | | | 10/15/2003 | | DONE |
|
|
|
|
Sprinkler Plan Check | 10/6/2003 | | 10/6/2003 | | PASS |
Bill Alexander
|
|
|
Additional work review and approved as submitted on 10/1/2003
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/6/2003 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 10/6/2003 | | 10/6/2003 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/6/2003 | | DONE |
|
|
|
|
Telephone call | | | 10/6/2003 | | DONE |
|
|
|
Spoke with Diane told permit ready & fees
|
Plan resubmittals received | | | 10/1/2003 | | DONE |
|
|
|
|
FIR-Aging Inspection | 9/12/2003 | 9/12/2003 | 9/12/2003 | | PASS |
Rick Jackson
|
|
|
work in progress 9/12/2003 7:33:41 AM
|
CHANGE STATUS TO (ISS) | | | 7/7/2003 | | DONE |
|
|
|
|
Telephone call | | | 7/3/2003 | | DONE |
|
|
|
LEFT MESS THAT PERMIT IS READY
|
Sprinkler Plan Check | 7/1/2003 | | 7/2/2003 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/2/2003 | | DONE |
Bill Alexander
|
|
|
|
Plan resubmittals received | | | 7/1/2003 | | DONE |
|
|
|
|
Issue permit | | | 6/13/2003 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 5/5/2003 | | 6/6/2003 | | DONE |
|
|
|
6/6/2003 14:36:40 JWA - activity updated through activity FIRA22 from case FIR03-00220.
|
Sprinkler Plan Check | 6/4/2003 | | 6/6/2003 | | PASS |
Bill Alexander
|
|
|
Clarified plans for interpretating installation code. Reference review dated 05/15/03.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/6/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/6/2003 | | 6/6/2003 | | DONE |
|
|
|
|
Telephone call | | | 6/6/2003 | | DONE |
|
|
|
permit ready and fees due
|
Plan resubmittals received | | | 6/4/2003 | | DONE |
|
|
|
|
Telephone call | | | 5/16/2003 | | DONE |
|
|
|
called to pick up denied plans
|
Sprinkler Plan Check | 5/5/2003 | | 5/15/2003 | | FAIL |
Bill Alexander
|
|
|
Overspacing from original design without verification. Plans are not definitive and readable as submitted in determining code.
|
Miscellaneous action | | | 5/15/2003 | | DONE |
|
|
|
faxed copy of review to Viking and took plans to front desk for calling and returning for corrections.
|
Application received | | | 5/5/2003 | | |
|
|
|
|