INSP-Final Inspection | 3/19/2004 | 3/19/2004 | 3/19/2004 | A | CANC |
Troy Cobbley
|
|
|
To be rescheduled 3/19/2004 7:46:02 AM
|
INSP-Final Inspection | 3/19/2004 | 3/19/2004 | 3/19/2004 | P | PASS |
Troy Cobbley
|
|
|
fire alarm finaled 3/19/2004 1:33:36 PM
|
DOC - Permit Finaled | 3/19/2004 | 3/19/2004 | 3/19/2004 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 3/19/2004 1:33:41 PM
|
INSP-Final Inspection | 3/15/2004 | 3/17/2004 | 3/17/2004 | A | FAIL |
Troy Cobbley
|
|
|
Induct detectors did not operate dampers 3/17/2004 9:59:38 AM
|
INSP-Final Inspection | 2/24/2004 | 2/27/2004 | 2/27/2004 | P | FAIL |
Troy Cobbley
|
|
|
The in-duct smoke detectors did not operate. Verify a/v's operate. Provide city approved building plans for life safety review. 2/27/2004 3:34:45 PM
|
INSP-Final Inspection | 2/16/2004 | 2/19/2004 | 2/17/2004 | P | CANC |
Troy Cobbley
|
|
|
Scheduled by a contractor via Hello! on 2/16/2004 at 1:51:45 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Feb 17 2004 6:21PM.
|
INSP-Conference | 11/4/2003 | 11/6/2003 | 11/6/2003 | A | DONE |
Troy Cobbley
|
|
|
met with steve and charlie about what is needed to finish up the four open FIR permits 11/6/2003 12:45:14 PM
|
FIR-Aging Inspection | 9/11/2003 | 9/11/2003 | 9/11/2003 | | NR |
Troy Cobbley
|
|
|
work in progress per Chris with SimplexGrinnell 9/12/2003 3:27:15 PM
|
Inspection Record Card- Fire | 6/12/2003 | | 6/12/2003 | | DONE |
|
|
|
|
Telephone call | | | 6/12/2003 | | DONE |
|
|
|
CALLED CHRIS WILLIS 6-12-03 PERMIT READY FEE GIVEN $ 130.20
|
Issue and Print Permit | | | 6/12/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 6/11/2003 | | DONE |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/11/2003 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 5/6/2003 | | 6/11/2003 | | DONE |
|
|
|
6/11/2003 15:07:38 M_F - activity updated through activity FIRA22 from case FIR03-00224.
|
Plan resubmittals received | | | 6/10/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/21/2003 | | FAIL |
|
|
|
Resubmittal required. Comments faxed to Chris Willis, Simplex Grinnell 5/21/2003.
|
Application received | | | 5/6/2003 | | |
|
|
|
|