INSP-Final Inspection | 8/22/2003 | 8/22/2003 | 8/22/2003 | P | PASS |
Troy Cobbley
|
|
|
Fire sprinklers finaled. Inspector program shows the resubmitted plans dated 8/11 have not been picked up yet, but the plans are here on site. I'm doc finaling it.
|
DOC - Permit Finaled | 8/22/2003 | 8/22/2003 | 8/22/2003 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 8/22/2003 3:35:05 PM
|
Plan assigned to (Bill) | 8/8/2003 | | 8/11/2003 | | DONE |
Bill Alexander
|
|
|
8/11/2003 09:44:57 JWA - activity updated through activity FIRA22 from case FIR03-00228.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/11/2003 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 8/11/2003 | | 8/11/2003 | | DONE |
|
|
|
|
Plan resubmittals received | | | 8/8/2003 | | |
Bill Alexander
|
|
|
|
INSP-Final Inspection | 8/4/2003 | 8/5/2003 | 8/5/2003 | A | FAIL |
Troy Cobbley
|
|
|
replace painted pendant in the restroom on the 2nd floor, provide missing canopies, provide tile in the comm. room, provide ceiling in the sky light area, provide tags for riser and backflow preventer, provide knox key box, provide forward flush for the backflow preventor, test all sprinkler devices 8/5/2003 1:08:23 PM
|
INSP-Sprinkler Rough-in/Hydro | 6/11/2003 | 6/12/2003 | 6/12/2003 | A | PART |
Troy Cobbley
|
|
|
pendant sprinkler head piping in the second floor tenant is ok for cover in areas of hard lid 6/12/2003 2:26:07 PM
|
Issue and Print Permit | | | 5/20/2003 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 5/7/2003 | | 5/19/2003 | | DONE |
|
|
|
5/19/2003 14:22:19 JWA - activity updated through activity FIRA22 from case FIR03-00228.
|
Sprinkler Plan Check | 5/8/2003 | | 5/19/2003 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/19/2003 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 5/19/2003 | | 5/19/2003 | | DONE |
|
|
|
|
Telephone call | | | 5/19/2003 | | DONE |
|
|
|
CALLED 5-19-03
|
Application received | | | 5/7/2003 | | |
|
|
|
|