INSP-Final Inspection | 3/12/2010 | 3/12/2010 | 3/12/2010 | P | PASS |
Forrest France
|
|
|
Site verified sprinkler riser is monitored by the fire alarm system during an inspection for wireless radio transmission work done by Allied General. Aging fire sprinkler permit final okayed.
|
Miscellaneous action | | | 3/12/2010 | | DONE |
|
|
|
Sent email requesting project status.
|
INSP-Final Inspection | 7/31/2003 | 7/31/2003 | 7/31/2003 | A | PART |
Troy Cobbley
|
|
|
Fire alarm and fire life safety given a temporary occupancy per Dave Miller until the main control vavle has been supervised by the fire alarm system. This will require city approved drawings. Contractor still needs to provide the annual inspection report so any other major issues can be addressed
|
INSP-Final Inspection | 7/30/2003 | 7/30/2003 | 7/30/2003 | P | FAIL |
Troy Cobbley
|
|
|
The main control vavle in the basement is not supervised by the fire alarm system. I could not verify any other possibly unsupervised valves. All valves to be supervised per review note #7. See NFPA 13 and NFPA 72. Provide inspection report. See review note #6. Provide canopies on pendants. 7/30/2003 12:28:42 PM
|
INSP-Final Inspection | 7/15/2003 | 7/16/2003 | 7/16/2003 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 7/15/2003 at 6:51:11 PM. Contact: ###-####.
(This is a rough-in inspection) Sprinkler coverage is lacking (IFC 903.3.1.1)
Lack access to verifiy existing riser, system supervision and flow, signage and current annual system inspection. (JWA)
|
Issue and Print Permit | | | 6/4/2003 | | DONE |
|
|
|
|
Application received | | | 5/9/2003 | | |
|
|
|
|
Plan assigned to (Bill) | 5/9/2003 | | 5/9/2003 | | DONE |
|
|
|
5/9/2003 11:12:27 JWA - activity updated through activity FIRA22 from case FIR03-00233.
|
Sprinkler Plan Check | 5/9/2003 | | 5/9/2003 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/9/2003 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 5/9/2003 | | 5/9/2003 | | DONE |
|
|
|
|
Telephone call | | | 5/9/2003 | | DONE |
|
|
|
CALLED 5-9-03
|