INSP-Final Inspection | 9/29/2003 | 9/30/2003 | 9/30/2003 | A | PASS |
Rick Jackson
|
|
|
Please call 1 hour in advance in order to schedule with the owner. Thankyou; Phone #: ###-#### Internet Inspection Request from: Trent Bice
|
DOC - Permit Finaled | 9/30/2003 | 9/30/2003 | 9/30/2003 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 9/30/2003 1:52:59 PM
|
FIR-Aging Inspection | 9/19/2003 | 9/19/2003 | 9/19/2003 | | NR |
Troy Cobbley
|
|
|
wip 9/19/2003 9:09:59 AM
|
Issue permit | | | 6/20/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/18/2003 | | 6/18/2003 | | DONE |
|
|
|
|
Telephone call | | | 6/18/2003 | | DONE |
|
|
|
LEFT MESS THAT PERMIT IS READY
|
Plan assigned to (Bill) | 5/14/2003 | | 6/17/2003 | | DONE |
Bill Alexander
|
|
|
6/17/2003 14:37:49 JWA - activity updated through activity FIRA22 from case FIR03-00241.
|
Sprinkler Plan Check | 6/13/2003 | | 6/17/2003 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/17/2003 | | DONE |
Bill Alexander
|
|
|
|
Plan resubmittals received | | | 6/13/2003 | | DONE |
|
|
|
|
Miscellaneous action | | | 6/11/2003 | | DONE |
|
|
|
Added Fire Permit to Building permit.
|
Sprinkler Plan Check | 5/14/2003 | | 5/22/2003 | | FAIL |
Bill Alexander
|
|
|
Racking requires a current building permit for attaching.
Verify racking layout and show modification of the same with resubmittal.
Provide rack information, which includes height, levels in each, shelf types, dimensioned widths, lengths, transverse flue, and longitudinal flue, aisle width between rows.
Provide a section view of the building over this area showing the dimensioned elevation of the racking, commodity storage, truss system depths, width, type, location of roof protection, light fixtures, heat equipment, ducts.
The Sidewall sprinklers at the 15-ft elevation, pointed toward one side of the steel column, shall be detailed on the plan with a dimensioned section view. Provide details showing you are meeting the requirement of 6-4.2.
Provide a sprinkler head legend on the plans that identify all sprinklers, including temperature, etc.
|
Miscellaneous action | | | 5/22/2003 | | DONE |
|
|
|
Took failed plans to front desk for calling and returning to Shilo.
|
Telephone call | | | 5/22/2003 | | DONE |
|
|
|
LEFT MESS THAT PLANS FAILED & NEED TO PICKUP
|
Application received | | | 5/14/2003 | | |
|
|
|
|