Permit Information
Permit NumberFIR03-00246
StatusFinaled
Name SYNERGY ENGINEERS
Site Address 6259 W EMERALD
Project Namealm - Digestive Health Clinic
Customer Number 
ePlanReview 
Description
A new fire alarm system in new building. The system includes annunciation, HVAC shutdown, initiation, elevator recall and tie into nurse call on Group I occupancy.
The associated building permit (BLD 02-02339) is to construct a 13,779 sq. ft. single story Type IIN fully fire sprinklered medical clinic with a 5110 sq. ft. basement with patio area. The medical treatment area Group I1.2 has been designed as a suite per UBC Chapter 10. Other work includes all site improvements, paving and landscaping per approved plans and attachments and DRH01-00196 CUP01-00131. Fire sprinklers used for area.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/28/200310/28/200310/28/2003APASS
DetailsTroy Cobbley
DOC - Permit Finaled10/28/200310/28/200310/28/2003PPASS
DetailsTroy Cobbley
Finaled by inspector at 10/28/2003 12:00:17 PM
INSP-Alarm Testing10/22/200310/23/200310/23/2003PFAIL
DetailsTroy Cobbley
provide verification of emergency generator for note number 6, update map and provide sticker 10/23/2003 3:20:02 PM
CHANGE STATUS TO (ISS)  10/22/2003 DONE
(F) Reprint permit  9/2/2003 DONE
Alarm Plan Check  8/29/2003 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  8/29/2003 DONE
Telephone call  8/29/2003 DONE
spoke with Carol told permit ready & fees
Miscellaneous action  8/19/2003 DONE
Received via Synergy, a letter from Rauland, the manufacturer of the Responder 4000 Nurse call system panel, verifying this nurse call panel is UL listed for auxillary Fire Alarm connection, satisfying the resubmittal requirement on the permit issued 8/7/03.
Issue and Print Permit  8/8/2003 DONE
Alarm Plan Check  8/7/2003 PASS
Resubmittal is still required on the nurses station listing issue as stated in the comments item #1 prior to a final on the fire alarm system. All other items are approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  8/7/2003 DONE
Inspection Record Card- Fire8/7/2003 8/7/2003 DONE
Miscellaneous action  8/7/2003 DONE
Pre-citation notice sent to Quality Electric for work without a permit; and notification that this permit fee will be doubled.
Telephone call  8/7/2003  
Plan resubmittals received  8/5/2003  
Linda took in plans on 7-31-03 and Mary came and got them off her desk on 8-5-03
INSP-Conference7/30/20037/30/20037/30/2003PFAIL
DetailsTroy Cobbley
I stopped at this project to verify that no fire alarm work was being performed and found conduit, boxes and fire alarm FPLP 12 guage wiring installed. A stop work order was issued to Quality Electrics (###-####) job foreman who's name is Alan. The actually man that installed the fire alarm, who also works for quality is Scott according to Alan.
Telephone call  7/30/2003 DONE
Per additional information resubmitted today, and telcon discussion with Paul at Synergy and with Mary Froemke, all required resubmittal items have been satisfactorily resubmitted with exception of the required verification of the listing of the nurse call system for combined fire & nurse call uses.(ref UFC 1007.2.7.1.2) This is to be provided or resolved, but in the interim, approval is granted for installation work of the fire alarm system to continue, pending satisfactory resolution of this single issue, which must be resolved prior to final field approval of this alarm permit and the associated building permit.
Plan assigned to (SAM)5/19/2003 7/17/2003 DONE
7/17/2003 16:33:30 JWA - activity updated through activity FIRA22 from case FIR03-00090.
Alarm Plan Check  6/25/2003 FAIL
Resubmittal required. Faxed comments to Paul Highley 6/25/2003.
Telephone call  6/24/2003  
Phone call into Paul Highley to inquire about the power requirements for the visual displays in the corridors.
Alarm Plan Check  5/27/2003 FAIL
Resubmittal required.
Application received  5/19/2003