INSP-Final Inspection | 10/28/2003 | 10/28/2003 | 10/28/2003 | A | PASS |
Troy Cobbley
|
|
|
|
DOC - Permit Finaled | 10/28/2003 | 10/28/2003 | 10/28/2003 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 10/28/2003 12:00:17 PM
|
INSP-Alarm Testing | 10/22/2003 | 10/23/2003 | 10/23/2003 | P | FAIL |
Troy Cobbley
|
|
|
provide verification of emergency generator for note number 6, update map and provide sticker 10/23/2003 3:20:02 PM
|
CHANGE STATUS TO (ISS) | | | 10/22/2003 | | DONE |
|
|
|
|
(F) Reprint permit | | | 9/2/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 8/29/2003 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/29/2003 | | DONE |
|
|
|
|
Telephone call | | | 8/29/2003 | | DONE |
|
|
|
spoke with Carol told permit ready & fees
|
Miscellaneous action | | | 8/19/2003 | | DONE |
|
|
|
Received via Synergy, a letter from Rauland, the manufacturer of the Responder 4000 Nurse call system panel, verifying this nurse call panel is UL listed for auxillary Fire Alarm connection, satisfying the resubmittal requirement on the permit issued 8/7/03.
|
Issue and Print Permit | | | 8/8/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 8/7/2003 | | PASS |
|
|
|
Resubmittal is still required on the nurses station listing issue as stated in the comments item #1 prior to a final on the fire alarm system. All other items are approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/7/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/7/2003 | | 8/7/2003 | | DONE |
|
|
|
|
Miscellaneous action | | | 8/7/2003 | | DONE |
|
|
|
Pre-citation notice sent to Quality Electric for work without a permit; and notification that this permit fee will be doubled.
|
Telephone call | | | 8/7/2003 | | |
|
|
|
|
Plan resubmittals received | | | 8/5/2003 | | |
|
|
|
Linda took in plans on 7-31-03 and Mary came and got them off her desk on 8-5-03
|
INSP-Conference | 7/30/2003 | 7/30/2003 | 7/30/2003 | P | FAIL |
Troy Cobbley
|
|
|
I stopped at this project to verify that no fire alarm work was being performed and found conduit, boxes and fire alarm FPLP 12 guage wiring installed. A stop work order was issued to Quality Electrics (###-####) job foreman who's name is Alan. The actually man that installed the fire alarm, who also works for quality is Scott according to Alan.
|
Telephone call | | | 7/30/2003 | | DONE |
|
|
|
Per additional information resubmitted today, and telcon discussion with Paul at Synergy and with Mary Froemke, all required resubmittal items have been satisfactorily resubmitted with exception of the required verification of the listing of the nurse call system for combined fire & nurse call uses.(ref UFC 1007.2.7.1.2) This is to be provided or resolved, but in the interim, approval is granted for installation work of the fire alarm system to continue, pending satisfactory resolution of this single issue, which must be resolved prior to final field approval of this alarm permit and the associated building permit.
|
Plan assigned to (SAM) | 5/19/2003 | | 7/17/2003 | | DONE |
|
|
|
7/17/2003 16:33:30 JWA - activity updated through activity FIRA22 from case FIR03-00090.
|
Alarm Plan Check | | | 6/25/2003 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Paul Highley 6/25/2003.
|
Telephone call | | | 6/24/2003 | | |
|
|
|
Phone call into Paul Highley to inquire about the power requirements for the visual displays in the corridors.
|
Alarm Plan Check | | | 5/27/2003 | | FAIL |
|
|
|
Resubmittal required.
|
Application received | | | 5/19/2003 | | |
|
|
|
|