Permit Information
Permit NumberFIR03-00258
StatusFinaled
Name NORTHWEST SALES COMPANY
Site Address 7960 W NORTHVIEW ST
Project NamealmSt Marks Catholic Community
Customer Number 
ePlanReview 
Description
New fire alarm system in new structure, fully sprinklered.

1/28/2004 - Additional scope, three strobes were required per the PDS Fire Inspector.

There is no impact to the battery, voltage drop and speaker wattage calculations, existing batteries are acceptable.


12/11/2003 - Additional scope, the following is being installed in area A (see modified plans, items are clouded):
" one new duct detector for HVAC shutdown (RTU-7)
" three new strobes to cover new space
" three new in-duct detectors for fire/smoke damper control
" two new pull stations
" four relocated strobes
" two relocated pull stations

There is no impact to the battery, voltage drop and speaker wattage calculations, existing batteries are acceptable.

12/16/2003 - Received updated matrix to include the in-duct detector for HVAC shutdown. Revised matrix is in the packet.

The associated building permit (BLD 02-02454) is to construct a new 26,050 sq.ft. single story, sanctuary, restroom and entry vestibule. NOTE: This building is fully fire sprinklered for one-hour substitution. This permit includes if accepted alternate #2 to "Area A", demo entry, modify existing exterior wall and make a two-hour separation wall and connect "Area A & Area B" via an new entry lobby. All construction per the approved plans and attached comment list. Refer to BLD 02-02667 for remodel of Area "A". See BLD 02 -02236 for grading permit. MJP PC#652-02 CUP02-00038
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled7/26/20047/26/20047/26/2004PPASS
DetailsTroy Cobbley
Finaled by inspector at 7/26/2004 2:05:38 PM
INSP-Final Inspection7/26/20047/26/20047/26/2004PPASS
DetailsTroy Cobbley
Fire alarm finaled
Issue and Print Permit  2/10/2004 DONE
Alarm Plan Check  1/28/2004 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  1/28/2004 DONE
Inspection Record Card- Fire1/28/2004 1/28/2004 DONE
Permit Ready to Issue  1/28/2004 DONE
Telephone call  1/28/2004 DONE
Spoke with Rick and told him that permit is ready & fees//1/28/04 1:58pm BAM
INSP-Final Inspection1/21/20041/21/20041/21/2004APASS
DetailsTroy Cobbley
DOC - Permit Finaled1/21/20041/21/20041/21/2004APASS
DetailsTroy Cobbley
Finaled by inspector at 1/21/2004 11:21:58 AM
Miscellaneous action  1/21/2004 DONE
Received resubmittal. Acceptable to final the FA permit.
Miscellaneous action  1/20/2004 DONE
Received a fax from Jackie Phelps regarding Troy's correction notice. Agreement to have as-built plans resubmitted and available on site for final inspection. Fire inspection can not be finaled until as-built plans are resubmitted at the city.
Plan resubmittals received  1/20/2004 DONE
INSP-Alarm Testing1/15/20041/16/20041/16/2004PFAIL
DetailsTroy Cobbley
Demo old fire alarm system, 185cd a/v's in room A38 are oerspaced. They exceed 35' from the walls. Provide strobe coverage in A38 mezzanine. Provide strobe in corridor behind A37. Provide strobe in unmarked toilet north of A27. Provide strobe in toilet A28. Resubmit plans per review note #2. 1/16/2004 3:06:49 PM
INSP-Alarm Testing12/22/200312/23/200312/23/2003PPART
DetailsTroy Cobbley
A temporary occupancy was given with dave millers permission until the existing building is completed. Battery calcs, map, breaker locks and breaker box location. Existing building needs to be inspected 12/23/2003 1:23:42 PM
Issue and Print Permit  12/19/2003 DONE
Miscellaneous action  12/16/2003 DONE
Received revised matrix via fax from Rick Groom at Northwest Sales.
Alarm Plan Check  12/16/2003 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  12/16/2003 DONE
Inspection Record Card- Fire12/16/2003 12/16/2003 DONE
Permit Ready to Issue  12/16/2003  
Telephone call  12/16/2003 DONE
left mess that permit is ready
Plan resubmittals received  12/11/2003 DONE
Plan Modification
Telephone call  12/11/2003 DONE
Request for revised matrix to include the in-duct smoke detectors. Sent e-mail and left phone message.

Gave authorization to proceed with the plan modification changes.
FIR-Aging Inspection10/20/200310/20/200310/20/2003 NR
DetailsTroy Cobbley
work in progress 10/20/2003 3:27:34 PM
Alarm Plan Check  7/21/2003 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  7/21/2003 DONE
Override - Parcel Holds  7/21/2003  
Inspection Record Card- Fire7/21/2003 7/21/2003 DONE
Telephone call  7/21/2003 DONE
permit ready no fees due new building
Override - Parcel Holds  7/21/2003  
Issue and Print Permit  7/21/2003 DONE
Plan assigned to (SAM)5/23/2003 7/18/2003 DONE
7/18/2003 15:16:35 M_F - activity updated through activity FIRA22 from case FIR03-00258.
Alarm Plan Check  6/2/2003 FAIL
Resubmittal required. Faxed comments to Rick Groom 6/2/2003.
Application received  5/23/2003