FIR-Aging Inspection | 10/7/2005 | 10/7/2005 | 10/11/2005 | | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 10/11/2005 | 10/11/2005 | 10/11/2005 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled 11-26-03
|
FIR-Aging Inspection | 6/22/2005 | 6/22/2005 | 6/29/2005 | | PASS |
Troy Cobbley
|
|
|
|
INSP-Final Inspection | 11/21/2003 | 11/24/2003 | 11/24/2003 | A | PART |
Troy Cobbley
|
|
|
A temp occupancy was given until adequate batteries are provided for the Nac panel. All other life safety items are ok. Provide 14.4 AH batteries for the facp 11/24/2003 12:31:51 PM
|
INSP-Final Inspection | 11/20/2003 | 11/21/2003 | 11/21/2003 | P | CANC |
Troy Cobbley
|
|
|
This is Grants cell; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
|
Issue and Print Permit | | | 9/23/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 9/22/2003 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/22/2003 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/17/2003 | | DONE |
|
|
|
Resubmitual received: Fax from Protex that contains a letter from Silent Knight that states the pull station PS-DA can be used with a plastic cover to divert moisture. Temperature is not a factor.
|
Plan resubmittals received | | | 9/11/2003 | | DONE |
|
|
|
|
Issue permit | | | 9/4/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 9/3/2003 | | PASS |
|
|
|
Resubmittal required on item #14, UL listing on pull station for outside usage with cover, prior to a final on the fire alarm system. All other items are approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/3/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/3/2003 | | 9/3/2003 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/3/2003 | | DONE |
|
|
|
|
Application received | | | 9/3/2003 | | DONE |
|
|
|
|
Telephone call | | | 9/3/2003 | | DONE |
|
|
|
permit ready and fees due
|
Plan assigned to (SAM) | 5/28/2003 | | 9/3/2003 | | DONE |
|
|
|
9/3/2003 11:17:12 M_F - activity updated through activity FIRA22 from case FIR03-00279.
|
Plan resubmittals received | | | 8/14/2003 | | DONE |
|
|
|
|
Telephone call | | | 8/7/2003 | | |
|
|
|
Called Rob Ahten to notify him that the drawings that he submitted are not clouded as he stated. I requested that he re-submit with 2 complete sets as required. He stated he would.
|
Plan resubmittals received | | | 8/5/2003 | | |
|
|
|
|
Telephone call | | | 7/29/2003 | | |
|
|
|
Called to remind Rob that he was to stop by and "cloud" the changes on the Aspen Springs Apartment resubmittal (he agreed to do so 7/17/2003). Left a message.
|
Telephone call | | | 7/17/2003 | | |
|
|
|
Phoned Rob Ahten at Protex to request that he "cloud" his changes from the previous submittal per the FA permit Plan Review Requirements. He stated he would be down after lunch.
|
Miscellaneous action | | | 6/19/2003 | | DONE |
|
|
|
Request approved to begin installation without approved plans with Protex assuming full finacial responsibility for any potential changes necessary to comply with approved plans.
|
Plan resubmittals received | | | 6/18/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/29/2003 | | FAIL |
|
|
|
Resubmittal required.
|
Application received | | | 5/28/2003 | | |
|
|
|
|