Permit NumberFIR03-00292
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 3424 W HILL RD
Project NameSPR ASHLEY MANOR
Customer Number 
ePlanReview 
Description
Ashley Manor Care/Assisted living facility * To install a (modified) NFPA 13D fire sprinkler system in a new 3,956-ft/2 single story, 10 bedroom, assisted living facility. This building is required to be fire sprinklered per IBC and IFC Sections 903.2.9 with a NFPA 13D system, modified by the State of Idaho-Facility Standards. No commercial style kitchen equipment installed within this building without the installation of a commercial Type I hood and applying for additional permits. The fire sprinkler flow alarm shall be interconnected to the required residence smoke detection system. All fire sprinkler work and related, which includes dual service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD03-00279. This facility cannot exceed 16 patients or the maximum allowed and licensed by the State of Idaho, which ever is the lesser.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/23/20039/23/20039/23/2003APASS
DetailsRick Jackson
DOC - Permit Finaled9/23/20039/23/20039/23/2003APASS
DetailsRick Jackson
Finaled by inspector at 9/23/2003 10:44:32 AM
INSP-Sprinkler Rough-in/Hydro9/17/20039/18/20039/18/2003AFAIL
DetailsTroy Cobbley
need to test the alarm portion of the sprinkler system 9/18/2003 10:50:05 AM
INSP-Final Inspection9/10/20039/11/20039/11/2003ACANC
DetailsRick Jackson
please do not not arrive untill after 11:00AM. Thanks Trent; Phone #: ###-#### Internet Inspection Request from: Trent Bice inspection not needed at this time as alarms aren't ready 9/11/2003 11:50:33 AM
Telephone call  8/18/2003 DONE
Don Weland-Designer called and indicated Troy Cobbley requested asbuilts for building changes. Changes are bedroom closets modified to bathrooms. I requested 2 plans for records (City and ISRB) and inspector could probably field verify without a revised site plan.
INSP-Sprinkler Rough-in/Hydro7/21/20037/21/20037/21/2003PPASS
DetailsTroy Cobbley
rough-in ok. Tenting is ok. Piping is ok to cover. Provide updated asbuilts to city 7/21/2003 4:11:35 PM
Issue permit  6/26/2003 DONE
Plan assigned to (Bill)6/2/2003 6/24/2003 DONE
6/24/2003 10:15:04 JWA - activity updated through activity FIRA22 from case FIR03-00292.
Sprinkler Plan Check6/20/2003 6/24/2003 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  6/24/2003 DONE
DetailsBill Alexander
Telephone call  6/24/2003 DONE
LEFT MESS THAT PERMIT IS READY
Inspection Record Card- Fire6/24/2003 6/24/2003 DONE
Plan resubmittals received  6/20/2003 DONE
Telephone call  6/5/2003 DONE
pick up failed plans
Sprinkler Plan Check6/2/2003 6/4/2003 FAIL
DetailsBill Alexander
Plans lack water meter information on plans and loss in the hydraulic calculations. Verify size of main provided to the meter.
Telephone call  6/4/2003 DONE
DetailsBill Alexander
2:30pm - Called Don Weland (designer) and asked about the underground. Whether it is a singler servise line and if so, why they are not doing it. If not, then where is the meter and related issues in regard to it, plans, calcs., etc.
Application received  6/2/2003