INSP-Final Inspection | 6/26/2003 | 6/27/2003 | 6/27/2003 | A | PASS |
Troy Cobbley
|
|
|
al; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
DOC - Permit Finaled | 6/27/2003 | 6/27/2003 | 6/27/2003 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 6/27/2003 11:05:27 AM
|
INSP-Final Inspection | 6/25/2003 | 6/26/2003 | 6/26/2003 | A | FAIL |
Troy Cobbley
|
|
|
remove the alarm verification from the manual pull station, test the east PIV, rewire the hose valve tampers, verify current draw, test smoke detectors, provide breaker location at the facp panel, test phone lines. There are two accounts for this system at the monitoring station since there are two addresses. Retest all devices unless Alarmco can provide test results for devices tested under the other account. 6/26/2003 2:54:49 PM
|
Plan assigned to (SAM) | 6/3/2003 | | 6/9/2003 | | DONE |
|
|
|
6/9/2003 12:28:33 M_F - activity updated through activity FIRA22 from case FIR03-00294.
|
Alarm Plan Check | | | 6/9/2003 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/9/2003 | | DONE |
|
|
|
|
Issue and Print Permit | | | 6/9/2003 | | DONE |
|
|
|
|
Telephone call | | | 6/9/2003 | | DONE |
|
|
|
permit ready and fees due
|
Application received | | | 6/3/2003 | | |
|
|
|
|