Information based on query as of Sunday, August 18, 2024.
Permit Information
Permit NumberFIR03-00294
StatusFinaled
Name ALARMCO
Site Address 11697 W PRESIDENT DR
Project Namealm - Closet & Storage Concept
Customer Number 
ePlanReview 
Description
The horn/strobe, smoke, pull station and remote annunciator are being added to an existing fire alarm system. The building is fully sprinklered.

The associated building permit (BLD 03-00812) is to remodel a 4,500 sq.ft. portion of an existing building to be used for office and woodworking tenant per approved plans on file. Work to include demolition of an existing wall, construction of approximately 38 lf of partition this will create woodworking area and office areas. Note: This building was constructed in Ada County in 1997 and annexed into Boise City on 12/30/99. It is being analysised for nonseparated uses per IBC Section 302.3.2. This building is fully fire sprinklered any alterations or modifications to the sprinkler system shall be per NFPA #13 as regulated by the fire department. (pc#204-03) rmh
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/26/20036/27/20036/27/2003APASS
DetailsTroy Cobbley
al; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
DOC - Permit Finaled6/27/20036/27/20036/27/2003APASS
DetailsTroy Cobbley
Finaled by inspector at 6/27/2003 11:05:27 AM
INSP-Final Inspection6/25/20036/26/20036/26/2003AFAIL
DetailsTroy Cobbley
remove the alarm verification from the manual pull station, test the east PIV, rewire the hose valve tampers, verify current draw, test smoke detectors, provide breaker location at the facp panel, test phone lines. There are two accounts for this system at the monitoring station since there are two addresses. Retest all devices unless Alarmco can provide test results for devices tested under the other account. 6/26/2003 2:54:49 PM
Plan assigned to (SAM)6/3/2003 6/9/2003 DONE
6/9/2003 12:28:33 M_F - activity updated through activity FIRA22 from case FIR03-00294.
Alarm Plan Check  6/9/2003 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  6/9/2003 DONE
Issue and Print Permit  6/9/2003 DONE
Telephone call  6/9/2003 DONE
permit ready and fees due
Application received  6/3/2003