Permit Information
Permit NumberFIR03-00297
StatusExpired
Name KISSLER LAURENCE H & FRANCES C
Site Address 1125 W AMITY RD
Project Namealm - Norco
Customer Number 
ePlanReview 
Description
Existing fire alarm system to be replaced due to addition of an Ansul Autopulse, 442R releasing control unit and an upgraded portion of the sprinkler system to preaction for the existing computer room. The existing FACP will be replaced to accommodate the releasing capability of a double/interlocked preaction valve.
7/22/2003 - The agent releasing panel has been changed to an Inergen.

The associated sprinkler permit is FIR03-00008. To tap into an existing wet pipe system main on the first floor riser supply, pipe 1½" main to the second floor and install a double interlock system riser and related piping (less the electrical detection operation devices and panel). Also reroute existing (wet) line coverage piping around the computer room. All work related and addressed in this permit shall comply with NFPA 13-1999, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of meeting minimum code. This permit is not attached to any building permit

There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Expired6/11/20106/11/20106/11/2010PPASS
DetailsForrest France
Ref IFC 2006 sec. 105.3.1
FIR-Aging Inspection6/11/20106/11/20106/11/2010 DONE
DetailsForrest France
INSP-Final Inspection11/12/200311/12/200311/12/2003PFAIL
DetailsRick Jackson
tamper on main wet system isn't supervised with supervisory signal as it is a "plug" type tamper; need updated map at annunciator 11/12/2003 12:07:19 PM
INSP-Sprinkler Rough-in/Hydro10/31/200310/31/200310/31/2003PPART
DetailsRick Jackson
john; Phone #: ###-#### Internet Inspection Request from: Darla Downs hydro static pressure test okay 10/31/2003 12:07:51 PM
INSP-Sprinkler Rough-in/Hydro10/27/200310/27/200310/27/2003PCANC
DetailsRick Jackson
John; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes wrong permit called in for fire sprinkler system see FIR03-00008 for sprinklers 10/27/2003 2:04:00 PM
Issue and Print Permit  7/29/2003 DONE
Plan assigned to (SAM)6/4/2003 7/22/2003 DONE
7/22/2003 10:21:50 M_F - activity updated through activity FIRA22 from case FIR03-00297.
Alarm Plan Check  7/22/2003 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  7/22/2003 DONE
Inspection Record Card- Fire7/22/2003 7/22/2003 DONE
Telephone call  7/22/2003 DONE
left mess that permit is ready
Plan resubmittals received  7/17/2003  
Alarm Plan Check  6/12/2003 FAIL
Resubmittal is required. Fax comments to Steve Larsen 6/12/2003.
Telephone call  6/9/2003  
Need BLDG permit #. Sprinkler drawings were included in the package. Left message for Steve Larsen regarding the above items.
Telephone call  6/9/2003  
Steve Larsen returned my call. There is no building permit associated with this FA permit. There is a sprinkler permit (FIR03-00008) that was issued for the pre-action system.
Application received  6/4/2003