INSP-Final Inspection | 7/1/2003 | 7/1/2003 | 7/1/2003 | A | PASS |
Troy Cobbley
|
|
|
|
DOC - Permit Finaled | 7/1/2003 | 7/1/2003 | 7/1/2003 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 7/1/2003 10:34:55 AM
|
INSP-Final Inspection | 6/27/2003 | 6/27/2003 | 6/27/2003 | P | FAIL |
Troy Cobbley
|
|
|
provide updated map at the facp and nfpa 72 forms 6/27/2003 11:31:02 AM
|
Inspection Record Card- Fire | 6/23/2003 | | 6/23/2003 | | DONE |
|
|
|
|
Issue permit | | | 6/23/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 6/20/2003 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/20/2003 | | DONE |
|
|
|
|
Telephone call | | | 6/20/2003 | | DONE |
|
|
|
called left message with john vastton permit ready & fee given for wes smith///DLD
|
Plan resubmittals received | | | 6/16/2003 | | DONE |
|
|
|
|
Telephone call | | | 6/12/2003 | | |
|
|
|
Spoke with Jon Van Stone (designer), smoke detectors for the Hepa filters are wired to shutdown the associated Hepa only. In case of any smoke detector alarm in the return, the "system" must be shutdown, therefore all 10 Hepas must shutdown. BOM does not match items and they will require an access panel in teh duct upstream of the in-duct detector.
|
Alarm Plan Check | | | 6/12/2003 | | FAIL |
|
|
|
Resubmittal required. Comments faxed to Wes Smith 6/12/03.
|
Plan assigned to (SAM) | 6/10/2003 | | 6/11/2003 | | DONE |
|
|
|
6/11/2003 13:34:32 JWA - activity updated through activity FIRA22 from case FIR03-00226.
|
Application received | | | 6/10/2003 | | |
|
|
|
|