INSP-Final Inspection | 11/21/2003 | 11/21/2003 | 11/21/2003 | A | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 11/21/2003 | 11/21/2003 | 11/21/2003 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 11/21/2003 10:01:24 AM
|
Inspection Record Card- Fire | 10/1/2003 | | 10/1/2003 | | DONE |
|
|
|
|
Telephone call | | | 10/1/2003 | | DONE |
|
|
|
called jim permit ready & fee's given///dld
|
Issue and Print Permit | | | 10/1/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 10/1/2003 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/1/2003 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/23/2003 | | DONE |
|
|
|
|
Telephone call | | | 8/20/2003 | | |
|
|
|
Dennis Schrecongost and I discussed the existing duct smoke detectors. The mechanical drawings are deleting them. I explained to him that he should resubmit under the same permit number (electrical and the FA plans) as a plan modification to show the changes.
|
INSP-Final Inspection | 8/18/2003 | 8/19/2003 | 8/19/2003 | A | CANC |
Rick Jackson
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie wrong permit number used 8/19/2003 9:40:59 AM
|
Alarm Plan Check | | | 7/3/2003 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/3/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/3/2003 | | 7/3/2003 | | DONE |
|
|
|
|
Telephone call | | | 7/3/2003 | | DONE |
|
|
|
permit ready
|
Issue permit | | | 7/3/2003 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 6/11/2003 | | 7/2/2003 | | DONE |
|
|
|
7/2/2003 16:40:15 JWA - activity updated through activity FIRA22 from case FIR03-00220.
|
Telephone call | | | 7/2/2003 | | |
|
|
|
Called Jim Shilton (Honeywell) to request a copy of the cut sheets and equipment information. He said he would drop it by tomorrow or Monday the 7th.
|
Telephone call | | | 6/25/2003 | | |
|
|
|
Called Dennis to let him know that the intent of the code is for the visual to be seen from the end of the corridor. (CA states 130 feet) Dennis claims that this would be a hardship as the rest of the hospital is based on the use of system smoke detectors and the LEDs for the remote indication. I asked that he place his request in writing via e-mail and we would review it again.
|
Plan resubmittals received | | | 6/25/2003 | | DONE |
|
|
|
|
Telephone call | | | 6/24/2003 | | |
|
|
|
Dennis called to inquire about the exception (FIR01-00435) for the use of LEDs in lieu of the visuals located in the corridors that actuate from the "single station" smoke detector in the patients rooms. I told him that I would discuss it with Sam.
|
Alarm Plan Check | | | 6/18/2003 | | FAIL |
|
|
|
Resubmittal Required. Faxed comments 6/18 to Jim Shelton.
|
Application received | | | 6/11/2003 | | |
|
|
|
|
Inspection Record Card- Fire | 10/1/2003 | | | | |
|
|
|
|