Case Summary | | | 7/21/2004 | | DONE |
|
|
|
|
INSP-Final Inspection | 6/9/2004 | 6/14/2004 | 6/14/2004 | A | PASS |
Rick Jackson
|
|
|
clifford; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
DOC - Permit Finaled | 6/14/2004 | 6/14/2004 | 6/14/2004 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 6/14/2004 10:15:04 AM
|
INSP-Final Inspection | 5/25/2004 | 5/28/2004 | 5/28/2004 | A | FAIL |
Rick Jackson
|
|
|
CLIFFORD; Phone #: ###-#### Internet Inspection Request from: Annette Moore On fire alarm NAC panel #1 circuits 1-2 develpoe a trouble condition that won't clear without powering down panel 5/28/2004 9:54:15 AM
|
INSP-Final Inspection | 5/18/2004 | 5/24/2004 | 5/24/2004 | A | FAIL |
Rick Jackson
|
|
|
Clifford; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Trouble on NAC-1 circuit - 2; descriptor for NAC/EVAC trouble modules; water flow restores alarm when flow stops 5/24/2004 10:32:22 AM
|
Issue permit | | | 4/13/2004 | | DONE |
|
|
|
|
Alarm Plan Check | 3/12/2004 | | 3/31/2004 | | PASS |
Troy Cobbley
|
|
|
Plan modifications approved
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/31/2004 | | DONE |
Troy Cobbley
|
|
|
|
Permit Ready to Issue | | | 3/31/2004 | | |
|
|
|
|
Telephone call | | | 3/31/2004 | | DONE |
|
|
|
left mess for ken webster that permit is ready
|
Inspection Record Card- Fire | 3/31/2004 | | 3/31/2004 | | DONE |
|
|
|
|
INSP-Conference | 3/22/2004 | 3/22/2004 | 3/22/2004 | A | DONE |
Troy Cobbley
|
|
|
I called to speak to Cliff but was only able to leave a message. I need description on what the scope of work is since this project was just issued.
|
Plan resubmittals received | | | 3/12/2004 | | DONE |
|
|
|
|
INSP-Final Inspection | 2/24/2004 | 3/1/2004 | 3/1/2004 | A | FAIL |
Rick Jackson
|
|
|
cliff-- ###-#### need resubmittals as there are two SNAC panels instead of one - 4 NAC are one SNAC and NAC 7-8 are on the other; batteries on SNAC aren't supervised; speakers are T-tapped; need maps; spot checked several smokes but need to test for alarm; need to check FACP for troubles; strobe to be 95 cd instead of 75 in SW gallery (see plans); need to test smokes for alarms and tampers plus manaul pulls and duct detectors; detectors 52 -and 53 are actually 72 and 74 - update maps/plans(didn't show up on address list either 3/1/2004 6:09:07 PM
|
INSP-Final Inspection | 2/23/2004 | 2/24/2004 | 2/24/2004 | A | NR |
Rick Jackson
|
|
|
CLIFF; Phone #: ###-#### Internet Inspection Request from: Darla Downs rescheduled for 34/1/04 2/24/2004 8:41:10 AM
|
Issue and Print Permit | | | 2/10/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/10/2004 | | 2/10/2004 | | DONE |
|
|
|
|
Alarm Plan Check | 2/9/2004 | | 2/9/2004 | | PASS |
|
|
|
Plan modifications approved with comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/9/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/9/2004 | | |
|
|
|
|
Telephone call | | | 2/9/2004 | | DONE |
|
|
|
spoke with Ken -- permit is ready.
|
Plan resubmittals received | | | 1/27/2004 | | DONE |
|
|
|
|
INSP-Final Inspection | 8/5/2003 | 8/6/2003 | 8/6/2003 | A | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 8/5/2003 at 9:53:09 AM. Contact: ###-####. this permit was called in by mistake by another contractor 8/6/2003 9:52:32 AM
|
INSP-Final Inspection | 8/6/2003 | 8/6/2003 | 8/6/2003 | P | CANC |
Rick Jackson
|
|
|
wrong permit added by inspector 409 8/6/2003 11:06:51 AM
|
Issue and Print Permit | | | 7/11/2003 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 6/13/2003 | | 7/1/2003 | | DONE |
|
|
|
7/1/2003 11:33:37 M_F - activity updated through activity FIRA22 from case FIR03-00315.
|
Alarm Plan Check | | | 7/1/2003 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/1/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/1/2003 | | 7/1/2003 | | DONE |
|
|
|
|
Telephone call | | | 7/1/2003 | | DONE |
|
|
|
permit ready
|
Plan resubmittals received | | | 6/27/2003 | | DONE |
|
|
|
|
Telephone call | | | 6/23/2003 | | |
|
|
|
Called to inquire about existing drawings. Ken Webster stated there weren't any to give for interim detector spacing, that basically we would not have any less coverage than we have now. He stated that Dave Miller agreed to a 36 month overhaul, he will get the letter and fax it to me.
|
Alarm Plan Check | | | 6/23/2003 | | FAIL |
|
|
|
Resubmittal required. Comments faxed to Kevin Webster 6/24/2003.
|
Application received | | | 6/13/2003 | | |
|
|
|
|