Permit Information
Permit NumberFIR03-00340
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 405 S 8TH ST (SUITE 121)
Project NameSPR FUNNY BONE
Customer Number 
ePlanReview 
Description
(FUNNY BONE - SUITE 121) To relocate and add fire sprinklers in the expansion of an existing tenant space, of which will be converted to an A-2 Occupancy nightclub. The total size of the expanded tenant space will be: 3,676-ft/2 with an occupant load of 280. Fire sprinkler work is related to include interior nonbearing walls, a new entry at the alley, new stairways, new skylights per drawing and plan review conditions on file. The fire sprinklers are used to substitute for 1-hr fire-resistance rated construction. The location of fire sprinkler heads shall comply with NFPA 13-1999 as regulated by the Fire Department. All fire sprinklers and related appurtenance within this permit work scope shall meet current NFPA 13-1999 standards, comply with the IFC-2000 and attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, in order to provide witness verification of compliance in meeting minimum code standards. This permit is attached to building permit: BLD03-01172.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/1/20037/2/20037/2/2003APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 7/1/2003 at 1:52:47 PM. Contact: ###-####. Bill Alexander approved the sidewall heads in the lobby to remain 7/2/2003 10:18:21 AM
DOC - Permit Finaled7/2/20037/2/20037/2/2003PPASS
DetailsRick Jackson
Finaled by inspector at 7/2/2003 1:44:16 PM
Sprinkler Plan Check7/1/2003 7/1/2003 PASS
PLANS/APPL TAKEN TO FRONT DESK  7/1/2003 DONE
Issue permit  7/1/2003 DONE
Inspection Record Card- Fire6/30/2003 6/30/2003 DONE
Telephone call  6/30/2003 DONE
permit ready
Plan assigned to (Bill)6/26/2003 6/27/2003 DONE
DetailsBill Alexander
6/27/2003 14:49:56 JWA - activity updated through activity FIRA22 from case FIR03-00340.
Sprinkler Plan Check6/26/2003 6/27/2003 PART
DetailsBill Alexander
It has been distributed throughout all fire sprinkler contractors, who have been permitting work in the City of Boise, that all plan "Sprinkler Legend's" must include the "Sprinkler Identification Number" (SIN) for all sprinkler heads installing. Please make a note of this for future reference. Sprinkler Legend must include the number of relocated and/or modified existing sprinklers also. (IFC 105.4.1, 105.4.2)

The "Front End" 2" piping from the basement appears to be overloaded for the pipe schedule design. This area is not approved and will require resubmittal/approval. (NFPA 13:8-5.2, 8-5.2.2)

Clarify the cavity above the "Box Office" on the west side of the obstructing duct. (The duct location is not clear in this area and this AHJ cannot verify "cavity" protection?) (IFC 105.4.1, 105.4.2)

Verify the cooler in this same area with its minimum operating temperature. Standard sprinklers shall not be allowed in coolers that operate below 40ºF. (NFPA 13:4-6.1.3.2)

Provide a detail/s on what any NEW hangers installing will be. (NFPA 13:8-1.1(22)

Provide the construction type of this structure, (reference NFPA 13:1-4.6, A-1.4.6).
PLANS/APPL TAKEN TO FRONT DESK  6/27/2003 DONE
DetailsBill Alexander
Application received  6/26/2003