INSP-Final Inspection | 7/1/2003 | 7/2/2003 | 7/2/2003 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 7/1/2003 at 1:52:47 PM. Contact: ###-####. Bill Alexander approved the sidewall heads in the lobby to remain 7/2/2003 10:18:21 AM
|
DOC - Permit Finaled | 7/2/2003 | 7/2/2003 | 7/2/2003 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 7/2/2003 1:44:16 PM
|
Sprinkler Plan Check | 7/1/2003 | | 7/1/2003 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/1/2003 | | DONE |
|
|
|
|
Issue permit | | | 7/1/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/30/2003 | | 6/30/2003 | | DONE |
|
|
|
|
Telephone call | | | 6/30/2003 | | DONE |
|
|
|
permit ready
|
Plan assigned to (Bill) | 6/26/2003 | | 6/27/2003 | | DONE |
Bill Alexander
|
|
|
6/27/2003 14:49:56 JWA - activity updated through activity FIRA22 from case FIR03-00340.
|
Sprinkler Plan Check | 6/26/2003 | | 6/27/2003 | | PART |
Bill Alexander
|
|
|
It has been distributed throughout all fire sprinkler contractors, who have been permitting work in the City of Boise, that all plan "Sprinkler Legend's" must include the "Sprinkler Identification Number" (SIN) for all sprinkler heads installing. Please make a note of this for future reference. Sprinkler Legend must include the number of relocated and/or modified existing sprinklers also. (IFC 105.4.1, 105.4.2)
The "Front End" 2" piping from the basement appears to be overloaded for the pipe schedule design. This area is not approved and will require resubmittal/approval. (NFPA 13:8-5.2, 8-5.2.2)
Clarify the cavity above the "Box Office" on the west side of the obstructing duct. (The duct location is not clear in this area and this AHJ cannot verify "cavity" protection?) (IFC 105.4.1, 105.4.2)
Verify the cooler in this same area with its minimum operating temperature. Standard sprinklers shall not be allowed in coolers that operate below 40ºF. (NFPA 13:4-6.1.3.2)
Provide a detail/s on what any NEW hangers installing will be. (NFPA 13:8-1.1(22)
Provide the construction type of this structure, (reference NFPA 13:1-4.6, A-1.4.6).
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/27/2003 | | DONE |
Bill Alexander
|
|
|
|
Application received | | | 6/26/2003 | | |
|
|
|
|