INSP-Final Inspection | 8/5/2004 | 8/6/2004 | 8/6/2004 | A | PASS |
Rick Jackson
|
|
|
Terry - 8:15 am; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley All items corrected - final okay 8/6/2004 2:14:26 PM
|
DOC - Permit Finaled | 8/6/2004 | 8/6/2004 | 8/6/2004 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 8/6/2004 2:14:53 PM
|
INSP-Final Inspection | 8/3/2004 | 8/4/2004 | 8/3/2004 | P | CANC |
Rick Jackson
|
|
|
contact: Terry, Idaho State Fire Marshall will be out at 2:30; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|
INSP-Final Inspection | 7/30/2004 | 8/2/2004 | 8/2/2004 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 7/30/2004 at 7:46:45 AM. Contact: ###-####. Need updated to reflect the correct location of M1-013 8/2/2004 10:44:42 AM
|
INSP-Final Inspection | 8/2/2004 | 8/2/2004 | 8/2/2004 | A | FAIL |
Rick Jackson
|
|
|
Pump pressure not reaching set pressure as reflected at the controlloer (130 psi) 8/2/2004 11:03:55 AM
|
INSP-Final Inspection | 7/28/2004 | 7/28/2004 | 7/28/2004 | P | FAIL |
Rick Jackson
|
|
|
Inspection was stopped as the alarms/flows/tampers weren't thoroughly pre-tested (low air didn't function/OS & Y tampers required adjustments; pump controller not reporting power loss as it was wired backwards) 7/28/2004 4:03:17 PM
|
INSP-Sprinkler Rough-in | 6/29/2004 | 6/30/2004 | 6/30/2004 | A | PART |
Rick Jackson
|
|
|
Contact: Terry -- Fire Pump Inspection, State Fire Marshal will be out at 8:30 with the pump man; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley The test consisted of the 100 and 150 percent flow only; flow tested okay; with Scott Buck of State Fire Marshall office 6/30/2004 10:24:45 AM
|
INSP-Sprinkler Rough-in/Hydro | 6/18/2004 | 6/23/2004 | 6/22/2004 | A | CANC |
Rick Jackson
|
|
|
Contact: Terry -- This is scheduled with the ISFM and pump guy for 10 am.; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|
INSP-Sprinkler Rough-in/Hydro | 6/8/2004 | 6/10/2004 | 6/10/2004 | P | FAIL |
Rick Jackson
|
|
|
Contact: Terry; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley All items have been corrected from previous inspection except onehead obstrcuted in parking outside the elevator lobby; need spare heads and test all sprinkler flows, tampers and trip test the dry system and witness pump test 6/10/2004 3:35:03 PM
|
INSP-Sprinkler Rough-in/Hydro | 4/14/2004 | 4/15/2004 | 4/15/2004 | A | PART |
Rick Jackson
|
|
|
Contact - Terry -- Hyrdo on Dry System ; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley hydro test for dry systems and dry standpipe okay; need through-bolts on EQ in cinder block; heads obstructed by conduit, etc; air compressor has on/off switch; pressure sensing lines shall be copper/brass - see NFPA 20 and plans; need flow switch on supervised main (from BFP to pump) 4/15/2004 11:32:23 AM
|
Issue and Print Permit | | | 4/7/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/24/2004 | | 3/26/2004 | | PASS |
Bill Alexander
|
|
|
Installation major changes.
|
Plan assigned to (Bill) | 3/25/2004 | | 3/26/2004 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/26/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/26/2004 | | 3/26/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/26/2004 | | DONE |
|
|
|
|
Telephone call | | | 3/26/2004 | | DONE |
|
|
|
permit ready and fee due
|
INSP-Sprinkler Rough-in/Hydro | 3/22/2004 | 3/24/2004 | 3/24/2004 | P | PART |
Rick Jackson
|
|
|
terry neilson; Phone #: ###-#### Internet Inspection Request from: Barbara Moore UG hydro okay 3/24/2004 3:27:54 PM
|
Plan resubmittals received | | | 3/24/2004 | | |
|
|
|
|
INSP-Supply line flush | 3/22/2004 | 3/23/2004 | 3/23/2004 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 3/22/2004 at 11:23:12 AM. Contact: ###-####. Flush only okay; still needs hydro; Terry said resubmittals are forthcoming due to changes in pump room layout 3/23/2004 4:29:51 PM
|
FIR-Aging Inspection | 11/18/2003 | 11/18/2003 | 11/18/2003 | | PASS |
Rick Jackson
|
|
|
still in progress 11/18/2003 9:31:16 AM
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/19/2003 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 8/19/2003 | | 8/19/2003 | | DONE |
|
|
|
|
Telephone call | | | 8/19/2003 | | DONE |
|
|
|
permit ready and fees due
|
Issue and Print Permit | | | 8/19/2003 | | DONE |
|
|
|
|
Plan resubmittals received | | | 8/18/2003 | | |
|
|
|
|
Sprinkler Plan Check | 8/18/2003 | | 8/18/2003 | | PASS |
Bill Alexander
|
|
|
Pump data submittals.
|
Inspection Record Card- Fire | 8/15/2003 | | 8/15/2003 | | DONE |
|
|
|
|
Telephone call | | | 8/15/2003 | | DONE |
|
|
|
left mess that permit is ready
|
Issue permit | | | 8/15/2003 | | DONE |
|
|
|
|
Sprinkler Plan Check | 8/8/2003 | | 8/14/2003 | | PART |
Bill Alexander
|
|
|
Lack items #10 and #31 (review).
|
Plan assigned to (Bill) | 8/8/2003 | | 8/14/2003 | | DONE |
Bill Alexander
|
|
|
8/14/2003 10:36:03 JWA - activity updated through activity FIRA22 from case FIR03-00343.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/14/2003 | | DONE |
Bill Alexander
|
|
|
|
Plan resubmittals received | | | 8/8/2003 | | |
|
|
|
|
Plan assigned to (Bill) | 7/24/2003 | | 8/5/2003 | | DONE |
Bill Alexander
|
|
|
8/5/2003 07:51:11 JWA - activity updated through activity FIRA22 from case FIR03-00343.
|
Plan assigned to (Bill) | 6/30/2003 | | 8/5/2003 | | DONE |
Bill Alexander
|
|
|
8/5/2003 07:51:11 JWA - activity updated through activity FIRA22 from case FIR03-00343.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/5/2003 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 8/5/2003 | | |
|
|
|
|
Inspection Record Card- Fire | 8/5/2003 | | 8/5/2003 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/5/2003 | | DONE |
|
|
|
resubmital required/ temp start
|
Sprinkler Plan Check | 7/24/2003 | | 8/4/2003 | | PART |
Bill Alexander
|
|
|
Many items not addressed or addressed incorrectly. Resubmittal required prior to accepting plans that can be approved. Work may proceed at the contractor own risk.
|
Plan resubmittals received | | | 7/24/2003 | | |
Bill Alexander
|
|
|
|
Telephone call | | | 7/9/2003 | | DONE |
|
|
|
Called John Graves - ###-#### (designer), asked for him to come down and we will go over the drawings/review to clarify problems and requirements. He indicated he will come visit about 2:20pm.
|
Sprinkler Plan Check | 6/30/2003 | | 7/8/2003 | | FAIL |
Bill Alexander
|
|
|
See review notes FIR03-00343F attached.
|
Application received | | | 6/30/2003 | | |
|
|
|
|