Permit Information
Permit NumberFIR03-00343
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 322 E FRONT ST
Project NameSPR ID WATER CENTER-GARAGE
Customer Number 
ePlanReview 
Description
IDAHO WATER CENTER BASEMENT (GARAGE) PA1 * To install fire sprinkler protection (including standpipes) in the East 50,500 square foot portion of the underground basement garage, which is open and shared access with the West portion of the underground basement garage, which is addressed as Phase One which consisted of 77,000 square foot portion (FIR03-00067). The break line between phases is column 13.5. This facility is constructed of reinforced concrete with grade level concrete structural support deck for future multi-story office, retail and residential buildings. This garage is fully fire sprinkled. All fire sprinkler system work shall be in accordance to NFPA 13-1999, complying with the IFC-2000 and attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to Building Permit: BLD02-00199.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/5/20048/6/20048/6/2004APASS
DetailsRick Jackson
Terry - 8:15 am; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley All items corrected - final okay 8/6/2004 2:14:26 PM
DOC - Permit Finaled8/6/20048/6/20048/6/2004PPASS
DetailsRick Jackson
Finaled by inspector at 8/6/2004 2:14:53 PM
INSP-Final Inspection8/3/20048/4/20048/3/2004PCANC
DetailsRick Jackson
contact: Terry, Idaho State Fire Marshall will be out at 2:30; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
INSP-Final Inspection7/30/20048/2/20048/2/2004AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 7/30/2004 at 7:46:45 AM. Contact: ###-####. Need updated to reflect the correct location of M1-013 8/2/2004 10:44:42 AM
INSP-Final Inspection8/2/20048/2/20048/2/2004AFAIL
DetailsRick Jackson
Pump pressure not reaching set pressure as reflected at the controlloer (130 psi) 8/2/2004 11:03:55 AM
INSP-Final Inspection7/28/20047/28/20047/28/2004PFAIL
DetailsRick Jackson
Inspection was stopped as the alarms/flows/tampers weren't thoroughly pre-tested (low air didn't function/OS & Y tampers required adjustments; pump controller not reporting power loss as it was wired backwards) 7/28/2004 4:03:17 PM
INSP-Sprinkler Rough-in6/29/20046/30/20046/30/2004APART
DetailsRick Jackson
Contact: Terry -- Fire Pump Inspection, State Fire Marshal will be out at 8:30 with the pump man; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley The test consisted of the 100 and 150 percent flow only; flow tested okay; with Scott Buck of State Fire Marshall office 6/30/2004 10:24:45 AM
INSP-Sprinkler Rough-in/Hydro6/18/20046/23/20046/22/2004ACANC
DetailsRick Jackson
Contact: Terry -- This is scheduled with the ISFM and pump guy for 10 am.; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
INSP-Sprinkler Rough-in/Hydro6/8/20046/10/20046/10/2004PFAIL
DetailsRick Jackson
Contact: Terry; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley All items have been corrected from previous inspection except onehead obstrcuted in parking outside the elevator lobby; need spare heads and test all sprinkler flows, tampers and trip test the dry system and witness pump test 6/10/2004 3:35:03 PM
INSP-Sprinkler Rough-in/Hydro4/14/20044/15/20044/15/2004APART
DetailsRick Jackson
Contact - Terry -- Hyrdo on Dry System ; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley hydro test for dry systems and dry standpipe okay; need through-bolts on EQ in cinder block; heads obstructed by conduit, etc; air compressor has on/off switch; pressure sensing lines shall be copper/brass - see NFPA 20 and plans; need flow switch on supervised main (from BFP to pump) 4/15/2004 11:32:23 AM
Issue and Print Permit  4/7/2004 DONE
Sprinkler Plan Check3/24/2004 3/26/2004 PASS
DetailsBill Alexander
Installation major changes.
Plan assigned to (Bill)3/25/2004 3/26/2004 DONE
PLANS/APPL TAKEN TO FRONT DESK  3/26/2004 DONE
Inspection Record Card- Fire3/26/2004 3/26/2004 DONE
Permit Ready to Issue  3/26/2004 DONE
Telephone call  3/26/2004 DONE
permit ready and fee due
INSP-Sprinkler Rough-in/Hydro3/22/20043/24/20043/24/2004PPART
DetailsRick Jackson
terry neilson; Phone #: ###-#### Internet Inspection Request from: Barbara Moore UG hydro okay 3/24/2004 3:27:54 PM
Plan resubmittals received  3/24/2004  
INSP-Supply line flush3/22/20043/23/20043/23/2004PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 3/22/2004 at 11:23:12 AM. Contact: ###-####. Flush only okay; still needs hydro; Terry said resubmittals are forthcoming due to changes in pump room layout 3/23/2004 4:29:51 PM
FIR-Aging Inspection11/18/200311/18/200311/18/2003 PASS
DetailsRick Jackson
still in progress 11/18/2003 9:31:16 AM
PLANS/APPL TAKEN TO FRONT DESK  8/19/2003 DONE
DetailsBill Alexander
Inspection Record Card- Fire8/19/2003 8/19/2003 DONE
Telephone call  8/19/2003 DONE
permit ready and fees due
Issue and Print Permit  8/19/2003 DONE
Plan resubmittals received  8/18/2003  
Sprinkler Plan Check8/18/2003 8/18/2003 PASS
DetailsBill Alexander
Pump data submittals.
Inspection Record Card- Fire8/15/2003 8/15/2003 DONE
Telephone call  8/15/2003 DONE
left mess that permit is ready
Issue permit  8/15/2003 DONE
Sprinkler Plan Check8/8/2003 8/14/2003 PART
DetailsBill Alexander
Lack items #10 and #31 (review).
Plan assigned to (Bill)8/8/2003 8/14/2003 DONE
DetailsBill Alexander
8/14/2003 10:36:03 JWA - activity updated through activity FIRA22 from case FIR03-00343.
PLANS/APPL TAKEN TO FRONT DESK  8/14/2003 DONE
DetailsBill Alexander
Plan resubmittals received  8/8/2003  
Plan assigned to (Bill)7/24/2003 8/5/2003 DONE
DetailsBill Alexander
8/5/2003 07:51:11 JWA - activity updated through activity FIRA22 from case FIR03-00343.
Plan assigned to (Bill)6/30/2003 8/5/2003 DONE
DetailsBill Alexander
8/5/2003 07:51:11 JWA - activity updated through activity FIRA22 from case FIR03-00343.
PLANS/APPL TAKEN TO FRONT DESK  8/5/2003 DONE
DetailsBill Alexander
Telephone call  8/5/2003  
Inspection Record Card- Fire8/5/2003 8/5/2003 DONE
Issue and Print Permit  8/5/2003 DONE
resubmital required/ temp start
Sprinkler Plan Check7/24/2003 8/4/2003 PART
DetailsBill Alexander
Many items not addressed or addressed incorrectly. Resubmittal required prior to accepting plans that can be approved. Work may proceed at the contractor own risk.
Plan resubmittals received  7/24/2003  
DetailsBill Alexander
Telephone call  7/9/2003 DONE
Called John Graves - ###-#### (designer), asked for him to come down and we will go over the drawings/review to clarify problems and requirements. He indicated he will come visit about 2:20pm.
Sprinkler Plan Check6/30/2003 7/8/2003 FAIL
DetailsBill Alexander
See review notes FIR03-00343F attached.
Application received  6/30/2003