Permit Information
Permit NumberFIR03-00348
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 1480 S KIMBALL WAY
Project Namealm - Blackeagle Lot 4
Customer Number 
ePlanReview 
Description
New Fire Alarm system for sprinkler monitoring and HVAC shutdown.

The associated building permit (BLD 02-03001) is to construct a new 12,500 square foot, one story, steel structural frame with metal stud exterior walls office shell building and related site improvements. This is a shell permit only and occupany is approved under this permit. Separate tenant improvement permits are required to finish this building for occupany. This building is fully fire sprinklered. All construction per the approved plans and attached comment list. Blackeagle Lot 4 Shell Building DRH02-00186/PC#786-02/JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/28/20037/29/20037/29/2003APASS
DetailsTroy Cobbley
fire alarm finaled 7/29/2003 9:22:41 AM
DOC - Permit Finaled7/29/20037/29/20037/29/2003APASS
DetailsTroy Cobbley
Finaled by inspector at 7/29/2003 9:22:46 AM
INSP-Final Inspection7/28/20037/28/20037/28/2003PNR
DetailsRick Jackson
Rick, This is other of the two projects that we spoke about this morning. They are right next to each other in the Blackeagle complex. Troy only had three comments for each building. 1.) Provide 18AH Batteries, 2.) Provide sinage on the riser room door, and 3.) provide definitions of the zones at the monitoring service. I will call you around noon to verify if you will have time this afternoon to final these out. Thanks, Jason Minnick c-###-####; Phone #: ###-#### Internet Inspection Request from: Jason Minnick; Phone #: ###-#### Internet Inspection Request from: Jason Minnick didn't test this system as this had the same problem as 9149 Blackeagle 7/28/2003 3:11:34 PM
INSP-Final Inspection7/24/20037/25/20037/25/2003AFAIL
DetailsTroy Cobbley
Provide 18ah batteries for the fire alarm panel, provide signage on the door. resend signals since all alarms came in as undefined at the central station 7/25/2003 10:03:33 AM
Plan assigned to (SAM)7/1/2003 7/3/2003 DONE
7/3/2003 11:16:57 M_F - activity updated through activity FIRA22 from case FIR03-00348.
Alarm Plan Check  7/3/2003 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  7/3/2003 DONE
Telephone call  7/3/2003 DONE
LEFT MESS THAT PERMIT IS READY & NO FEES
Issue permit  7/3/2003 DONE
Application received  7/1/2003