INSP-Final Inspection | 10/6/2003 | 10/7/2003 | 10/7/2003 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/6/2003 at 9:19:20 PM. Contact: ###-####.
|
DOC - Permit Finaled | 10/7/2003 | 10/7/2003 | 10/7/2003 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 10/7/2003 12:57:02 PM
|
INSP-Alarm Testing | 9/30/2003 | 10/1/2003 | 10/1/2003 | A | FAIL |
Troy Cobbley
|
|
|
provide nfpa 72 forms, supervise all batteries, verify current draw 10/1/2003 1:10:28 PM
|
INSP-Alarm Testing | 9/29/2003 | 9/30/2003 | 9/30/2003 | A | FAIL |
Troy Cobbley
|
|
|
Provide NFPA forms, provide signage on door, 5amp battery needs supervised, verify current draw, mount map at facp 9/30/2003 12:04:04 PM
|
Telephone call | | | 7/8/2003 | | DONE |
|
|
|
CALLED RAND ,PERMIT READY NO FEES
|
Inspection Record Card- Fire | 7/8/2003 | | 7/8/2003 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/8/2003 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 7/2/2003 | | 7/7/2003 | | DONE |
|
|
|
7/7/2003 11:45:21 M_F - activity updated through activity FIRA22 from case FIR03-00357.
|
Telephone call | | | 7/7/2003 | | |
|
|
|
Phoned Rand at Alarm Star then Peter Rockwell at Glancey and Rockwell to confirm no occupants are moving in based upon adding a notification applicance to one of the offices. For future only.
|
Alarm Plan Check | | | 7/7/2003 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/7/2003 | | DONE |
|
|
|
|
Miscellaneous action | | | 7/3/2003 | | DONE |
|
|
|
Faxed Sam's Transmittal for additional information on the application. Alarm Star only submitted one set of prints. Review on hold until receipt of second set of prints.
|
Application received | | | 7/2/2003 | | |
|
|
|
|