INSP-Final Inspection | 4/20/2004 | 4/20/2004 | 4/20/2004 | A | PASS |
Troy Cobbley
|
|
|
Fire alarm finaled on 1/8/2004 under FIR03-00658
|
DOC - Permit Finaled | 4/20/2004 | 4/20/2004 | 4/20/2004 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 4/20/2004 9:23:16 AM
|
INSP-Final Inspection | 11/10/2003 | 11/10/2003 | 11/10/2003 | A | PART |
Troy Cobbley
|
|
|
Temp occupancy given until the fire alarm system has been approved, installed and tested per Dave Millers permission
|
INSP-Sprinkler Rough-in/Hydro | 10/30/2003 | 10/31/2003 | 10/31/2003 | A | PASS |
Troy Cobbley
|
|
|
wet system hydro test is ok 10/31/2003 1:49:46 PM
|
INSP-Sprinkler Rough-in/Hydro | 10/23/2003 | 10/24/2003 | 10/24/2003 | A | PART |
Troy Cobbley
|
|
|
rough-in items from the first two inspections have been taken care of. Items at the riser still need to be completed. Hydro test failed. 10/24/2003 1:02:37 PM
|
INSP-Sprinkler Rough-in/Hydro | 10/6/2003 | 10/7/2003 | 10/7/2003 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/6/2003 at 1:41:13 PM. Contact: ###-####. okay to cover 2nd floor only except room 209 as it has protective cover on head; the branch line on the north side of the new addition is not installed; the new wet part of the riser is not complete; canopies not installed on all 401 heads; will need spare heads in head box; branch line on east side not complete; this building will now have over 20 heads and will require monitoring and does not have complete sprinkler coverage 10/7/2003 3:24:35 PM
|
INSP-Sprinkler Rough-in/Hydro | 10/1/2003 | 10/2/2003 | 10/2/2003 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/1/2003 at 2:01:10 PM. area on first floor okay to cover except by the NE area by stair as SSU and SSP are too close together - reinspection needed to cover this area; sidewall installed under stair instead of pendant as shown on plans 10/2/2003 9:52:07 AM
|
Inspection Record Card- Fire | 8/1/2003 | | 8/1/2003 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/1/2003 | | DONE |
|
|
|
|
Sprinkler Plan Check | 7/25/2003 | | 7/31/2003 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/31/2003 | | DONE |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 7/9/2003 | | 7/31/2003 | | DONE |
|
|
|
7/31/2003 10:01:09 JWA - activity updated through activity FIRA22 from case FIR03-00375.
|
Plan resubmittals received | | | 7/25/2003 | | DONE |
|
|
|
|
Telephone call | | | 7/22/2003 | | DONE |
|
|
|
Review failed called for pick up
|
Sprinkler Plan Check | 7/9/2003 | | 7/21/2003 | | FAIL |
Bill Alexander
|
|
|
A. Second floor cavity protection is not considered a "small room" and will not be allowed to be spaced as such. Must meet 5-6.2.2.
B. Light Hazard protection may be designed for up to 225-ft/2 spacing (with exceptions) and this design submitted (was verified for a maximum spacing of 186-ft/2 for densities of .10. Limits for small room rule allow spacing off one wall up to 9'-0", but maximum allowable area of protection cannot exceed the design proven which is: 186-ft/2. Office #205 even exceed maximum allowed if proven at 225-ft/2?
C. Trapeze hangers appear to be used for the roof main piping? Plans provide not location of roof truss supports. Include the location of truss support, span and provide the pipe size and type installing with the trapeze hangers. Where a pipe is suspended from a pipe trapeze of a diameter less than the diameter of the pipe being supported, ring, strap, or clevis hangers of the size corresponding to the suspended pipe shall be used on both ends. Include ring sizes on the trapeze. (6-1.1.3)
D. Provide data submittals on the "Riser Check" installing.
E. Show and/or provide a forward flow backflow test connection in accordance with 5-15.4.6.1 for provisions of meeting NFPA 13:10-2.6. Calculations provided (faxed) do not verify flows through piping out of this structure.
|
Miscellaneous action | | | 7/21/2003 | | DONE |
|
|
|
Took failed plans to the front "call" desk for calling and returning.
|
Application received | | | 7/9/2003 | | |
|
|
|
|