Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberFIR03-00399
StatusFinaled
Name THE SECURITY GROUP
Site Address 12601 W EXPLORER DR Unit: 250
Project Namealm - ZASIO-2ND FLR
Customer Number 
ePlanReview 
Description
The addition of 19 duct detectors, 12 fire/smoke dampers with associated in-duct smoke detectors and one notification device to an existing sprinkler monitoring fire alarm system with HVAC shutdown and elevator recall.

The associated building permit (BLD 02-02987) is to construct a 8,842 square foot office tenant space located on the 22,000 square foot 2nd floor of a 44,000 square foot, 2 story, building. Work is to included tenant demising walls, a restroom accessible to the disabled, interior nonbearing walls, interior finishes, interior doors and windows, and suspended ceilings all per approved drawings and plan review conditions on file. The fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. (ZASIO - SUITE 250) This building is fire sprinklered for building area increase. **CJW**

The associated building permit (BLD 02-02988) is to construct a 5,375 square foot office tenant space located on the 22,000 square foot 2nd floor of a 44,000 square foot, 2 story, building. Work is to included tenant demising walls, interior nonbearing walls, interior finishes, interior doors, and suspended ceilings all per approved drawings and plan review conditions on file. The fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. (BRIGHTON CORPORATION - SUITE 200) This building is fire sprinklered for building area increase. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled8/22/20038/22/20038/22/2003PPASS
DetailsTroy Cobbley
Finaled by inspector at 8/22/2003 3:34:51 PM
INSP-Final Inspection8/22/20038/22/20038/22/2003PPASS
DetailsTroy Cobbley
DOC - Permit Finaled8/22/20038/22/20038/22/2003PPASS
DetailsTroy Cobbley
Finaled by inspector at 8/22/2003 3:27:28 PM
INSP-Alarm Testing8/20/20038/21/20038/21/2003ACANC
DetailsTroy Cobbley
technical problems with the induct detector circuit 8/21/2003 3:36:25 PM
INSP-Final Inspection8/13/20038/14/20038/14/2003PFAIL
DetailsTroy Cobbley
mike; Phone #: ###-#### The sample tube duct smoke detectors that are being used for smoke damper operation are not listed for use on the 8" round duct, provide access to all dampers, test power supervision for the elevator, test the two duct smoke detectors being used for damper operation at the entrance to suite 200. All items tested are listed on the approved plans 8/14/2003 4:36:57 PM
INSP-Alarm Testing8/12/20038/13/20038/13/2003PCANC
DetailsRick Jackson
Scheduled by a contractor via Hello! on 8/12/2003 at 2:34:17 PM. Contact: ###-####. rescheduled for 8/14 as I was delayed on another permit 8/13/2003 5:22:28 PM
Issue and Print Permit  8/8/2003 DONE
Plan assigned to (SAM)7/17/2003 8/7/2003 DONE
8/7/2003 16:16:54 M_F - activity updated through activity FIRA22 from case FIR03-00399.
Alarm Plan Check  8/7/2003 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  8/7/2003 DONE
Inspection Record Card- Fire8/7/2003 8/7/2003 DONE
Telephone call  8/7/2003  
Plan resubmittals received  8/4/2003  
Alarm Plan Check  7/29/2003 FAIL
Resubmittal Required. Faxed comments to Michael Ford 7/29/2003.
Telephone call  7/23/2003  
Spoke with Michael Ford. I requested that he stop by and mark up his drawings to show existing devices and to update the riser diagram. He stated he would drop by.
Application received  7/17/2003