DOC - Permit Finaled | 8/22/2003 | 8/22/2003 | 8/22/2003 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 8/22/2003 3:34:51 PM
|
INSP-Final Inspection | 8/22/2003 | 8/22/2003 | 8/22/2003 | P | PASS |
Troy Cobbley
|
|
|
|
DOC - Permit Finaled | 8/22/2003 | 8/22/2003 | 8/22/2003 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 8/22/2003 3:27:28 PM
|
INSP-Alarm Testing | 8/20/2003 | 8/21/2003 | 8/21/2003 | A | CANC |
Troy Cobbley
|
|
|
technical problems with the induct detector circuit 8/21/2003 3:36:25 PM
|
INSP-Final Inspection | 8/13/2003 | 8/14/2003 | 8/14/2003 | P | FAIL |
Troy Cobbley
|
|
|
mike; Phone #: ###-#### The sample tube duct smoke detectors that are being used for smoke damper operation are not listed for use on the 8" round duct, provide access to all dampers, test power supervision for the elevator, test the two duct smoke detectors being used for damper operation at the entrance to suite 200. All items tested are listed on the approved plans 8/14/2003 4:36:57 PM
|
INSP-Alarm Testing | 8/12/2003 | 8/13/2003 | 8/13/2003 | P | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 8/12/2003 at 2:34:17 PM. Contact: ###-####. rescheduled for 8/14 as I was delayed on another permit 8/13/2003 5:22:28 PM
|
Issue and Print Permit | | | 8/8/2003 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 7/17/2003 | | 8/7/2003 | | DONE |
|
|
|
8/7/2003 16:16:54 M_F - activity updated through activity FIRA22 from case FIR03-00399.
|
Alarm Plan Check | | | 8/7/2003 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/7/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/7/2003 | | 8/7/2003 | | DONE |
|
|
|
|
Telephone call | | | 8/7/2003 | | |
|
|
|
|
Plan resubmittals received | | | 8/4/2003 | | |
|
|
|
|
Alarm Plan Check | | | 7/29/2003 | | FAIL |
|
|
|
Resubmittal Required. Faxed comments to Michael Ford 7/29/2003.
|
Telephone call | | | 7/23/2003 | | |
|
|
|
Spoke with Michael Ford. I requested that he stop by and mark up his drawings to show existing devices and to update the riser diagram. He stated he would drop by.
|
Application received | | | 7/17/2003 | | |
|
|
|
|