INSP-Final Inspection | 11/30/2005 | 11/30/2005 | 11/30/2005 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 11/1/2005 | 11/4/2005 | 11/4/2005 | A | FAIL |
Troy Cobbley
|
|
|
Need to provide outside control for the fire sprinkler riser that is associated with this upgrade. This was verified with Bill Alexander. Information was originally requested under review note C but not provided.
|
Case Summary | | | 10/21/2005 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 7/20/2004 | | DONE |
|
|
|
|
(F) Reprint permit | | | 7/20/2004 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 7/29/2003 | | 7/19/2004 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 7/16/2004 | | 7/19/2004 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/19/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/19/2004 | | 7/19/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/19/2004 | | DONE |
|
|
|
|
Telephone call | | | 7/19/2004 | | DONE |
|
|
|
PERMIT READY AND FEE DUE
|
Miscellaneous action | | | 7/16/2004 | | DONE |
Bill Alexander
|
|
|
Requested information on the status in responding to this permit review comments which failed initial review. No information available. (07/15/04)
Only response to date is "unknown" from Jeff Anderson and Ron Stenquist.
|
Plan resubmittals received | | | 7/16/2004 | | DONE |
|
|
|
|
Telephone call | | | 8/7/2003 | | DONE |
|
|
|
called Jeff left message to pick up plan
|
Sprinkler Plan Check | 7/29/2003 | | 8/6/2003 | | FAIL |
Bill Alexander
|
|
|
Loop is not constructed to code and plans lack information which includes forward flow outlet, pipe types, riser detail missing (lacking control valve in calcs?), UG calced for PVC (which system would appear to be older than that?) and lacks repair gate in calcs. Riser appears to be located in the middle of the structure? Antifreeze using is not identified and valve not tampered.
|
Miscellaneous action | | | 8/6/2003 | | DONE |
|
|
|
Plans returned to front desk for returning, revising and resubmittal action.
|
Application received | | | 7/29/2003 | | |
|
|
|
|