Permit Information
Permit NumberFIR03-00424
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 3439 N COLE RD
Project NameSPR COLE VILLAGE CANOPY #4
Customer Number 
ePlanReview 
Description
COLE VILLAGE CANOPY #4 - To replace a defective 2" RP Backflow Preventer located on the east exterior canopy between column lines 24 and 35, or fourth canopy from the south off of Ustick Rd. Also includes modification from the 3" supply tap from at above the ceiling to 21/2" pipe up to the backflow device. This fire permit is from an inspection upgrade and not attached to any building permit. The fire sprinkler system work shall comply with IFC 2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/30/200511/30/200511/30/2005PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection11/1/200511/4/200511/4/2005AFAIL
DetailsTroy Cobbley
Need to provide outside control for the fire sprinkler riser that is associated with this upgrade. This was verified with Bill Alexander. Information was originally requested under review note C but not provided.
Case Summary  10/21/2005 DONE
CHANGE STATUS TO (ISS)  7/20/2004 DONE
(F) Reprint permit  7/20/2004 DONE
Plan assigned to (Bill)7/29/2003 7/19/2004 DONE
DetailsBill Alexander
Sprinkler Plan Check7/16/2004 7/19/2004 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  7/19/2004 DONE
Inspection Record Card- Fire7/19/2004 7/19/2004 DONE
Permit Ready to Issue  7/19/2004 DONE
Telephone call  7/19/2004 DONE
PERMIT READY AND FEE DUE
Miscellaneous action  7/16/2004 DONE
DetailsBill Alexander
Requested information on the status in responding to this permit review comments which failed initial review. No information available. (07/15/04)

Only response to date is "unknown" from Jeff Anderson and Ron Stenquist.
Plan resubmittals received  7/16/2004 DONE
Telephone call  8/7/2003 DONE
called Jeff left message to pick up plan
Sprinkler Plan Check7/29/2003 8/6/2003 FAIL
DetailsBill Alexander
Loop is not constructed to code and plans lack information which includes forward flow outlet, pipe types, riser detail missing (lacking control valve in calcs?), UG calced for PVC (which system would appear to be older than that?) and lacks repair gate in calcs. Riser appears to be located in the middle of the structure? Antifreeze using is not identified and valve not tampered.
Miscellaneous action  8/6/2003 DONE
Plans returned to front desk for returning, revising and resubmittal action.
Application received  7/29/2003