Information based on query as of Thursday, September 24, 2026.
Permit Information
Permit NumberFIR03-00425
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 100 S 6TH ST
Project NameSPR China Blue Bar - T.I.
Customer Number 
ePlanReview 
Description
(CHINA BLUE BAR) To modify, add and relocate fire sprinkler protection and piping for the remodel of an existing 18,348-ft/2 (5,565-ft/2 basement, 8,006-ft/2 first floor, 4,777-ft/2 second floor) for a new bar. Fire sprinkler work is related to complete protection for this tenant throughout, including basement and related elevated platforms, and cavities relating to the T.I. and existing portions of previously sprinklered areas. The building is fire sprinklered for story increase and because the fire area exceeds 5,000 square feet and the occupant load exceeds 300. The fire sprinkler system shall comply with NFPA 13-1999 as regulated by the Fire Department. All fire sprinklers and related appurtenance within this permit work scope shall meet current NFPA 13-1999 standards, comply with the IFC-2000 and attached review comment and conditions list, which is regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, in order to provide witness verification of compliance in meeting minimum code standards. Shell sprinklers for un-sprinklered areas of the building are currently being installed under FIR03-00368. A demolition permit was also issued under FIR03-00325, which must be completed prior to completion (is not to completed to date). This permit is attached to building permit: BLD03-00830.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/15/200312/15/200312/15/2003PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/15/2003 at 10:18:09 AM.
DOC - Permit Finaled12/15/200312/15/200312/15/2003PPASS
DetailsRick Jackson
Finaled by inspector at 12/15/2003 2:16:51 PM
Inspection Record Card- Fire12/10/2003 12/10/2003 DONE
Permit Ready to Issue  12/10/2003 DONE
Telephone call  12/10/2003 DONE
Spoke with John and told him permit is ready & fees
Issue and Print Permit  12/10/2003 DONE
INSP-Final Inspection12/8/200312/9/200312/9/2003AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/8/2003 at 3:16:35 PM. need remote area in restrooms recalc'd as additional heads are not shown on plans 12/9/2003 10:24:41 AM
Plan resubmittals received  12/9/2003 DONE
Sprinkler Plan Check12/9/2003 12/9/2003 PASS
DetailsBill Alexander
Plan/filed changes, corrections. Added sprinkler head in remote Area #2. Calced area is not
Plan assigned to (Bill)12/9/2003 12/9/2003 DONE
PLANS/APPL TAKEN TO FRONT DESK  12/9/2003 DONE
DetailsBill Alexander
INSP-Sprinkler Rough-in/Hydro12/5/200312/8/200312/8/2003AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/5/2003 at 4:18:05 PM. will need the remote area (restrooms) recalc'd per Bill Alexander as there are more heads than shown on plans; provide as-builts for the changes made to DJ area and restrooms; add head gaurds for heads under stairs; heads obstructed/overspaced by ductwork at new bar on first floor under another FIR permit 12/8/2003 10:13:01 AM
Issue and Print Permit  9/23/2003 DONE
Sprinkler Plan Check9/22/2003 9/22/2003 PASS
DetailsBill Alexander
Plans approved with comments
PLANS/APPL TAKEN TO FRONT DESK  9/22/2003 DONE
DetailsBill Alexander
Inspection Record Card- Fire9/22/2003 9/22/2003 DONE
Permit Ready to Issue  9/22/2003  
Telephone call  9/22/2003 DONE
left mess that permit is ready
Plan resubmittals received  9/2/2003 DONE
Inspection Record Card- Fire8/19/2003 8/19/2003 DONE
Telephone call  8/19/2003 DONE
This set of plans superceded by 9/2/03 resubmittal per Sam Rogers 9/22/03 BAM
Plan assigned to (Bill)8/8/2003 8/18/2003 DONE
DetailsBill Alexander
8/18/2003 15:55:35 JWA - activity updated through activity FIRA22 from case FIR03-00425.
Sprinkler Plan Check8/15/2003 8/18/2003 PART
DetailsBill Alexander
Plan is not approved. Work may proceed at contractors risk.
Plan assigned to (Bill)8/15/2003 8/18/2003 DONE
DetailsBill Alexander
8/18/2003 15:55:35 JWA - activity updated through activity FIRA22 from case FIR03-00425.
PLANS/APPL TAKEN TO FRONT DESK  8/18/2003 DONE
DetailsBill Alexander
This is a partial approval to proceed less approved plans.
Plan resubmittals received  8/15/2003  
Sprinkler Plan Check8/8/2003 8/14/2003 FAIL
DetailsBill Alexander
Documents were bundled incorrectly in the 6 sets submittal provided. Returned to sender for correcting.
Telephone call  8/14/2003 DONE
Documents are bundled incorrectly in the 6 sets submittal provided. Called Randy Bowron amd requested De Best send someone down to straighten the mess prior to reviewing. Resubmittal set aside untill then.
Plan resubmittals received  8/8/2003  
Plan resubmittals received  8/5/2003 DONE
per bill
Plan assigned to (Bill)8/5/2003 8/5/2003 DONE
DetailsBill Alexander
Sprinkler Plan Check8/5/2003 8/5/2003 FAIL
DetailsBill Alexander
Not designed for pyrotechnics (as requesting by the tenant).
Telephone call  8/5/2003 DONE
Received a call from Bob Brady FPE (CSHQA) who is now involved with this project and the proposed pyrotechnics show relating to (protection requirements). He indicated a design for OH-2 would be sufficient. I requested a letter addressing the same and include the areas of performances shall be addressed the same, and relay the information to the Fire Sprinkler Contractor for design submittals and approval.
Telephone call  8/5/2003 DONE
Contacted Jim Danes - De Best Fire Protection and indicated I have received plans that show light hazard protection and pyrotechnics will be involved. They should contact Bob Brady (CSHQA) and coodinate an approved design for the same and what shall I do with this submittal. He indicated to put it asside for now.
Plan assigned to (Bill)7/29/2003 7/30/2003 DONE
DetailsBill Alexander
Sprinkler Plan Check7/29/2003 7/30/2003 FAIL
DetailsBill Alexander
Sprinkler plans require verification of piping design through hydraulic calculations since approximately 50 heads have been installed on ONE 1½" line in the same areas on the first floor alone? Office, restrooms, hallway, janitors closet, cooler and breakroom, stairs, and foyer, (14 heads) have been installed on 1" piping and separation must be verified, in order to accept this piping (room design method) to apply, or calculations must be provided.
Telephone call  7/30/2003 DONE
Called designer (John Venche) and gave information on first glance review. Asked if I should contiune in the review and was instructed "No." "I will verify it with calculations and resubmit." Will not proceed until verification of protection is provided.
Miscellaneous action  7/30/2003 DONE
Emailed failed review (document).
Application received  7/29/2003  
Inspection Record Card- Fire8/19/2003