INSP-Sprinkler Rough-in/Hydro | 2/19/2004 | 2/19/2004 | 2/19/2004 | P | PASS |
Rick Jackson
|
|
|
Final inspection for China Blue; Phone #: ###-#### Internet Inspection Request from: Robert Bailey
|
INSP-Final Inspection | 2/19/2004 | 2/19/2004 | 2/19/2004 | P | PASS |
Rick Jackson
|
|
|
final okay
|
DOC - Permit Finaled | 2/19/2004 | 2/19/2004 | 2/19/2004 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 2/19/2004 1:53:56 PM
|
INSP-Final Inspection | 1/7/2004 | 1/9/2004 | 1/9/2004 | P | FAIL |
Rick Jackson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Robert Bailey need updated maps and record of completion 1/9/2004 4:10:13 PM
|
INSP-Final Inspection | 1/6/2004 | 1/7/2004 | 1/7/2004 | A | NR |
Rick Jackson
|
|
|
Aaron; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes talked to Robert and he wilol reschedule for 1/9/04 1/7/2004 3:28:32 PM
|
INSP-Final Inspection | 10/8/2003 | 10/9/2003 | 10/9/2003 | P | FAIL |
Rick Jackson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Robert Bailey NAC circuits aren't wired as shown on plans; need map with initiating devices; damper #2 detector dirty; NFPA 72 record of completion; 10/9/2003 4:35:02 PM
|
Issue and Print Permit | | | 9/24/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/23/2003 | | 9/23/2003 | | DONE |
|
|
|
|
Telephone call | | | 9/23/2003 | | DONE |
|
|
|
Called and told permit ready & fees
|
Permit Ready to Issue | | | 9/23/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 9/22/2003 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/22/2003 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 7/30/2003 | | 9/22/2003 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/12/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 8/29/2003 | | FAIL |
|
|
|
Resubmittal required for items #3 and #9. Faxed comments to Tom Kyle 8/29/2003.
|
Plan resubmittals received | | | 8/18/2003 | | |
|
|
|
|
INSP-Final Inspection | 8/7/2003 | 8/6/2003 | 8/7/2003 | P | PART |
Rick Jackson
|
|
|
performed inspection from 5-8:30 pm; NAC in basement not sync'd; horn in VIP not temporal; need to verify batteries and voltage drops
|
Alarm Plan Check | | | 8/6/2003 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Tom Kyle 8/5/2003.
|
Meeting | | | 8/6/2003 | | |
|
|
|
Meeting to discuss comments.
|
Miscellaneous action | | | 8/6/2003 | | |
|
|
|
Tom Kyle (Mountain Alarm) received copy of the comments, cut sheets and marked up plans/riser.
|
Plan resubmittals received | | | 8/6/2003 | | DONE |
|
|
|
|
Meeting | | | 8/6/2003 | | |
|
|
|
Met with Tom Kyle to receive his resubmittal drawings.
|
Application received | | | 7/30/2003 | | |
|
|
|
|