FIR-Aging Inspection | 7/8/2005 | 7/8/2005 | 7/8/2005 | | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 7/8/2005 | 7/8/2005 | 7/8/2005 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 10/7/2004 | 10/7/2004 | 10/7/2004 | P | PASS |
Troy Cobbley
|
|
|
Fire alarm system finaled
|
INSP-Alarm Testing | 8/30/2004 | 8/30/2004 | 8/30/2004 | P | PART |
Troy Cobbley
|
|
|
Provide connection to the hood. Suppression system still needs installed and provide NFPA 72 forms at final 8/30/2004 4:33:48 PM
|
INSP-Final Inspection | 8/25/2004 | 8/26/2004 | 8/26/2004 | P | FAIL |
Troy Cobbley
|
|
|
hvac unit at point 74 did not shutdown. Could not get unit at point 75 to start. Kitchen door does not latch. Flow switch at point 489 did not operate within 90 seconds. Still need to connect hood (point reports), the remaining duct smoke detectors and sprinkler risers and all of the items listed above that didn't work the first time 8/26/2004 3:45:56 PM
|
INSP-Final Inspection | 8/19/2004 | 8/19/2004 | 8/19/2004 | P | PART |
Troy Cobbley
|
|
|
Still need to test sprinkler risers, door closures, duct detectors and hood system 8/19/2004 4:24:18 PM
|
INSP-Final Inspection | 8/16/2004 | 8/17/2004 | 8/17/2004 | A | PART |
Troy Cobbley
|
|
|
All of the notification devices in the central area (retirement) were tested. Spot smoke detectors in the central (retirement) area were tested. Second floor west central corridor smokes are mislabeled as first floor. 8/17/2004 4:01:41 PM
|
INSP-Final Inspection | 7/8/2004 | 7/8/2004 | 7/8/2004 | P | PART |
Troy Cobbley
|
|
|
Center retirement area needs inspection. Sprinkler system for the I-1 area and all elevators need tested. 7/9/2004 8:28:10 AM
|
INSP-Final Inspection | 7/7/2004 | 7/7/2004 | 7/7/2004 | P | PART |
Troy Cobbley
|
|
|
Inspection was for the second floor of the I-2 area. See city approved plans for locations and deficencies 7/7/2004 3:53:15 PM
|
INSP-Final Inspection | 7/1/2004 | 7/1/2004 | 7/1/2004 | P | PART |
Troy Cobbley
|
|
|
Tested I-2 section, first floor. See approved plans for specific location and correction. 7/1/2004 4:16:36 PM
|
INSP-Final Inspection | 6/15/2004 | 6/15/2004 | 6/15/2004 | P | PART |
Troy Cobbley
|
|
|
Inspection was for the assisted living area on the southwest corner of the building. All items tested except for the sprinkler flow alarms and the PIV. Some items need corrected. See city approved plans for specific items. 6/15/2004 4:08:11 PM
|
FIR-Aging Inspection | 12/17/2003 | 12/17/2003 | 12/17/2003 | | NR |
Troy Cobbley
|
|
|
According to phil the work is in progress 12/17/2003 2:08:37 PM
|
Plan assigned to (SAM) | 8/12/2003 | | 9/17/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 9/17/2003 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/17/2003 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/17/2003 | | 9/17/2003 | | DONE |
|
|
|
|
Issue and Print Permit | | | 9/17/2003 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/3/2003 | | DONE |
|
|
|
|
Alarm Plan Check | | | 8/21/2003 | | FAIL |
|
|
|
Resubmittal required. Comments given to Phil Omas 8/21/2003.
|
Application received | | | 8/12/2003 | | |
|
|
|
|