Permit Information
Permit NumberFIR03-00471
StatusFinaled
Name PROTEX
Site Address 1105 N 13TH ST
Project Namealm - School-North Jr. High
Customer Number 
ePlanReview 
Description
To add six (6) smoke detectors and door hold-opens to an existing fire alarm system.

The associated building permit 10/7/2003 - (BLD 03-01529) is to replace doors and frames to meet a 1hr. occupancy separation to the gym and install two new walk-in coolers and additional work in the kitchen area per approved plans and attachments. (NORTH JR HIGH)(KITCHEN REMODEL)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/2/20102/2/20102/9/2010PPASS
DetailsForrest France
Permit finaled, okay per subsequent work.
INSP-Final Inspection11/10/200311/12/200311/12/2003PFAIL
DetailsRick Jackson
Please note school is in session until 3:30; Phone #: ###-#### Internet Inspection Request from: Terry Owsley need approved drawings; need map updated and zone 4 identified with new smokes added; tested the six smokes for door holders and okay; the plan review notes indicated duct detectors but they were not part of this project 11/12/2003 4:07:41 PM
INSP-Sprinkler Rough-in/Hydro11/10/200311/12/200311/10/2003PCANC
DetailsRick Jackson
Please note that school is in session until 3:30. Have a great day; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
Issue and Print Permit  10/17/2003 DONE
INSP-Conference10/14/200310/14/200310/14/2003PPART
DetailsRick Jackson
stopped by the school and there are boxes with wire at locations where smoke detectors would be installed for release of new doors at serving line 10/14/2003 2:59:38 PM
Inspection Record Card- Fire10/8/2003 10/8/2003 DONE
Permit Ready to Issue  10/8/2003 DONE
Telephone call  10/8/2003 DONE
permit ready and fee due
Telephone call  10/8/2003 DONE
Spoke with Rob told permit ready & new fees due to penalty fee
Telephone call  10/8/2003 DONE
Received a phone call from the architect to get clarification on "work without a permit". They state the contractor assumed that installing cinduit and wire (no devices) did not constitute installing the fire alarm components without a permit. I stated that it was working without a permit.
Plan assigned to (SAM)8/19/2003 10/7/2003 DONE
Alarm Plan Check  10/7/2003 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  10/7/2003 DONE
Plan resubmittals received  9/24/2003  
Alarm Plan Check  9/2/2003 FAIL
Resubmittal required. Comments faxed to Rob Ahten 9/2/2003.
Application received  8/19/2003