Permit Information
Permit NumberFIR03-00474
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 8172 W OVERLAND RD
Project NameSPR UG Venture Development Grp
Customer Number 
ePlanReview 
Description
Venture Development Group Retail Shell Building - To install approximately 240'-0 of 6" C-900 class 50 underground fire service main from the property line in Overland Rd., North, routing along the East side of the structure, to the North East corner of the proposed 18,154-ft/2, one story type VB, fully fire sprinklered retail shell building. Separate plans and permits required for the overhead system in the building. Fire sprinklers are used for area increase. The fire sprinkler underground work shall comply with NFPA 13-1999, NFPA 24-1995 and the IFC-2000, attached review comment and conditions list, all as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD03-000706.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled12/10/200312/10/200312/10/2003APASS
DetailsTroy Cobbley
INSP-Supply line flush12/2/200312/2/200312/2/2003PPASS
DetailsRick Jackson
UG flush only okay 12/2/2003 3:36:44 PM
INSP-Sprinkler Rough-in11/10/200311/12/200311/12/2003APART
DetailsRick Jackson
Bruce; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes okay to cover outside canopy - plans show 155 heads but 200 installed; dry pendants not installed 11/12/2003 8:57:44 AM
INSP-Sprinkler Rough-in/Hydro10/6/200310/6/200310/6/2003PPART
DetailsRick Jackson
BRUCE; Phone #: ###-#### Internet Inspection Request from: Annette Moore UG hydro okay 10/6/2003 4:05:39 PM
INSP-Sprinkler Rough-in8/22/20038/25/20038/25/2003APART
DetailsTroy Cobbley
Underground sprinkler piping is OK to cover 8/25/2003 10:47:09 AM
Plan assigned to (Bill)8/19/2003 8/22/2003 DONE
DetailsBill Alexander
8/22/2003 12:48:13 JWA - activity updated through activity FIRA22 from case FIR03-00474.
Sprinkler Plan Check8/21/2003 8/22/2003 DONE
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  8/22/2003 DONE
DetailsBill Alexander
Miscellaneous action  8/22/2003 DONE
Emailed review and notice of approval 12:50 pm.
Inspection Record Card- Fire8/22/2003 8/22/2003 DONE
Telephone call  8/22/2003 DONE
left mess that permit is ready
Issue permit  8/22/2003 DONE
Plan resubmittals received  8/21/2003 DONE
Telephone call  8/20/2003 DONE
plans failed called to have them picked up
Sprinkler Plan Check8/19/2003 8/20/2003 FAIL
DetailsBill Alexander
Need the following:
1. Type and size of material the underground riser is being installed with,
2. Appurtenance/detail information of thrust protection for the same (riser).
3. Dimensioning of pipe from bottom of footing,
4. Dimension of riser pipe around the floor,
5. Depth of bury throughout,
6. Distance of underground following the structures footing,
7. Include a directional arrow,
8. Information addressed on the plans that the outside shutoff will be provided at the riser in a 1 hour fire separated fire sprinkler control room, or provide an outside control P.I.V. with tamper supervision, etc.
Miscellaneous action  8/20/2003 DONE
Emailed failed review and request list for resubmittals.
Application received  8/19/2003