Final inspection | | | 3/15/2010 | | DONE |
|
|
|
This permit has been finaled since all work required under the scope of work was completed. However, there are issues outside of the scope of work that needs to be addressed. Therefore, this permit has been referred to the prevention officer. Please see below:
Ray,
This permit has some outstanding issues that I think could do with some of your attention when you are in the area and get the chance.
The one sprinkler head has been taken care of and finaled. However, the inspector noted several items that were outside of the scope of work for this permit but are still required items.
Let me know if you have any questions.
Thank you for the help.
|
Miscellaneous action | | | 3/12/2010 | | DONE |
|
|
|
Sent email requesting project status.
|
INSP-Final Inspection | 9/4/2003 | 9/4/2003 | 9/4/2003 | P | FAIL |
Rick Jackson
|
|
|
todd; Phone #: ###-#### Internet Inspection Request from: Annette Moore need smoke detector above fire alarm panel, manual pull station and audible alarm; need sign on riser room door - "Fire sprinkler controls"; need annual inspection report to verify Ames 2000 backflow preventor doesn't cycle open/closed; appears to need Knox box - couldn't locate 9/4/2003 1:20:05 PM
|
Issue permit | | | 9/2/2003 | | |
|
|
|
|
Inspection Record Card- Fire | 8/21/2003 | | 8/21/2003 | | DONE |
|
|
|
|
Telephone call | | | 8/21/2003 | | DONE |
|
|
|
left mess that permit is ready
|
Application received | | | 8/20/2003 | | |
|
|
|
|
Plan assigned to (Bill) | 8/20/2003 | | 8/20/2003 | | DONE |
|
|
|
8/20/2003 15:16:47 JWA - activity updated through activity FIRA22 from case FIR03-00476.
|
Alarm Plan Check | 8/20/2003 | | 8/20/2003 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/20/2003 | | DONE |
Bill Alexander
|
|
|
|